8-14
Drive Functions
Arranging the Home Switch
Fig. 8-9:
Selecting a reference mark via home switch
After starting the C0600 command, the dedicated point is detected when
the first reference mark signal occurs after the determined edge of the
home switch.
travel range limits
Fig. 8-10:
Arranging the home switch with regard to travel range limits
In the case of linear axes, the "activated" range of the home switch has to
reach beyond the next travel range limit. The home switch signal thereby
indicates the proximity of the end of the travel range if the reference travel
direction was appropriately selected. The travel range limit is not passed
during the homing procedure when the "activated" range of the home
switch signal begins with sufficient distance to the travel range limit!
The distance between dedicated point (first reference mark after home
switch signal) and travel range limit is sufficient if the drive can safely
shutdown the axis out of maximum homing velocity (S-0-0041) with
homing acceleration (S-0-0042), within the travel range. The following
applies to the minimum distance home switch-travel range limit:
x
v:
value in S-0-0041, Homing velocity
a:
value in S-0-0042, Homing acceleration
x
:
distance of the reference marks occurred at the axis - or –
RefMarks
value of S-0-0165 for distance-coded measuring system
x
:
minimum distance to travel range limit
HS_TrLimit
Fig. 8-11:
Minimum distance of home switch signal to travel range limit
MPH-02, MPB-02, MPD-02
home switch
switch cam
axis slide
mapped reference marks of motor encoder
correct implementation of "activated" range
of home switch signal
incorrect implementation of "activated" range
of home switch signal
reference travel direction
2
v
≥
+
x
HS_TrLimit
RefMarks
2
*
a
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
selected
reference mark
axis
DF0072v1.fh7
DF0075v1.fh7