Control Panel
Default: 0
Selections: 0-3600 (seconds)
–
–
When there are no towers present the control panel starts two timers, one for a
No Towers event, one for a No IP Address event. The control panel uses the duration set by
this Reporting Delay for No Tower parameter for both timers. If the cellular plug-in module
does not find a tower before the end of the delay, the control panel creates a No Towers event
and a No IP Address event at the same time.
The control panel creates a No Tower restoral event when one or more towers are available for
the duration set by this Reporting Delay for No Tower parameter.
The contro panel creates a No IP Address restoral event when the cellular plug-in module
successfully registers with one or more towers and receives an IP address.
Notice!
When one or more towers are available, 60 second delay for No IP Address event
If the cellular plug-in module successfully registers with one or more towers, but does not
receive an IP address within 60 seconds, the control panel creates a No IP Address event.
RPS menu location
SDI2 modules > IP Communicator > B450 Cellular > Reporting delay for no towers
14.5.7
SIM PIN
Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default: Blank
Selections: 4-8 numbers
This is an optional parameter. This parameter is only necessary if the SIM card uses a PIN for
security.
The SIM PIN is hidden on the display and appears as asterisks (********) when entered. If an
invalid SIM PIN is entered, an event is logged in history. A report is sent only if the report
function is enabled. If no SIM PIN is required, you can leave the field blank.
RPS menu location
SDI2 modules > IP Communicator > B450 Cellular > SIM PIN
14.5.8
Network Access Point Name (APN)
Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default: wyless.apn
Selections: 0-99 ASCII characters
Bosch Security Systems, Inc.
0 - Disabled.
1 to 3600 - Enabled.