344/653
Functions and Parameters
Example 2
Modifying value of parameter E0.26 'Acceleration time'. 0x30 is the parameter
group, 0x1A is the index No. of the function code within the parameter group. If
the modifying value is 0x0064, then request and response data frames in PKW
area are shown in table below:
Request data frame of PKW area
Response data frame of PKW area
Tab. 12-70: Example 2_request and response data frames of PKW area
Example 3
Modifying value of parameter E0.26 'Acceleration time'. 0x30 is the parameter
group, 0x1A is the index No. of the function code within the parameter group. If
the modifying value is 0xFFFF, then request and response data frames in PKW
area are shown in table below:
Request data frame of PKW area
Response data frame of PKW area
Tab. 12-71: Example 3_request and response data frames of PKW area
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
ID
IND
0x0002
0x301A
0x0002
0x301A
ID
IND
0x0002
0x301A
0x0007
0x301A
VALUE_high
VALUE_low
0x0000
0x0064
0x0000
0x0064
VALUE_high
VALUE_low
0x0000
0xFFFF
0x0000
0x0064
Series