hit counter script

Module Enable; Module Enclosure Tamper; One Or Two Batteries; Wireless Receiver - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
Settings
RPS supports the configuration of the Enclosure Tamper, page 238 on each of the Power
Supply modules.
Yes = Enable enclosure tamper, No = Disable enclosure tamper. Default setting is No.
RPS supports the configuration of the Module Enable, page 251 on each of the Power Supply
modules.
Yes = Enable module supervision, No = Disable module supervision. Default setting is No.
RPS supports the configuration of the One or Two Batteries, page 251 on each of the Power
Supply modules.
Switch Settings
Ref. Hardware Switch Settings > SDI2 Devices > B520 Power Supply switch settings, page 263
14.6.1

Module Enable

Default: No
Selections: Yes or No
Yes  Supervise the SDI2 module.
No    Do not supervise the SDI2 module.
This parameter indicates to the control panel if the SDI2 module should be supervised.
RPS Menu Location
SD12 > B520 Power Supply > Module Enable
14.6.2

Module Enclosure Tamper

Default: No - Disable
Selections:
Yes - Enable enclosure tamper input
No - Disable enclosure tamper input
This parameter enables the enclosure tamper switch input on the SDI2 module.
When the input is enabled and connected to a Bosch ICP-EZTS tamper switch installed in the
module enclosure, the control panel can create a tamper event when the enclosure door is
opened, or when the enclosure is removed from the wall.
RPS Menu Location
SDI2 > B520 Aux Power Supply > Enclosure Tamper
14.6.3

One or Two Batteries

Default: One
Selections: One or Two
This parameter specifies if 1 or 2 backup batteries are installed with the Auxiliary Power
Supply module.
RPS Menu Location
SDI2 Modules > B520 Aux Power Supply > One or Two Batteries
14.7

Wireless Receiver

The SDI2 bus of the control panel supports the B820 Inovonics SDI2 Wireless Interface
Module. The B820 module provides the ability to use wireless key fobs, repeaters and points
with the control panel.
Capacity
The control panel supports two types of SDI2 wireless interface modules:
Bosch Security Systems, Inc.
Program Entry Guide
SDI2 modules | en 251
2017.03 | 09 | F.01U.303.998

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B8512gB8512g-eB9512g-e

Table of Contents

Save PDF