Electric Drives Linear Motion and and Controls Hydraulics Assembly Technologies Pneumatics Service Rexroth Frequency Converter R912004886 Edition 02 EFC 3600 Instruction Manual...
Page 2
This document, as well as the data, specifications and other information set forth in it, are the exclusive property of Bosch Rexroth (Xi'an) Electric Drives and Controls Co., Ltd. It may not be reproduced or given to third parties with- out its consent.
Check the case for transport damage such as scratches, cracks or dents. ● If you find any deviation from one of the above points, please contact your Bosch Rexroth sales partner. 1.2 Ambient Conditions If it is to function perfectly, the frequency converter must be installed in an envi- ronment matching the data provided below.
Bosch Rexroth AG EFC 3600 Mechanical Installation 1.3 Installation Conditions Depending on rating, the frequency converters are available in different frames. For perfect heat dissipation, the minimum installation spacing above and below the devices shown in the drawing must be observed.
Bosch Rexroth AG EFC 3600 Electric Installation 2 Electric Installation 2.1 Cable Specifications 2.1.1 Power Connection Depending on rating, the frequency converters are available in different sizes. For the device to function perfectly, flexible cables with corresponding wire end sleeves must be used during the electric installation. The fuses, cable cross-sec- tions and tightening torques required for the mounting screws are listed below.
Page 11
EFC 3600 Bosch Rexroth AG Electric Installation 2.1.2 Signal Connection The following requirements are applicable to the signal connection wiring: flexible cables with wire end sleeves ● cable cross-section: 0.2 ~ 1.5 mm ● cable length: max. 20 m ●...
Page 12
Bosch Rexroth AG EFC 3600 Electric Installation 2.1.3 Overview of Electric Connections Fig. 2-1: Block diagram It is recommended to use shielded cable to connect the motor. ● The communication interface shown in the figure above is RJ11 ● for ModBus communication; for PROFIBUS communication inter- face DB9, see "13.2: PROFIBUS Protocol"...
EFC 3600 Bosch Rexroth AG Electric Installation 2.2 Power Terminals The table below describes the symbols on the frequency converter's power con- nection terminals and their function. Terminal Description 1-phase AC 200 V class L1, L2 Mains power supply inputs...
Bosch Rexroth AG EFC 3600 Electric Installation 2.3 Interface Connection for Signals 2.3.1 NPN/PNP Mode Selection Switch SW Fig. 2-4: NPN / PNP wwitch SW for the digital inputs As shown in the figure above, the factory default setting is NPN.
Page 15
EFC 3600 Bosch Rexroth AG Electric Installation 2.3.2 Analog Input Terminals (+10 V, Vr1, GND, +I) Fig. 2-5: Analog input terminals (+10 V, Vr1, GND,+I) For connections of low level analog signals, which are easily affec- ● ted by external interference, the wiring length should be as short as possible (less than 20 m).
Page 16
Bosch Rexroth AG EFC 3600 Electric Installation 2.3.3 Control Circuit Terminals Control circuit terminals figure Fig. 2-6: Control circuit terminals The sequence of the label and the terminals is as indicated by ar- rows in the above figure. 12/35 DOK-RCON03-EFC-3600***-IN02-EN-P...
Page 17
EFC 3600 Bosch Rexroth AG Electric Installation Control Circuit Terminals Description Type Terminal Signal function Description Signal requirement Activated with “closed” see parameters E0.01 ~ Multiple speed X1 ~ X5 E0.05, chapter 8.6 in 24 VDC 8 mA inputs via op-...
Bosch Rexroth AG EFC 3600 Parameter Settings 3 Parameter Settings 3.1 Operating Panel The operating panel is removable and composed of two areas: display and keys. The display shows mode settings and operation state of the frequency convert- er. The keys allow the user to program the frequency converter.
EFC 3600 Bosch Rexroth AG Parameter Settings 3.2 Start-up The diagram below shows the standard start-up procedure for the frequency converter. White boxes: check whether all the work listed has been performed correctly ● before beginning the start-up Light grey boxes: start-up (described on the following pages) ●...
EFC 3600 Bosch Rexroth AG Parameter Settings 3.4 Parameters 3.4.1 Description of Attribute Symbols in Parameter Tables Parameter attribute Description Parameter setting can be modified when the frequency converter is in RUN RUN/STOP or STOP mode. Parameter setting can only be modified when the frequency converter is in STOP STOP mode.
