Bosch rexroth IndraDrive Mi KCU02 Project Planning Manual page 62

Drive systems
Hide thumbs Also See for rexroth IndraDrive Mi KCU02:
Table of Contents

Advertisement

48/407
General data and specifications
Description
Temperature range
Relative humidity
Absolute humidity
Climatic category (IEC721)
Moisture condensation
Icing
KSM: Storage times
Bosch Rexroth AG R911335703_Edition 04
NOTICE
The DC bus capacitor unit KLC contains electrolytic capacitors which may
deteriorate during storage. When storing the DC bus capacitor unit KLC for a
longer period of time, run it once a year for at least 1 hour at DC bus voltage
U
.
DC
Ambient and operating conditions - storage
Symbol
Unit
T
°C
a_store
%
g/m
3
Tab. 4-5:
Ambient and operating conditions - storage
Additional measures must be taken on commissioning to preserve proper
functioning – irrespective of the storage time which may be longer than the
warranty period of our products. However, this does not involve any
additional warranty claims.
Motors
Storage time / months
Measures for commissioning
> 1
> 12
> 60
Visual inspection of all parts to be damage-free
Resurface the holding brake
Check the electric contacts to verify that they are free from
corrosion
Let the motor run in without load for one hour at 800 ... 1000 rpm
Measure insulation resistance. Dry the winding at a value of <
1kohm per volt rated voltage.
Replace bearing
Replace encoder
Tab. 4-6:
Measures before commissioning motors that have been stored over
a prolonged period of time
IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
DC bus capacitor unit
Risk of damage to the
KLC from long-term storage!
Value
-20 ... +55
5 ... 95
1 ... 29
1K3
Not allowed
Not allowed