128 en | Custom Functions
Notice!
When a Custom Function initiates, assigned functions run in order, 1 to 6
The control panel runs the functions assigned to a custom function consecutively. The panel
starts functions immediately after starting the previous function. It does not wait for the
previous function to finish.
Use the Delay function selection to create a delay between the start of two functions.
Parameter 1 configures the length of the delay (1 to 90 seconds).
For example: To toggle an output at the end of a Part On Delay with a 30 second exit delay,
set Function 1 to "Part On Delay", set Function 2 to "Delay" with Parameter 1 set to greater
than 30 seconds, and set Function 3 to "Toggle Output".
Notice!
Special Force Arm / Bypass Max rules for arming with Custom Functions
When a Custom Function includes an arming function (All On Delay, All On Instant, Part On
Instant, Part On Delay) special rules for the Force Arm/Bypass Max, page 93 limit for faulted
points apply.
If a user activates the Custom Function from a keypad using a shortcut or function key, from
an RF Keyfob, or by presenting their credential (card or token) to a reader or keypad,
and the Custom Function requires a passcode (Custom Function, page 157 = P),
then the control panel enforces the Force Arm / Bypass Max limit for faulted points. If the
number of faulted points exceeds the Force / Arm Bypass Max limit, the function fails The
control panel does not arm the Area. There is no indication at keypads for the failed function.
The control panel includes the user number in the arming event (history log and report).
If a user activates a Custom Function from a keypad using a shortcut or function key, from an
RF Keyfob, or by presenting their credential (card or token) to a reader or keypad,
and the Custom Function does not require a passcode (Custom Function, page 157 = E),
then the control panel enforces the Force Arm / Bypass Max limit for faulted points. If the
number of faulted points exceeds the Force / Arm Bypass Max limit, the function fails The
control panel does not arm the Area. There is no indication at keypads for the failed function.
The control panel does not include the user number in the arming event (history log and
report).
If a custom function is activated by a Sked, point, or automation, the control panel does not
enforce the Force Arm / Bypass Max limit for faulted points. The control panel arms all faulted
points, even if the Force Arm / Bypass Max limit is exceeded.
FUNCTION:
Click on a function name for information about that function.
Not In Use - This function is disabled and no functions after this will be performed.
All On Delay, page 219
All On Instant, page 220
Part On Delay, page 220
Part On Instant, page 220
Disarm, page 220
Extend Close, page 220
Bypass a Point, page 220
Unbypass a Point, page 220
Unbypass All Points, page 220
Reset Sensors, page 220
Turn Output On, page 220
Turn Output Off, page 221