Series
After power on, when no error happens, no run command, output active indi-
cates that the converter is ready for running.
1: Converter running
The output is active when the frequency converter is running and has fre-
quency output (including 0.00 Hz).
2: Converter DC-braking
The output is active when the converter is in the DC braking process at start-
ing or stopping process. See
page 210
and
chapter 12.8.9 "Stop Mode Configuration" on page
3: Converter running at zero speed
The output is active when the frequency converter is running at zero speed.
There is no output for this selection during dead zone time of rota-
tion direction change.
4: Speed arrival
This function is used to detect the difference between the output frequency
and the set frequency. The indicative signals are outputted when the differ-
ence between the output frequency and the set frequency is within the range
set in [E2.70], see
258.
5: Frequency level detection signal (FDT1)
6: Frequency level detection signal (FDT2)
See
chapter 12.10.5 "Frequency Detection Function" on page
7: Simple PLC stage complete
8: Simple PLC cycle complete
See
chapter 12.11 "E3: Multi-Speed and Simple PLC" on page
10: Converter undervoltage
The output is active when DC-bus voltage is lower than 230 VDC (1P 200 VAC
models) / 430 VDC (3P 400 VAC models). The output will be inactive when
DC-bus voltage resumes and becomes stable.
In addition, this digital output will be activated by any soft start error.
11: Converter overload pre-warning
See
chapter 12.2.12 "Converter Overload Pre-Warning" on page
12: Motor overload pre-warning
See
chapter 12.3.6 "Motor Overload Pre-Warning" on page
13: Converter stop by external error
This signal is activated when the error "E.-St" is generated and deactivated
when this error is reset. See
page 229
when digital input is set to '32: Error signal N.O. contact input' and
'33: Error signal N.C. contact input'.
chapter 12.8.7 "Start Mode Configuration" on
chapter 12.10.5 "Frequency Detection Function" on page
chapter 12.9.1 "Digital Input Configuration" on
Functions and Parameters
163.
R912005854_Edition 09 Bosch Rexroth AG
461/653
216.
258.
262.
146.