Page 3
Addendum GE Industrial Systems ADDENDUM This addendum contains information that relates to the F60 Feeder Protection System, version 5.4x. This addendum lists a number of information items that appear in the instruction manual GEK-113345 (revision R1) but are not included in the current F60 operations.
Page 9
C.3.4 LOGICAL DEVICE NAME..................C-5 C.3.5 LOCATION......................C-5 C.3.6 LOGICAL NODE NAME PREFIXES ..............C-6 C.3.7 CONNECTION TIMING ..................C-6 C.3.8 NON-IEC 61850 DATA ..................C-6 C.3.9 COMMUNICATION SOFTWARE UTILITIES .............C-6 C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE GE Multilin F60 Feeder Protection System...
Page 10
ANALOG INPUTS.................... E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY..................F-1 F.1.2 CHANGES TO THE F60 MANUAL..............F-2 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-4 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY................F-6 INDEX F60 Feeder Protection System GE Multilin...
• registration card (attached as the last page of the manual) • Fill out the registration form and return to GE Multilin (include the serial number located on the rear nameplate). • For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin web- site at http://www.GEmultilin.com.
This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. F60 Feeder Protection System...
(dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin F60 Feeder Protection System...
CTs and VTs is in the Introduction to AC Sources section in Chapter 5. A description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section in Chapter 5. F60 Feeder Protection System GE Multilin...
After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD. Insert the GE EnerVista CD into your CD-ROM drive.
Page 16
EnerVista UR Setup to the Windows start menu. Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista Launchpad window, as shown below. F60 Feeder Protection System GE Multilin...
A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is will be required. Refer to the F485 instruction manual for additional details. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details.
Page 18
Ethernet communications, it will be necessary to define a Site, then add the relay as a Device at that site. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.GEmultilin.com).
Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port with a straight-through 9-pin to 9-pin RS232 cable. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details.
Page 20
White/orange Blue Blue White/blue White/blue Green Orange White/brown White/brown Brown Brown 842799A1.CDR Figure 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUT Now, assign the laptop computer an IP address compatible with the relay’s IP address. 1-10 F60 Feeder Protection System GE Multilin...
Page 21
Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. GE Multilin F60 Feeder Protection System 1-11...
Page 22
Verify the physical connection between the F60 and the laptop computer, and double-check the programmed IP address in setting, then repeat step 2 in the above procedure. PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS If the following sequence of messages appears when entering the command: C:\WINNT>ping 1.1.1.1 1-12 F60 Feeder Protection System GE Multilin...
Page 23
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the F60 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details.
Page 24
Ethernet network. The Setup Software will then proceed to configure all settings and order code options in the Device Setup menu, for the purpose of communicating to multiple relays. Using this feature will allow you to identify and interrogate in seconds, all UR devices found in a particular location. 1-14 F60 Feeder Protection System GE Multilin...
The Quick Action functions available are: • View device’s Event Record • View device’s last recorded Oscillography Record • View status of all device Inputs and Outputs • View all of the device Metering values GE Multilin F60 Feeder Protection System 1-15...
Page 26
1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED • View the device’s Protection Summary 1-16 F60 Feeder Protection System GE Multilin...
Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the F60 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the F60 rear communications port.
LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed 1-18 F60 Feeder Protection System GE Multilin...
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. GE Multilin F60 Feeder Protection System 1-19...
Unscheduled maintenance such as during a disturbance causing system interruption: View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements. If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service. 1-20...
The information required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules). Order codes are subject to change without notice. Refer to the GE Multilin ordering page at http://www.GEindustrial.com/multilin/order.htm for the latest details concerning F60 ordering options.
Not all replacement modules may be applicable to the F60 relay. Only the modules specified in the order codes are available as replacement modules. NOTE Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http:// www.GEindustrial.com/multilin/order.htm for the latest details concerning F60 ordering options.
Page 35
4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs GE Multilin F60 Feeder Protection System...
Page 36
4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs F60 Feeder Protection System GE Multilin...
±1.5% of reading > 2.0 × CT rating Inverse; IEC (and BS) A/B/C and Short Curve shapes: IEEE Moderately/Very/Extremely Inverse; GE IAC Inverse, Short/Very/ Inverse; IEC (and BS) A/B/C and Short Extremely Inverse; I t; FlexCurves™ Inverse; GE IAC Inverse, Short/Very/ (programmable);...
Page 38
40 to 90° in steps of 1, independent for Level accuracy: ±0.5% of reading from 10 to 208 V forward and reverse Curve shapes: GE IAV Inverse, Definite Time Angle accuracy: ±2° Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 0.00 to 250.00 Ω...
Page 39
±3% or ±4 ms, whichever is greater 95% settling time for df/dt: < 24 cycles typically 6.5 cycles at 2 × pickup Operate time: typically 5.5 cycles at 3 × pickup typically 4.5 cycles at 5 × pickup GE Multilin F60 Feeder Protection System...
Type: set-dominant or reset-dominant chronize to a 3-bit control input or synch/ Number: 16 (individually programmed) restore mode Output: stored in non-volatile memory Execution sequence: as input prior to protection, control, and FlexLogic™ 2-10 F60 Feeder Protection System GE Multilin...
–0.8 < PF ≤ –1.0 and 0.8 < PF ≤ 1.0 ±0 to 2 × 10 Range: Mvarh REACTIVE POWER (VARS) Parameters: 3-phase only ±1.0% of reading at –0.2 ≤ PF ≤ 0.2 Accuracy: Update rate: 50 ms GE Multilin F60 Feeder Protection System 2-11...
1 to 275 V Auto-burnish impulse current: 50 to 70 mA Voltage withstand: continuous at 260 V to neutral Duration of auto-burnish impulse: 25 to 50 ms 1 min./hr at 420 V to neutral 2-12 F60 Feeder Protection System GE Multilin...
0.3 A FORM-A VOLTAGE MONITOR 250 V 0.2 A Applicable voltage: approx. 15 to 250 V DC Trickle current: approx. 1 to 2.5 mA Operate time: < 4 ms Contact material: silver alloy GE Multilin F60 Feeder Protection System 2-13...
Page 44
L/R = 10 ms (0 to 250 V 1.6 A 10 A 10 A L/R = 20 ms L/R = 40 ms L/R = 40 ms 0.8 A L/R = 40 ms 2-14 F60 Feeder Protection System GE Multilin...
–1 dBm –30 dBm 29 dB Singlemode 1550 nm Laser, +5 dBm –30 dBm 35 dB Singlemode These Power Budgets are calculated from the manufacturer’s worst-case transmitter power NOTE and worst case receiver sensitivity. GE Multilin F60 Feeder Protection System 2-15...
Up to 2000 m Cold: IEC 60068-2-1, 16 h at –40°C Installation Category: Dry Heat: IEC 60068-2-2, 16 h at +85°C The LCD contrast may be impaired at temperatures less than –20°C. NOTE 2-16 F60 Feeder Protection System GE Multilin...
Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration of electrolytic capacitors. NOTE GE Multilin F60 Feeder Protection System 2-17...
Page 48
2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-18 F60 Feeder Protection System GE Multilin...
RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.016” [279,81 mm] 9.687” [246,05 mm] 17.56” [446,02 mm] 7.460” [189,48 mm] 6.995” 6.960” [177,67 mm] [176,78 mm] 19.040” [483,62 mm] 842807A1.CDR Figure 3–1: F60 HORIZONTAL DIMENSIONS (ENHANCED PANEL) GE Multilin F60 Feeder Protection System...