Page 22
Bosch Rexroth AG EFC 3600 Parameter Settings 3.4.2 Quick Start Parameters Access & motor nameplate parameters Code Name Setting range Min. unit Default Attri. 0: Basic parameters 1: Standard parameters Access authority set- b0.02 2: Extended parameters RUN/STOP ting 3: Advanced parameters...
Page 23
EFC 3600 Bosch Rexroth AG Parameter Settings Start-up parameters Code Name Setting range Min. unit Default Attri. 0: Start directly b1.30 Starting mode 1: Braking before start STOP 2: Start with speed capture 0: Deceleration to stop 1: Freewheeling to stop b1.40 Stopping mode...
Page 24
Bosch Rexroth AG EFC 3600 Parameter Settings Input / Output terminal functions Code Name Setting range Min. unit Default Attri. 0: Forward/stop, reverse/stop 2-wire/3-wire E0.00 1: Forward/reverse, run/stop STOP running control 2: 3-wire control E0.01 Terminal X1 STOP E0.02 Terminal X2 STOP E0.03 Terminal X3...
Page 25
EFC 3600 Bosch Rexroth AG Parameter Settings 11: Zeroing of external terminal frequency setting 12: Reserved 13: Stopping DC braking enabled 14: Reserved 15: Simple PLC prohibited 16: Simple PLC paused 17: Reserved 18: Second frequency command source enabled 19: External fault N.O. contact input 20: External fault N.C.
Page 26
Bosch Rexroth AG EFC 3600 Parameter Settings Fault message and diagnosis Setting Code Name Min. unit Default Attri. range E4.20 Last fault type read only E4.21 Second last fault type 0 ~ 51 read only E4.22 Third last fault type...
Page 27
EFC 3600 Bosch Rexroth AG Parameter Settings 14: Reserved ● 15: Ot, motor over temperature ● 16: CPUd, CPU is disturbed by external signal and program run to illegal ad- ● dress 17: SC, short circuit of IGBT happens; 18: Reserved ●...
Bosch Rexroth AG EFC 3600 Fault Indication 4 Fault Indication Error Error name Possible reason Solution code Reduce occurrence and scale of sudden Sudden change in run mode change Low mains voltage Check the input power supply Motor power and frequency con-...
Page 29
EFC 3600 Bosch Rexroth AG Fault Indication Error Error name Possible reason Solution code Surge voltage from power supply Check the input power supply Motor to earth short circuit causes Check the motor connection DC bus capacitors overcharged OE-1 Too large load rotation inertia...
Page 30
Bosch Rexroth AG EFC 3600 Fault Indication Error Error name Possible reason Solution code Long time over load Reduce over load time, reduce load Adjust V/F proportion and torque in- Too large proportion of V/F curve crease settings Motor power and frequency con-...
Page 31
EFC 3600 Bosch Rexroth AG Fault Indication Error Error name Possible reason Solution code Try to backup the data from the ope- EEP- Flash memory in a bad condition rating panel, and then contact with serv- Check the wiring of control circuit, main...
Page 32
Bosch Rexroth AG EFC 3600 Fault Indication Error Error name Possible reason Solution code External short circuit of motor Check the motor phase-phase Remove the short circuit and check the Earth surge motor Internal fault of IGBT Contact with service...
Page 33
EFC 3600 Bosch Rexroth AG Fault Indication Error Error name Possible reason Solution code Check the wiring of control circuit, ● main circuit and grounding to find out the source of interference CE3- Problem with operating panel If it happens again, replace the ope- ●...
Page 34
Bosch Rexroth AG EFC 3600 Fault Indication Error Error name Possible reason Solution code Check the wiring ● CE5- Problem with CPU on main board If it fails again, contact with service ● Power failure during running Check the input power supply...
Page 35
EFC 3600 Bosch Rexroth AG Fault Indication Error Error name Possible reason Solution code Remove the environmental interference EMC problem or EMI CE8- Defect on I/O board Replace the I/O board or drive Remove the environmental interference EMC problem or EMI...
Page 36
Bosch Rexroth AG EFC 3600 Fault Indication Error Error name Possible reason Solution code Remove the environmental interference EMC problem or EMI CE6- Replace the operating panel or frequen- Defect on operating panel cy converter Firmware version of I/O board...
Page 37
EFC 3600 Bosch Rexroth AG 33/35 DOK-RCON03-EFC-3600***-IN02-EN-P...
Page 38
Bosch Rexroth AG EFC 3600 34/35 DOK-RCON03-EFC-3600***-IN02-EN-P...