Control Panel
Controlled Point Types, Single EOL Circuit Style, Point Response Selections
Armed
Circuit
State
State
Armed
Open
Armed
Short
Disarmed
Open
Disarmed
Short
Key: I = instant alarm, D = delayed alarm, T = trouble, blank = no response
Example: Point Type = Part On and Point Response = 8. Perimeter point with delayed alarm
response when armed (opened or shorted) and no response when disarmed.
Controlled Point Types, Dual EOL Circuit Style, Point Response Selections
Armed
Circuit
State
State
Armed
Open/
Short
Armed
Fault
Disarmed
Open/
Short
Disarmed
Fault
Key: I = instant alarm, D = delayed alarm, T = trouble, blank = no response
Example: Point Type = Part On and Point Response = 1. When the area is on (armed), a fault
on the point circuit creates a delayed alarm response. An open or short on the point circuit
creates an instant alarm.
When the area is off (disarmed), an open or short on the point circuit creates a point trouble.
There is no response for a fault on the point circuit.
Notice!
For Dual EOL Circuit Style, purchase second 1kΩ EOL separately
Order ICP-1K22AWG-10, package of 10 resistors.
Notice!
Control panel and B208 Octo-input firmware requirements for Dual EOL
To use the Dual EOL Circuit style, verify the control panel firmware is v3.01 or greater.
If you are using a B208 Octo-input Module, verify the module firmware is v2.1.1 or greater.
Controlled Point Types, No EOL Circuit Style, Point Response Selections
Armed
Circuit
State
State
Armed
Fault
Disarmed
Fault
Key: I = instant alarm, D = delayed alarm, T = trouble, blank = no response
Bosch Security Systems, Inc.
0
1
2
3
4
I
I
I
I
D
I
I
I
I
I
T
T
T
T
0
1
2
3
4
I
I
I
I
I
I
D
I
D
I
T
T
I
I
T
T
0
1
2
3
4
I
I
D
D
T
T
T
T
5
6
7
8
D
I
I
D
I
D
D
D
T
T
5
6
7
8
I
I
I
D
I
D
T
I
I
T
T
T
5
6
7
8
Program Entry Guide
9
A
B
C
D
I
I
I
I
I
I
I
I
I
I
T
I
I
T
I
9
A
B
C
D
9
A
B
C
D
2017.03 | 09 | F.01U.303.998
Points | en 187
E
F
I
T
I
I
T
I
E
F
E
F