Page 50
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. F60 Feeder Protection System GE Multilin...
Page 51
3 HARDWARE 3.1 DESCRIPTION UR SERIES UR SERIES Figure 3–4: F60 VERTICAL MOUNTING AND DIMENSIONS GE Multilin F60 Feeder Protection System...
Page 52
3.1 DESCRIPTION 3 HARDWARE Figure 3–5: F60 VERTICAL SIDE MOUNTING INSTALLATION F60 Feeder Protection System GE Multilin...
The enhanced faceplate can be opened to the left, once thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the F60. GE Multilin F60 Feeder Protection System...
Page 54
When the clips have locked into position, the module will be fully inserted. All CPU modules except the 9E are equipped with 10Base-T or 10Base-F Ethernet connectors. These connectors must be individually disconnected from the module before it can be removed from the chassis. NOTE F60 Feeder Protection System GE Multilin...
Two-slot wide modules take their slot designation from the first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. GE Multilin F60 Feeder Protection System...
Page 56
3.1 DESCRIPTION 3 HARDWARE Figure 3–10: EXAMPLE OF MODULES IN F AND H SLOTS F60 Feeder Protection System GE Multilin...
Page 58
This diagram provides an example of how the device is wired, not specifically how to wire the device. Please refer to the Instruction Manual for additional details on wiring based on various configurations. GE Consumer & Industrial Multilin FEEDER MANAGEMENT RELAY COMPUTER...
An LED on the front of the module shows the status of the power supply: LED INDICATION POWER SUPPLY ON / OFF CYCLING Failure Failure GE Multilin F60 Feeder Protection System 3-11...
CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair cabling on the zero-sequence CT is recommended. 3-12 F60 Feeder Protection System GE Multilin...
Page 61
8F and 8G modules (4 CTs and 4 VTs) Current inputs 8H and 8J modules (8 CTs) Current inputs Not used 8Z module (used for high-impedance fault detection) 842769A1.CDR Figure 3–15: CT MODULE WIRING GE Multilin F60 Feeder Protection System 3-13...
Block diagrams are shown below for form-A and form-A / solid-state relay outputs with optional voltage monitor, optional current monitor, and with no monitoring 3-14 F60 Feeder Protection System GE Multilin...
Page 63
Load b) Current with optional Current monitoring only Both voltage and current monitoring voltage monitoring (external jumper a-b is required) 827862A2.CDR Load c) No monitoring Figure 3–18: FORM-A / SOLID STATE CONTACT FUNCTIONS GE Multilin F60 Feeder Protection System 3-15...
Page 65
2 Inputs 2 Outputs Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin F60 Feeder Protection System 3-17...
Page 66
3.2 WIRING 3 HARDWARE Figure 3–19: DIGITAL INPUT/OUTPUT MODULE WIRING (1 of 2) 3-18 F60 Feeder Protection System GE Multilin...
Page 67
3 HARDWARE 3.2 WIRING Figure 3–20: DIGITAL INPUT/OUTPUT MODULE WIRING (2 of 2) CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT AND SOLID STATE OUTPUT CON- NECTIONS FOR PROPER FUNCTIONALITY. CAUTION GE Multilin F60 Feeder Protection System 3-19...
Page 68
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. NOTE 3-20 F60 Feeder Protection System GE Multilin...
Page 69
CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–23: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE GE Multilin F60 Feeder Protection System 3-21...
(5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the Slot Position of the module. NOTE Figure 3–24: TRANSDUCER INPUT/OUTPUT MODULE WIRING 3-22 F60 Feeder Protection System GE Multilin...
The CPU modules do not require a surge ground connection. NOTE CPU TYPE COM1 COM2 RS485 RS485 10Base-F and 10Base-T RS485 Redundant 10Base-F RS485 100Base-FX RS485 Redundant 100Base-FX RS485 100Base-FX RS485 Redundant 100Base-FX RS485 10/100Base-T RS485 100Base-FX RS485 Redundant 100Base-FX RS485 GE Multilin F60 Feeder Protection System 3-23...
Page 72
To ensure maximum reliability, all equipment should have similar transient protection devices installed. Both ends of the RS485 circuit should also be terminated with an impedance as shown below. 3-24 F60 Feeder Protection System GE Multilin...
Page 73
For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers, the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connec- tor, only a quarter turn of the coupling is required. GE Multilin F60 Feeder Protection System 3-25...
UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–29: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors in event time-stamping. NOTE 3-26 F60 Feeder Protection System GE Multilin...
Channel 1 to Channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. GE Multilin F60 Feeder Protection System 3-27...
Page 76
Channel 1 - G.703; Channel 2 - 1550 nm, single-mode, LASER IEEE C37.94, 820 nm, multi-mode, LED, 1 channel IEEE C37.94, 820 nm, multi-mode, LED, 2 channels OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE. CAUTION 3-28 F60 Feeder Protection System GE Multilin...
1 Channel 2 Channels Figure 3–34: LASER FIBER MODULES When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed Maximum Optical Input Power to the receiver. WARNING GE Multilin F60 Feeder Protection System 3-29...
Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. 3-30 F60 Feeder Protection System GE Multilin...
Page 79
For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). GE Multilin F60 Feeder Protection System 3-31...
Page 80
G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–39: G.703 DUAL LOOPBACK MODE 3-32 F60 Feeder Protection System GE Multilin...
1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin F60 Feeder Protection System 3-33...
Page 82
Figure 3–43: CLOCK AND DATA TRANSITIONS d) RECEIVE TIMING The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data. NRZI-MARK is an edge-type, invertible, self-clocking code. 3-34 F60 Feeder Protection System GE Multilin...
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed Maximum Optical Input Power to the receiver. WARNING Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–45: G.703 AND FIBER INTERFACE CONNECTION GE Multilin F60 Feeder Protection System 3-35...
For the Looped Timing Mode, the system clock is derived from the received line signal. Therefore, the timing selection should be in Loop Timing Mode for connections to higher order systems. The C37.94 communications module cover removal procedure is as follows: 3-36 F60 Feeder Protection System GE Multilin...
Page 85
Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–46: IEEE C37.94 TIMING SELECTION SWITCH SETTING GE Multilin F60 Feeder Protection System 3-37...
For the Looped Timing Mode, the system clock is derived from the received line signal. Therefore, the timing selection should be in Loop Timing Mode for connections to higher order systems. The C37.94SM communications module cover removal procedure is as follows: 3-38 F60 Feeder Protection System GE Multilin...
Page 87
Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–47: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin F60 Feeder Protection System 3-39...
Page 88
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE 3-40 F60 Feeder Protection System GE Multilin...
Factory default values are supplied and can be restored after any changes. c) CREATING AND EDITING FLEXLOGIC™ You can create or edit a FlexLogic™ equation in order to customize the relay. You can subsequently view the automatically generated logic diagram. GE Multilin F60 Feeder Protection System...
Page 90
EEPROM DATA ERROR message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This message does not signal any problems when appearing after firmware upgrades. F60 Feeder Protection System GE Multilin...
Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick Action Hot Links 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin F60 Feeder Protection System...
LED panel 1 LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–3: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS F60 Feeder Protection System GE Multilin...
IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. • TROUBLE: This LED indicates that the relay has detected an internal problem. GE Multilin F60 Feeder Protection System...
Page 94
IN SERVICE: Indicates that control power is applied; all monitored inputs/outputs and internal systems are OK; the relay has been programmed. • TROUBLE: Indicates that the relay has detected an internal problem. • TEST MODE: Indicates that the relay is in test mode. F60 Feeder Protection System GE Multilin...
