hit counter script

User-Definable Displays - GE UR Series F60 Instruction Manual

Feeder protection system
Hide thumbs Also See for UR Series F60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the "Flex States" register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
USER-DEFINABLE
DISPLAYS
5
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the
USER DISPLAYS
tate text entry and Modbus Register data pointer options for defining the User Display content.
Once programmed, the user-definable displays can be viewed in two ways.
KEYPAD: Use the Menu key to select the
that only the programmed screens are displayed). The screens can be scrolled using the Up and Down keys. The dis-
play disappears after the default message time-out period specified by the
DEFAULT MESSAGE TIMEOUT
USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
gate the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the Down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The
INVOKE AND SCROLL
When the default timer expires (set by the
user displays. The next activity of the
play, not at the first user-defined display. The
5-50

USER-DEFINABLE DISPLAYS

INVOKE AND SCROLL:
Off
USER DISPLAY
MESSAGE
USER DISPLAY
MESSAGE
USER DISPLAY 16
MESSAGE
menu (between the
USER DISPLAYS
setting.
input and the Down keypad key operate concurrently.
DEFAULT MESSAGE TIMEOUT
INVOKE AND SCROLL
INVOKE AND SCROLL
F60 Feeder Protection System
Range: FlexLogic™ operand
Range: up to 20 alphanumeric characters
1
Range: up to 20 alphanumeric characters
2
Range: up to 20 alphanumeric characters
and
TARGETS
ACTUAL VALUES
menu item to access the first user-definable display (note
PRODUCT SETUP
setting), the relay will start to cycle through the
input stops the cycling at the currently displayed user dis-
pulses must last for at least 250 ms to take effect.
5 SETTINGS
5.2.16 USER-DEFINABLE DISPLAYS
top-level menus). The sub-menus facili-
DISPLAY PROPERTIES
INVOKE AND SCROLL
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents