Advertisement

6 ACTUAL VALUES
The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.

PATH: ACTUAL VALUES
METERING
 PMU AGGREGATOR 1
Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernet
frame size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown in
the displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result in
fragmented data frames, causing increased network traffic.

PATH: ACTUAL VALUES
METERING
 DCMA INPUT xx
Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.

PATH: ACTUAL VALUES
METERING
 RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and
the bottom line as the value.
GE Multilin

PHASOR MEASUREMENT UNIT

PMU AGGREGATOR 1

PDU SIZE: 0

TRANSDUCER I/O DCMA INPUTS
DCMA INPUT xx
0.000 mA

TRANSDUCER I/O RTD INPUTS
RTD INPUT xx
-50 °C
D60 Line Distance Protection System
6.3.11 PMU AGGREGATOR
PMU AGGREGATOR 1

6.3.12 TRANSDUCER INPUTS AND OUTPUTS

DCMA INPUT xx
RTD INPUT xx
6.3 METERING
6
6-23