Page 95
RECLOSE ENABLED: The recloser is operational. • RECLOSE DISABLED: The recloser is not operational. • RECLOSE IN PROGRESS: A reclose operation is in progress. • RECLOSE LOCKED OUT: The recloser is not operational and requires a reset. GE Multilin F60 Feeder Protection System...
EnerVista UR Setup software is installed and operational. • The F60 settings have been saved to a settings file. • The F60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http:// www.GEindustrial.com/multilin/support/ur and printed.
Page 97
These tabs will be used for insertion and removal of the default and custom LED labels. It is important that the tool be adjusted and used, EXACTLY as shown below, with the printed side containing the GE part number, facing UPWARDS. NOTE...
Page 98
4.2 FACEPLATE INTERFACE 4 HUMAN INTERFACES SETTING UP THE LABEL TOOL: Figure 4–10: LABEL TOOL - BENDING THE UPPER TABS UPWARD Figure 4–11: LABEL TOOL - BENDING THE LOWER TABS DOWNWARD 4-10 F60 Feeder Protection System GE Multilin...
Page 99
Figure 4–13: STEP 1 - USE KNIFE TO LIFT THE LED LABEL AND SLIDE THE LABEL TOOL UNDERNEATH. MAKE SURE THE BENDED UPPER TABS ARE POINTING OUTWARDS ( IE - AWAY FROM YOU). GE Multilin F60 Feeder Protection System 4-11...
Page 100
4 HUMAN INTERFACES Figure 4–14: STEP 2 - SLIDE THE TOOL IN UNTIL THE TABS SNAP OUT AS SHOWN Figure 4–15: STEP 3 - PULL THE TOOL OUT ALONG WITH THE LED LABEL 4-12 F60 Feeder Protection System GE Multilin...
Page 101
4 HUMAN INTERFACES 4.2 FACEPLATE INTERFACE Figure 4–16: STEP 7 - SLIDE HALF OF THE PRINTED LED LABEL INSIDE THE POCKET Figure 4–17: STEP 8 - SLIDE THE LABEL TOOL INSIDE THE POCKET AS SHOWN GE Multilin F60 Feeder Protection System 4-13...
Page 102
Figure 4–19: STEP 1 - USE KNIFE TO LIFT THE PUSHBUTTON LABEL AND SLIDE TAIL OF THE LABEL TOOL UNDERNEATH. MAKE SURE THE BENDED TAB IS POINTING OUTWARDS ( IE - AWAY FROM YOU). 4-14 F60 Feeder Protection System GE Multilin...
Page 103
4 HUMAN INTERFACES 4.2 FACEPLATE INTERFACE Figure 4–20: STEP 2 - SLIDE THE TOOL IN UNTIL THE TAB SNAPS OUT AS SHOWN Figure 4–21: STEP 3 - PULL THE TOOL OUT WITH THE PUSHBUTTON LABEL GE Multilin F60 Feeder Protection System 4-15...
Page 104
The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). Push in...
Microsoft Word 97 or later software for editing the template. • 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069), and a custom module cover (GE Multilin Part Number: 1502-0015).
Each press of the MENU key advances through the following main heading pages: • Actual values • Settings • Commands • Targets • User displays (when enabled) 4-18 F60 Feeder Protection System GE Multilin...
Page 107
FLASH MESSAGE Display Properties. TIME: 1.0 s To view the remaining settings associated with the Display Properties subheader, DEFAULT MESSAGE repeatedly press the MESSAGE DOWN key. The last message appears as shown. INTENSITY: 25% GE Multilin F60 Feeder Protection System 4-19...
ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters. 4-20 F60 Feeder Protection System GE Multilin...
Page 109
When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The F60 supports password entry from a local or remote connection. GE Multilin F60 Feeder Protection System 4-21...
Page 110
FlexLogic™ operand will be set to “On” and the F60 will not allow LOCAL ACCESS DENIED Settings or Command access via the faceplate interface for the next ten minutes. The TOO MANY ATTEMPTS – BLOCKED 4-22 F60 Feeder Protection System GE Multilin...
Page 111
F60 will not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout. REMOTE ACCESS DENIED GE Multilin F60 Feeder Protection System 4-23...
Page 112
4.2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-24 F60 Feeder Protection System GE Multilin...
See page 5-49. PARAMETERS USER-DEFINABLE See page 5-50. DISPLAYS DIRECT I/O See page 5-52. TELEPROTECTION See page 5-59. INSTALLATION See page 5-59. SETTINGS AC INPUTS See page 5-61. SYSTEM SETUP POWER SYSTEM See page 5-62. GE Multilin F60 Feeder Protection System...
Page 114
OVERFREQUENCY See page 5-155. FREQUENCY RATE See page 5-157. OF CHANGE SYNCHROCHECK See page 5-159. AUTORECLOSE See page 5-163. DIGITAL ELEMENTS See page 5-169. DIGITAL COUNTERS See page 5-172. MONITORING See page 5-174. ELEMENTS F60 Feeder Protection System GE Multilin...
Page 115
See page 5-206. DCMA OUTPUTS See page 5-207. SETTINGS TEST MODE See page 5-211. TESTING FUNCTION: Disabled TEST MODE INITIATE: See page 5-211. FORCE CONTACT See page 5-211. INPUTS FORCE CONTACT See page 5-212. OUTPUTS GE Multilin F60 Feeder Protection System...
0 at any time, the comparator returns to the default state. The RUN input is used to supervise the comparator. The BLOCK input is used as one of the inputs to RUN control. F60 Feeder Protection System GE Multilin...
The same considerations apply to transformer Winding 2. The protection elements require access to the net current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2. GE Multilin F60 Feeder Protection System...
Page 118
INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > F60 Feeder Protection System GE Multilin...
Page 119
CTs on each of two breakers is required to measure the winding current flow. GE Multilin F60 Feeder Protection System...
Programming a password code is required to enable each access level. A password consists of 1 to 10 numerical charac- ters. When a setting is set to "Yes", the following message sequence is invoked: CHANGE ... PASSWORD F60 Feeder Protection System GE Multilin...
Page 121
When EnerVista UR Setup is used to access a particular level, the user will continue to have access to that level as long as there are open windows in the EnerVista UR Setup software. To re-establish the Password Security feature, all windows must be closed for at least 30 minutes. NOTE GE Multilin F60 Feeder Protection System...
The F60 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical 5-10 F60 Feeder Protection System GE Multilin...
Page 123
CURRENT CUT-OFF LEVEL as valid measurements. Unless dictated otherwise by a specific application, the default settings of “0.02 pu” for and “1.0 V” for are recommended. NOTE CURRENT CUT-OFF LEVEL VOLTAGE CUT-OFF LEVEL GE Multilin F60 Feeder Protection System 5-11...
Set the properties for User-Programmable Pushbutton 1 by making the following changes in the SETTINGS PROD- menu: UCT SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 “Self-reset” PUSHBUTTON 1 FUNCTION: “0.20 s” PUSHBTN 1 DROP-OUT TIME: 5-12 F60 Feeder Protection System GE Multilin...
RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of GE Multilin F60 Feeder Protection System...
Page 126
1. Refer to Appendix B for more information on the Modbus protocol. Changes to the setting will not take effect until the F60 is restarted. MODBUS TCP PORT NUMBER NOTE 5-14 F60 Feeder Protection System GE Multilin...
Page 127
DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULT MESSAGE DEADBAND: 30000 Range: 1 to 10080 min. in steps of 1 DNP TIME SYNC IIN MESSAGE PERIOD: 1440 min GE Multilin F60 Feeder Protection System 5-15...
Page 128
DNP CHANNEL 1(2) PORT NOTE settings can force the F60 to respond to a maximum of five specific DNP masters. The DNP NETWORK CLIENT ADDRESS settings in this sub-menu are shown below. 5-16 F60 Feeder Protection System GE Multilin...
Page 129
The DNP NUMBER OF PAIRED CONTROL setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on POINTS a one-to-one basis. GE Multilin F60 Feeder Protection System 5-17...
Page 130
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. NOTE 5-18 F60 Feeder Protection System GE Multilin...
Page 131
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception. PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION GSSE / GOOSE TRANSMISSION CONFIGURATION RECEPTION MESSAGE The main transmission menu is shown below: GE Multilin F60 Feeder Protection System 5-19...
Page 132
Range: 0 to 7 in steps of 1 GOOSE VLAN PRIORITY: MESSAGE Range: 0 to 4095 in steps of 1 GOOSE VLAN ID: MESSAGE Range: 0 to 16383 in steps of 1 GOOSE ETYPE APPID: MESSAGE 5-20 F60 Feeder Protection System GE Multilin...
Page 133
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes- sages due to an oscillation being created that is triggering a message. GE Multilin F60 Feeder Protection System 5-21...
Page 134
(the default value is “0”). – Set the value. This value changes automatically as described in IEC 61850 part 7-2. For CONFIG GSE 1 CONFREV this example it can be left at its default value. 5-22 F60 Feeder Protection System GE Multilin...
Page 135
The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™ operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con- taining the defined dataset. GE Multilin F60 Feeder Protection System 5-23...
Page 136
UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC 61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be “Disabled”. 5-24 F60 Feeder Protection System GE Multilin...
Page 137
The minimum value for all quantities is 0; the maximum values are as follows: phase current: 46 × phase CT primary setting • neutral current: 46 × ground CT primary setting • voltage: 275 × VT ratio setting • GE Multilin F60 Feeder Protection System 5-25...
Page 138
GGIO4. When this value is NUMBER OF ANALOG POINTS changed, the F60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly configured number of analog points. 5-26 F60 Feeder Protection System GE Multilin...
Page 139
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted: PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XCBR CONFIGURATION Range: FlexLogic™ operand XCBR XCBR1 ST.LOC OPERAND CONFIGURATION Range: FlexLogic™ operand XCBR2 ST.LOC OPERAND MESSAGE GE Multilin F60 Feeder Protection System 5-27...
Page 140
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the F60 contains a list and description of all available files (event records, oscillography, etc.). 5-28 F60 Feeder Protection System GE Multilin...
Page 141
Ethernet network. The F60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported. GE Multilin F60 Feeder Protection System...
Page 142
Range: 0 to 65535 in steps of 1 EXCH 1 DATA ITEM 1: MESSAGE (Modbus register address range) ↓ Range: 0 to 65535 in steps of 1 EXCH 1 DATA ITEM 20: MESSAGE (Modbus register address range) 5-30 F60 Feeder Protection System GE Multilin...
Range: 0 to 65535 in steps of 1 MODBUS USER MAP ADDRESS VALUE: Range: 0 to 65535 in steps of 1 ADDRESS MESSAGE VALUE: ↓ Range: 0 to 65535 in steps of 1 ADDRESS 256: MESSAGE VALUE: GE Multilin F60 Feeder Protection System 5-31...
Note that when IRIG-B time synchronization is active, the DST settings are ignored. The DST settings are used when the F60 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used. 5-32 F60 Feeder Protection System GE Multilin...
Elements operated at the time of triggering • Events: 9 before trigger and 7 after trigger (only available via the relay webpage) • Fault duration times for each breaker (created by the breaker arcing current feature) GE Multilin F60 Feeder Protection System 5-33...
Page 146
It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). 5-34 F60 Feeder Protection System GE Multilin...
64 samples per cycle, i.e. it has no effect on the fundamental calculations of the device. When changes are made to the oscillography settings, all existing oscillography records will be CLEARED. WARNING GE Multilin F60 Feeder Protection System 5-35...
Page 148
2nd to 25th harmonics in the relay as follows: NOTE Analog channel 0 ↔ 2nd harmonic Analog channel 1 ↔ 3rd harmonic Analog channel 23 ↔ 25th harmonic 5-36 F60 Feeder Protection System GE Multilin...
DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to “Continu- ous”, the data logger will actively record any configured channels at the rate as defined by the . The DATA LOGGER RATE GE Multilin F60 Feeder Protection System 5-37...
D 1 e (EQ 5.6) – where: d = demand value after applying input quantity for time t (in minutes) D = input quantity (constant), and k = 2.3 / thermal 90% response time. 5-38 F60 Feeder Protection System GE Multilin...
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LED TEST See below LEDS TRIP & ALARM See page 5–42. MESSAGE LEDS USER-PROGRAMMABLE See page 5–42. MESSAGE LED1 USER-PROGRAMMABLE MESSAGE LED2 ↓ USER-PROGRAMMABLE MESSAGE LED48 GE Multilin F60 Feeder Protection System 5-39...
Page 152
The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-40 F60 Feeder Protection System GE Multilin...
Page 153
Stage 2. Once Stage 2 has started, the pushbutton can be released. When Stage 2 is completed, Stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. GE Multilin F60 Feeder Protection System...
Page 154
LED 21 Operand AR ENABLED LED 10 Operand BREAKER 1 CLOSED LED 22 Operand AR DISABLED LED 11 Operand BREAKER 1 TROUBLE LED 23 Operand AR RIP LED 12 Operand LED 24 Operand AR LO 5-42 F60 Feeder Protection System GE Multilin...
ANY SELF-TEST mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter 7 for additional information on major and minor self-test alarms. GE Multilin F60 Feeder Protection System 5-43...
USER 1 through 3 pushbuttons as shown below. If configured for manual control, breaker control typically uses the larger, optional user-programmable pushbuttons, making the control pushbuttons available for other user applications. 5-44 F60 Feeder Protection System GE Multilin...
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter- ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered with the relay. GE Multilin F60 Feeder Protection System 5-45...
Page 158
(SBO) breaker control applications, where the command type (close/open) or breaker location (feeder number) must be selected prior to command execution. The selection must reset automatically if con- trol is not executed within a specified time period. 5-46 F60 Feeder Protection System GE Multilin...
Page 159
50 ms. • PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable only if the pushbutton is in the “Latched” mode. GE Multilin F60 Feeder Protection System 5-47...
Page 160
“Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. 5-48 F60 Feeder Protection System GE Multilin...
INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL 5-50 F60 Feeder Protection System GE Multilin...
Page 163
4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. GE Multilin F60 Feeder Protection System...
On type 7 cards that sup- port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output 5-52 F60 Feeder Protection System GE Multilin...
Page 165
Delivery time for direct input/output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. GE Multilin F60 Feeder Protection System...
Page 166
UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional input/output and programmable logic requirements. The two IEDs are con- nected via single-channel digital communication cards as shown in the figure below. 5-54 F60 Feeder Protection System GE Multilin...
Page 167
In the above application, the following settings should be applied: UR IED 1: “1” UR IED 2: “2” DIRECT OUTPUT DEVICE ID: DIRECT OUTPUT DEVICE ID: “Yes” “Yes” DIRECT I/O RING CONFIGURATION: DIRECT I/O RING CONFIGURATION: GE Multilin F60 Feeder Protection System 5-55...
