en | Compliance Settings
Control Panel
PANEL WIDE PARAMETERS > Report Routing > Fire Reports > Fire Cancel
Set the PANEL WIDE PARAMETERS > Report Routing > Fire Reports > Fire Cancel parameter
for each Route Group (1 to 4) to No.
Figure 2.1: Fire Cancel
POINTS > Point Profiles (Point Indexes)
Configure Point Profiles 1, 4, and 6 as shown below.
It is important to configure the parameters in order.
Point Profile 1
Set Alarm Abort to: No.
Set Point Profile Text (First Language) to: Fire Panel Trouble.
Set Point Type / Response / Circuit Style > Point Type to: Fire Point.
Set Point Type / Response / Circuit Style > Circuit Style to: Single EOL (1KΩ) or
Single EOL (2KΩ).
Set Response to: 3.
Point Profile 4
Set Point Profile Text (First Language) to: Fire Panel Alarm.
Set Point Type / Response / Circuit Style > Point Type to: Fire Point.
Set Point Type / Response / Circuit Style > Circuit Style to: Single EOL (1KΩ),
Single EOL (2KΩ), or Dual EOL.
If you set Point Type / Response / Circuit Style > Circuit Style to Single EOL (1KΩ) or
Single EOL (2KΩ), set Response to: 1.
If you set Point Type / Response / Circuit Style > Circuit Style to Dual EOL, set Response to: 0.
Point Profile 6
Set Point Profile Text (First Language) to: Fire Panel Supervisory.
Set Point Type / Response / Circuit Style > Point Type to: Fire Point.
Set Point Type / Response / Circuit Style > Circuit Style to: Single EOL (1KΩ),
Single EOL (2KΩ), or Dual EOL.