Control Panel
Notice!
Switch 5 sets line termination for control panel ZONEX terminals
Follow the rules below to set switch 5 (switch 4 on D8128C OctoPOPIT).
If a D8125 POPEX module is connected to the control panel ZONEX 1 terminals, set switch 5
of all OctoPOPITs connected to those terminals to the OFF position.
If there is no D8125 POPEX module connected to the control panel ZONEX 1 terminals, set
switch 5 of only one OctoPOPIT connected to those terminals to the ON position.
If a D8125 POPEX module is connected to the control panel's ZONEX 2 terminals, set switch 5
of all OctoPOPITs connected to those terminals to the OFF position.
If there is no D8125 POPEX module connected to the control panel's ZONEX 2 terminals, set
switch 5 of only one OctoPOPIT connected to those terminals to the ON position.
Point Switches
To enable each point (sensor loop) on an OctoPOPIT, set its point switch to the ON position.
To disable each point (sensor loop) on an OctoPOPIT, set its point switch to the OFF position.
Notice!
Point switch 8 must be OFF for a D8128D set to points 121 to 127 or 241 to 247
For D8128D OctoPOPITs set to points 121 to 127 or points 241 to 247 you must set point
switch 8 to OFF.
The D8128C OctoPOPIT does not support points 121 to 127 or points 241 to 247.
RPS Menu Location
Hardware Switch Settings > D8128 OctoPOPIT Module switch settings
15.12
D8129 Octo-relay Module switch settings
ZONEX 1
Output
number
1 to 8
9 to 16
17 to 24
25 to 32
33 to 40
41 to 48
49 to 56
57 to 64
RPS Menu Location
Hardware Switch Settings > D8129 Octo-relay Module switch settings
Bosch Security Systems, Inc.
D8129 address switches
1
2
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
Program Entry Guide
Hardware switch settings | en 265
3
4
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ZONEX 2
5
Output
number
ON
65 to 72
ON
73 to 80
ON
81 to 88
ON
89 to 96
ON
97 to 104
ON
105 to 112
ON
113 to 120
ON
121 to 128
2017.03 | 09 | F.01U.303.998