Page 168
DIRECT I/O RING CONFIGURATION: DIRECT I/O RING CONFIGURATION: UR IED 3: "3" DIRECT OUTPUT DEVICE ID: "Yes" DIRECT I/O RING CONFIGURATION: In this configuration the following delivery times are expected (at 128 kbps): 5-56 F60 Feeder Protection System GE Multilin...
Page 169
The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based output. Latching and acknowledging conditions - if required - should be programmed accordingly. GE Multilin F60 Feeder Protection System 5-57...
Page 170
The Unreturned Messages Alarm function is available on a per-channel basis and is active only in the ring configuration. The total number of unreturned input/output messages is available as the ACTUAL VALUES STATUS DIRECT INPUTS actual value. UNRETURNED MSG COUNT CH1(2) 5-58 F60 Feeder Protection System GE Multilin...
TERMINAL 1 ID NUMBER 5.2.19 INSTALLATION PATH: SETTINGS PRODUCT SETUP INSTALLATION Range: Not Programmed, Programmed INSTALLATION RELAY SETTINGS: Not Programmed Range: up to 20 alphanumeric characters RELAY NAME: MESSAGE Relay-1 GE Multilin F60 Feeder Protection System 5-59...
Page 172
This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. 5-60 F60 Feeder Protection System GE Multilin...
CTs will be adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 cur- rents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). GE Multilin F60 Feeder Protection System 5-61...
Range: 25 to 60 Hz in steps of 1 POWER SYSTEM NOMINAL FREQUENCY: 60 Hz Range: ABC, ACB PHASE ROTATION: MESSAGE Range: SRC 1, SRC 2 FREQUENCY AND PHASE MESSAGE REFERENCE: SRC 1 Range: Disabled, Enabled FREQUENCY TRACKING: MESSAGE Enabled 5-62 F60 Feeder Protection System GE Multilin...
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered, including specifying which CTs will be summed together. GE Multilin F60 Feeder Protection System 5-63...
Page 176
0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting ( PROD- ) controls the sensitivity of the disturbance detector UCT SETUP DISPLAY PROPERTIES CURRENT CUT-OFF LEVEL accordingly. 5-64 F60 Feeder Protection System GE Multilin...
0 when the breaker is open. If is selected as "3-Pole", this set- BREAKER 1 MODE ting selects a single input as the operand used to track the breaker open or closed position. If the mode is selected as GE Multilin F60 Feeder Protection System 5-65...
Page 178
MANUAL CLOSE RECAL1 TIME: Sets the interval required to maintain setting changes in effect after an operator has initiated a manual close command to operate a circuit breaker. • BREAKER 1(2) OUT OF SV: Selects an operand indicating that breaker 1(2) is out-of-service. 5-66 F60 Feeder Protection System GE Multilin...
Page 179
BREAKER 1 C CLSD Ø BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN FLEXLOGIC OPERAND SETTING BREAKER 1 OUT OF SV: BREAKER 1 OOS 827061AP.CDR Figure 5–17: DUAL BREAKER CONTROL SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-67...
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin- NOTE ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. 5-68 F60 Feeder Protection System GE Multilin...
Page 181
The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin F60 Feeder Protection System 5-69...
Page 182
EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the F60 are displayed in the following graphs. 5-70 F60 Feeder Protection System GE Multilin...
Page 183
CURRENT (multiple of pickup) 842723A1.CDR Figure 5–21: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–22: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin F60 Feeder Protection System 5-71...
Page 184
Figure 5–23: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–24: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-72 F60 Feeder Protection System GE Multilin...
Page 185
Figure 5–25: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–26: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin F60 Feeder Protection System 5-73...
Page 186
Figure 5–27: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–28: RECLOSER CURVES GE119, GE135, AND GE202 5-74 F60 Feeder Protection System GE Multilin...
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and wiring while making more complex schemes possible. GE Multilin F60 Feeder Protection System 5-75...
Page 188
The virtual input is presently in the ON state. Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1"). 5-76 F60 Feeder Protection System GE Multilin...
Page 189
BKR FAIL 1 T3 OP Breaker failure 1 timer 3 is operated BKR FAIL 1 TRIP OP Breaker failure 1 trip is operated BKR FAIL 2 Same set of operands as shown for BKR FAIL 1 GE Multilin F60 Feeder Protection System 5-77...
Page 190
GROUND IOC1 OP Ground instantaneous overcurrent 1 has operated instantaneous GROUND IOC1 DPO Ground instantaneous overcurrent 1 has dropped out overcurrent GROUND IOC2 Same set of operands as shown for GROUND IOC 1 5-78 F60 Feeder Protection System GE Multilin...
Page 191
Neutral directional overcurrent 1 forward has operated Neutral directional NTRL DIR OC1 REV Neutral directional overcurrent 1 reverse has operated overcurrent NTRL DIR OC2 Same set of operands as shown for NTRL DIR OC1 GE Multilin F60 Feeder Protection System 5-79...
Page 192
Phase B of phase undervoltage 1 has dropped out PHASE UV1 DPO C Phase C of phase undervoltage 1 has dropped out PHASE UV2 Same set of operands as shown for PHASE UV1 5-80 F60 Feeder Protection System GE Multilin...
Page 193
FIXED OPERANDS Logic = 0. Does nothing and may be used as a delimiter in an equation list; used as ‘Disable’ by other features. Logic = 1. Can be used as a test setting. GE Multilin F60 Feeder Protection System 5-81...
Page 194
RESET OP (COMMS) Communications source of the reset command RESET OP (OPERAND) Operand (assigned in the menu) INPUTS/OUTPUTS RESETTING source RESET OP (PUSHBUTTON) of the reset command Reset key (pushbutton) source of the reset command 5-82 F60 Feeder Protection System GE Multilin...
Page 195
2 to 16 any input is ‘1’ 2 to 16 all inputs are ‘1’ 2 to 16 all inputs are ‘0’ NAND 2 to 16 any input is ‘0’ only one input is ‘1’ GE Multilin F60 Feeder Protection System 5-83...
When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during testing, for example, it is suggested to power the unit down and then back up. 5-84 F60 Feeder Protection System GE Multilin...
DIGITAL ELEMENT 1 on Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–31: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin F60 Feeder Protection System 5-85...
Page 198
Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-86 F60 Feeder Protection System GE Multilin...
Page 199
87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin F60 Feeder Protection System 5-87...
Page 200
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-88 F60 Feeder Protection System GE Multilin...
TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". • TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". GE Multilin F60 Feeder Protection System 5-89...
Page 202
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-90 F60 Feeder Protection System GE Multilin...
Page 203
The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin F60 Feeder Protection System 5-91...
Page 205
“Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. GE Multilin F60 Feeder Protection System 5-93...
Each of the six setting group menus is identical. (the default active group) automatically becomes active if SETTING GROUP 1 no other group is active (see the Control Elements section for additional details). GE Multilin F60 Feeder Protection System 5-95...
Page 208
The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of the load encroachment characteristics used to block the quadrilateral distance element. 5-96 F60 Feeder Protection System GE Multilin...
Page 209
LOAD ENCHR DPO Load Encroachment LOAD ENCROACHMENT LOAD ENCROACHMENT LOAD ENCHR OP Characteristic SOURCE: MIN VOLT: Pos Seq Voltage (V_1) V_1 > Pickup Pos Seq Current (I_1) 827847A2.CDR Figure 5–43: LOAD ENCROACHMENT SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-97...
Page 210
(2) phase directional overcurrent elements. b) INVERSE TIME OVERCURRENT CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
Page 213
= characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–16: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
Page 214
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The F60 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. 5-102 F60 Feeder Protection System GE Multilin...
Page 215
(Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. GE Multilin F60 Feeder Protection System 5-103...
Page 216
Multiplier PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–45: PHASE TOC1 SCHEME LOGIC 5-104 F60 Feeder Protection System GE Multilin...
Page 217
Off = 0 PHASE IOC1 PKP SETTING PHASE IOC1 OP PHASE IOC1 BLOCK-B: PHASE IOC1 DPO Off = 0 SETTING 827033A6.VSD PHASE IOC1 BLOCK-C: Off = 0 Figure 5–46: PHASE IOC1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-105...
Page 218
CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two phase directional elements should be programmed with opposite element characteristic angle (ECA) settings. 5-106 F60 Feeder Protection System GE Multilin...
Page 219
Therefore, a coordination time of at least 10 ms must be added to all the instantaneous protec- tion elements under the supervision of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. GE Multilin F60 Feeder Protection System 5-107...
Page 220
MESSAGE DIRECTIONAL OC1 NEUTRAL See page 5–111. MESSAGE DIRECTIONAL OC2 The F60 Feeder Protection System has two (2) Neutral Time Overcurrent, two (2) Neutral Instantaneous Overcurrent, and two (2) Neutral Directional Overcurrent elements. 5-108 F60 Feeder Protection System GE Multilin...
Page 221
NEUTRAL TOC 1 SETTING NEUTRAL TOC1 PKP RESET: NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–49: NEUTRAL TOC1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-109...
Page 223
× × (EQ 5.17) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. GE Multilin F60 Feeder Protection System 5-111...
Page 224
The reverse-looking function is designed to be faster as compared to the forward- looking function and should be used for the blocking direction. This allows for better protection coordination. 5-112 F60 Feeder Protection System GE Multilin...
Page 225
If "Dual" polarizing is selected, the element performs both directional comparisons as described above. A given direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward and reverse) indication occurs, the forward direction overrides the reverse direction. GE Multilin F60 Feeder Protection System 5-113...
Page 226
NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the reverse direction. When selecting this setting it must be kept in mind that the design uses a ‘positive-sequence restraint’ technique for the “Calculated 3I0” mode of operation. 5-114 F60 Feeder Protection System GE Multilin...
Page 227
3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN _1 IS BELOW 0.8pu NEUTRAL DIR OC1 POS- SEQ RESTRAINT: 3( _0 - K _1 ) PICKUP 827077AB.CDR PICKUP Figure 5–52: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC GE Multilin F60 Feeder Protection System 5-115...
Page 228
This setting allows selecting between the internally calculated neutral voltage, or externally supplied voltage (broken delta VT connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel 5-116 F60 Feeder Protection System GE Multilin...
Page 229
⎛ ⎞ FlexCurve --------- - (EQ 5.20) ⎝ ⎠ Again, the FlexCurve timer starts after the definite time timer expires. GE Multilin F60 Feeder Protection System 5-117...
Page 233
The F60 relay provides two (2) negative-sequence time overcurrent elements, two (2) negative-sequence instantaneous overcurrent elements, and two (2) negative-sequence directional overcurrent elements. For additional information on the negative sequence time overcurrent curves, refer to the Inverse Time Overcurrent Curves section earlier. GE Multilin F60 Feeder Protection System 5-121...
Page 236
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative- and zero- sequence currents resulting from: • System unbalances under heavy load conditions. • Transformation errors of current transformers (CTs). • Fault inception and switch-off transients. 5-124 F60 Feeder Protection System GE Multilin...
This allows for better protection coordination. The above bias should be taken into account when using the negative-sequence directional overcurrent element to directionalize other protection elements. GE Multilin F60 Feeder Protection System 5-125...
Page 238
NEG SEQ DIR OC1 REV NEG SEQ DIR OC1 POS- Neg Sequence SEQ RESTRAINT: Zero Sequence _2 - K _1 PICKUP 827091A4.CDR _0 - K _1 PICKUP Figure 5–60: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC 5-126 F60 Feeder Protection System GE Multilin...
Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu GE Multilin F60 Feeder Protection System 5-127...
Page 240
This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes into a fault; the protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of closing, but does not yet have current flowing through it. 5-128 F60 Feeder Protection System GE Multilin...
Page 242
Note that in bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be significantly longer than the normal interrupting time. • BF1 USE TIMER 3: If set to "Yes", the Slow Path is operational. 5-130 F60 Feeder Protection System GE Multilin...
Page 243
1-pole breaker failure schemes. Upon operation of the breaker failure element for a single pole trip command, a 3-pole trip command should be given via output operand BKR FAIL 1 TRIP OP GE Multilin F60 Feeder Protection System 5-131...
Page 244
BF1 SOURCE : Initiated Ph C PICKUP : TO SHEET 2 OF 2 PICKUP PICKUP PICKUP TO SHEET 2 OF 2 (827070.CDR) 827069A5.CDR Figure 5–63: BREAKER FAILURE 1-POLE [INITIATE] (Sheet 1 of 2) 5-132 F60 Feeder Protection System GE Multilin...
Page 245
BF1 BKR POS2 FLEXLOGIC OPERAND Off=0 BKR FAIL 1 T3 OP SETTING BF1 BKR POS2 Off=0 SETTING BF1 BREAKER TEST ON: Off=0 827070A4.CDR Figure 5–64: BREAKER FAILURE 1-POLE [TIMERS] (Sheet 2 of 2) GE Multilin F60 Feeder Protection System 5-133...
Page 246
5.5 GROUPED ELEMENTS 5 SETTINGS Figure 5–65: BREAKER FAILURE 3-POLE [INITIATE] (Sheet 1 of 2) 5-134 F60 Feeder Protection System GE Multilin...
Page 247
5 SETTINGS 5.5 GROUPED ELEMENTS Figure 5–66: BREAKER FAILURE 3-POLE [TIMERS] (Sheet 2 of 2) GE Multilin F60 Feeder Protection System 5-135...
The time delay is adjustable from 0 to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char- acteristic. 5-136 F60 Feeder Protection System GE Multilin...
Page 249
V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–67: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the setting. UNDERVOLTAGE DELAY NOTE GE Multilin F60 Feeder Protection System 5-137...
Page 250
Source VT = Wye FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–68: PHASE UNDERVOLTAGE1 SCHEME LOGIC 5-138 F60 Feeder Protection System GE Multilin...
Page 252
“Definite time”. The source assigned to this element must be configured for a phase NEUTRAL OV1(3) CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–70: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC 5-140 F60 Feeder Protection System GE Multilin...
Page 253
NEG SEQ OV1 DPO NEG SEQ OV1 OP SETTING ≥ V_2 or 3 × V_2 PKP NEG SEQ OV1 SIGNAL SOURCE: Wye VT Delta VT 3 × V_2 827839A3.CDR Figure 5–71: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-141...
Page 254
Vx Pickup AUX UV1 PKP AUX UV1 DPO SETTING SETTING AUX UV1 OP AUX UV1 MINIMUM AUX UV1 SIGNAL VOLTAGE: SOURCE: < AUX VOLT Vx Vx Minimum 827849A2.CDR Figure 5–72: AUXILIARY UNDERVOLTAGE SCHEME LOGIC 5-142 F60 Feeder Protection System GE Multilin...
Page 255
AUX OV1 RESET Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–73: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-143...
The operating quantity is displayed in the actual ACTUAL VALUES METERING SENSITIVE DIRECTIONAL POWER 1(2) value. The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively. 5-144 F60 Feeder Protection System GE Multilin...
Page 258
DIR POWER 1 OP Three-phase reactive power (Q) DIR POWER 1 STG2 DPO DIR POWER 1 STG2 OP SETTING DIR POWER 1 STG2 DELAY: 100 ms 842003A3.CDR Figure 5–76: SENSITIVE DIRECTIONAL POWER SCHEME LOGIC 5-146 F60 Feeder Protection System GE Multilin...
The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 GE Multilin F60 Feeder Protection System 5-147...
Page 261
A user-programmable pushbutton is typically configured as the acknowledging input. • SELECTOR 1 3BIT A0, A1, and A2: These settings specify a 3-bit control input of the selector. The 3-bit control word pre-selects the position using the following encoding convention: POSITION rest GE Multilin F60 Feeder Protection System 5-149...
Page 262
The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the 3-bit control input has not been confirmed before the time out. 5-150 F60 Feeder Protection System GE Multilin...
Page 263
3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–78: TIME-OUT MODE GE Multilin F60 Feeder Protection System 5-151...
Page 264
3BIT A2 3BIT ACK POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842736A1.CDR Figure 5–79: ACKNOWLEDGE MODE 5-152 F60 Feeder Protection System GE Multilin...
Page 265
Finally, assign configure User-Programmable Pushbutton 1 by making the following changes in the SETTINGS PRODUCT menu: SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 “Self-reset” PUSHBUTTON 1 FUNCTION: “0.10 s” PUSHBUTTON 1 DROP-OUT TIME: The logic for the selector switch is shown below: GE Multilin F60 Feeder Protection System 5-153...
If the control systems of the system gen- erators do not respond fast enough, the system may collapse. A reliable method to quickly restore the balance between 5-154 F60 Feeder Protection System GE Multilin...
The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage chan- nel, current channel A, ground current channel. The first available signal is used for frequency calculation. GE Multilin F60 Feeder Protection System...
Page 268
OVERFREQ 1 BLOCK: OVERFREQ 1 RESET OVERFREQ 1 PKP DELAY : Off = 0 OVERFREQ 1 DPO OVERFREQ 1 OP SETTING ≥ PICKUP OVERFREQ 1 SOURCE: Frequency 827832A5.CDR Figure 5–82: OVERFREQUENCY SCHEME LOGIC 5-156 F60 Feeder Protection System GE Multilin...
FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element. The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set the pickup threshold to zero if no overcurrent supervision is required. GE Multilin F60 Feeder Protection System 5-157...
Page 270
SETTINGS FREQ RATE 1 PKP FREQ RATE 1 MIN FREQUENCY: FREQ RATE 1 MAX FREQUENCY: F > MIN & F < MAX Calculate df/dt 832023A2.CDR Figure 5–83: FREQUENCY RATE OF CHANGE SCHEME LOGIC 5-158 F60 Feeder Protection System GE Multilin...
ΔF. This time can be calculated by: ------------------------------- - (EQ 5.25) 360° ----------------- - × ΔF 2 ΔΦ × where: ΔΦ = phase angle difference in degrees; ΔF = frequency difference in Hz. GE Multilin F60 Feeder Protection System 5-159...
Page 272
SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this mag- nitude, the V2 voltage input used for synchrocheck will be considered “Live” or energized. 5-160 F60 Feeder Protection System GE Multilin...
Page 273
The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. GE Multilin F60 Feeder Protection System 5-161...
Page 274
SETTING CALCULATE SYNC1 SYNC DPO SYNCHK1 MAX FREQ Magnitude V2 SYNCHK1 V2 SIGNAL HYSTERESIS: SOURCE: Angle Calculate I F1-F2 I= SRC 2 Frequency F2 ACTUAL VALUE SYNC1: 827076AA.CDR Figure 5–84: SYNCHROCHECK SCHEME LOGIC 5-162 F60 Feeder Protection System GE Multilin...
4.000 s Range: FlexLogic™ operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic™ operand AR1 ADD DELAY 2: MESSAGE GE Multilin F60 Feeder Protection System 5-163...
Page 276
Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). 5-164 F60 Feeder Protection System GE Multilin...
Page 277
‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE GE Multilin F60 Feeder Protection System 5-165...
Page 278
5.6 CONTROL ELEMENTS 5 SETTINGS To sheet 2 Figure 5–85: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) 5-166 F60 Feeder Protection System GE Multilin...
Page 279
5 SETTINGS 5.6 CONTROL ELEMENTS Figure 5–86: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) GE Multilin F60 Feeder Protection System 5-167...
Page 280
5.6 CONTROL ELEMENTS 5 SETTINGS Figure 5–87: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT 5-168 F60 Feeder Protection System GE Multilin...
Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A). GE Multilin F60 Feeder Protection System...
Page 282
The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR Setup example shown): setting should be greater than the operating time of the breaker to avoid nuisance PICKUP DELAY alarms. NOTE 5-170 F60 Feeder Protection System GE Multilin...
Page 283
RESISTANCE POWER SUPPLY (V DC) (OHMS) (WATTS) I = Current Monitor 1000 5000 V = Voltage Monitor 10000 25000 By-pass 25000 Resistor 50000 Trip Coil 827074A2.VSD DC– Figure 5–90: TRIP CIRCUIT EXAMPLE 2 GE Multilin F60 Feeder Protection System 5-171...
–2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are blocked. 5-172 F60 Feeder Protection System GE Multilin...
Page 285
COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–91: DIGITAL COUNTER SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-173...
Range: 1 to 999 A/2cycle in steps of 1 HI-Z PHASE RATE OF MESSAGE CHANGE: 150 A/2cycle Range: 1 to 999 A/2cycle in steps of 1 HI-Z NEUTRAL RATE OF MESSAGE CHANGE: 150 A/2cycle 5-174 F60 Feeder Protection System GE Multilin...
Page 287
High-Z Data Capture: Hi-Z Data Captures are triggered and maintained in an identical manner as RMS Data Cap- tures. The relay maintains four captures of 300 records each. The capture frequency is 1 Hz and the data collected is defined in the following two tables. GE Multilin F60 Feeder Protection System 5-175...
Page 288
“enough times” means. If these criteria are met, the algorithm temporarily moves to either the “Arcing” state or the “Downed Conductor” state, the difference being determined by whether or not there was a 5-176 F60 Feeder Protection System GE Multilin...
Page 289
The Hi-Z detection algorithms will ignore all data as long as an overcurrent condition exists on the system, because it is assumed that conventional feeder overcurrent protection GE Multilin F60 Feeder Protection System...
Page 290
For the first three to five days after installation (or after being out-of-service for a sig- NOTE nificant period), the F60 may identify some of this noise as arcing. This should be taken into account when responding to alarms during these type of operating periods. 5-178 F60 Feeder Protection System GE Multilin...
Page 291
IC EVEN % > PKP > 0 VOLTAGE SUPERVISION ALG. SETTING HI-Z VOLTAGE SUPV SETTING THRESHOLD: HI-Z VOLTAGE SUPV DELAY: VA % > PKP VB % > PKP VC % > PKP 827838A8.CDR Figure 5–92: HI-Z SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-179...
Page 292
• BKR 1(2) ARC AMP LIMIT: Selects the threshold value above which the output operand is set. 5-180 F60 Feeder Protection System GE Multilin...
Page 293
BKR 1 ARCING AMP C Φ 827071A3.CDR BKR 1 OPERATING TIME A Φ BKR 1 OPERATING TIME B Φ BKR 1 OPERATING TIME C Φ BKR 1 OPERATING TIME Figure 5–94: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-181...
Page 294
Voltage drop measured from either side of the breaker during the flashover period, Voltage difference drop, and Measured flashover current through the breaker. Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across the breaker. 5-182 F60 Feeder Protection System GE Multilin...
Page 295
This application do not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than the setting. However, monitoring the breaker contact will ensure scheme stability. BRK 1(2) FLSHOVR DIFF V PKP GE Multilin F60 Feeder Protection System 5-183...
Page 296
Supervision can be provided by operation of other protection elements, breaker failure, and close and trip commands. A 6-cycle time delay applies after the selected FlexLogic™ operand resets. 5-184 F60 Feeder Protection System GE Multilin...
Page 297
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive sequence voltage and current are both below threshold levels. The function setting enables and disables the fuse failure feature for each source. GE Multilin F60 Feeder Protection System 5-185...
During the cold load condition, the current level can be above the pickup setting of some protection elements, so this feature can be used to prevent the tripping that would otherwise be caused by the normal settings. 5-186 F60 Feeder Protection System GE Multilin...
Page 299
The reset delay interval is intended to be set to a period until the ON-LOAD TIME BEFORE RESET feeder load has decayed to normal levels, after which other features may be used to switch setting groups. Figure 5–98: COLD LOAD PICKUP SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-187...
If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-188 F60 Feeder Protection System GE Multilin...
Page 301
TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–100: TRIP BUS LOGIC GE Multilin F60 Feeder Protection System 5-189...
Page 302
The update is performed at the beginning of the protection pass so all protection and control functions, as well as FlexLogic™ equations, are fed with the updated states of the contact inputs. 5-190 F60 Feeder Protection System GE Multilin...
Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin F60 Feeder Protection System 5-191...
Page 306
Application Example 3: A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement this functionality as described below: 5-194 F60 Feeder Protection System GE Multilin...
FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin F60 Feeder Protection System 5-195...
LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a F60 relay, the device ID that identifies the originator of the message is programmed in the SETTINGS PRODUCT SETUP setting. INSTALLATION RELAY NAME 5-196 F60 Feeder Protection System GE Multilin...
REMOTE IN 1 DEFAULT STATE the remote device sending the point is declared to be non-communicating. The following choices are available: GE Multilin F60 Feeder Protection System 5-197...
GSSE/GOOSE CONFIGURATION Range: 1 to 60 s in steps of 1 DEFAULT GSSE/GOOSE UPDATE TIME: 60 s For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the Remote Devices section. NOTE 5-198 F60 Feeder Protection System GE Multilin...
DIRECT INPUT 1 DEFAULT STATE state is not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 0. When communication resumes, the input becomes fully operational. GE Multilin F60 Feeder Protection System 5-199...
Page 312
2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below. UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–104: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME 5-200 F60 Feeder Protection System GE Multilin...
Page 313
Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown below. The scheme output operand is used to key the permission. HYB POTT TX1 UR IED 1 UR IED 2 UR IED 3 842714A1.CDR Figure 5–106: SINGLE-CHANNEL OPEN-LOOP CONFIGURATION GE Multilin F60 Feeder Protection System 5-201...
Page 314
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, Direct Inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip ( HYB POTT setting). 5-202 F60 Feeder Protection System GE Multilin...
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On” and logic 0 for “Latest/Off”. GE Multilin F60 Feeder Protection System 5-203...
Page 316
(On 3-terminal system or 2-terminal (same for 1-2...1-16) SETTING with redundant channel) FLEXLOGIC OPERAND TELEPROT OUTPUT 2-1: (same for 2-2...2-16) Fail TELEPRO INPUT 2-1 On Off (Flexlogic Operand) (same for 1-2...1-16) 842750A2.CDR Figure 5–108: TELEPROTECTION INPUT/OUTPUT PROCESSING 5-204 F60 Feeder Protection System GE Multilin...
–20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin F60 Feeder Protection System 5-205...
1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-206 F60 Feeder Protection System GE Multilin...
Range: –90.000 to 90.000 pu in steps of 0.001 DCMA OUTPUT H1 MESSAGE MIN VAL: 0.000 pu Range: –90.000 to 90.000 pu in steps of 0.001 DCMA OUTPUT H1 MESSAGE MAX VAL: 1.000 pu GE Multilin F60 Feeder Protection System 5-207...
Page 320
DCMA OUTPUT H1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This setting is used to control the mapping between an internal analog value and the output current (see the following 5-208 F60 Feeder Protection System GE Multilin...
Page 321
The minimum and maximum power values to be monitored (in pu) are: 0 kA 6.3 kA minimum current ----------- - 0 pu, maximum current ---------------- - 1.26 pu (EQ 5.35) 5 kA 5 kA The following settings should be entered: GE Multilin F60 Feeder Protection System 5-209...
Page 322
254.03 kV 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-210 F60 Feeder Protection System GE Multilin...
Mode LED will be On, indicating that the relay is in Test Mode. The state of each contact input may be programmed as “Dis- abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled. GE Multilin F60 Feeder Protection System...
USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION remote input 1 to initiate the Test mode, make the following changes in the menu: SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: 5-212 F60 Feeder Protection System GE Multilin...
Page 325
STATUS EGD PROTOCOL See page 6-8. STATUS TELEPROT CH TESTS See page 6-9. ACTUAL VALUES SOURCE SRC 1 See page 6-13. METERING SOURCE SRC 2 See page 6-13. SENSITIVE See page 6-19. DIRECTIONAL POWER GE Multilin F60 Feeder Protection System...
See page 6-22. OSCILLOGRAPHY See page 6-23. DATA LOGGER See page 6-23. MAINTENANCE See page 6-24. HIZ RECORDS See page 6-24. ACTUAL VALUES MODEL INFORMATION See page 6-25. PRODUCT INFO FIRMWARE REVISIONS See page 6-25. F60 Feeder Protection System GE Multilin...
The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin F60 Feeder Protection System...
For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output. F60 Feeder Protection System GE Multilin...
DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented whenever a GSSE message is sent. This number will rollover to zero when a count of 4,294,967,295 is incremented. GE Multilin F60 Feeder Protection System...
PATH: ACTUAL VALUES STATUS ETHERNET Range: Fail, OK ETHERNET ETHERNET PRI LINK STATUS: OK Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: OK These values indicate the status of the primary and secondary Ethernet links. F60 Feeder Protection System GE Multilin...
The UNRETURNED MSG COUNT CRC FAIL COUNT values can be cleared using the command. CLEAR DIRECT I/O COUNTERS values represent the state of each direct input. DIRECT INPUT 1(32) GE Multilin F60 Feeder Protection System...
SLOW EXCHANGE 1 SIGNATURE: SLOW EXCHANGE 1 MESSAGE DATA LENGTH: These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size for the slow EGD exchanges are displayed. F60 Feeder Protection System GE Multilin...
“FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan- nel is failed, or if the teleprotection inputs/outputs are not enabled. GE Multilin F60 Feeder Protection System...
PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS 6-10 F60 Feeder Protection System GE Multilin...
Page 335
ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. GE Multilin F60 Feeder Protection System 6-11...
Page 336
SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure. SYSTEM VOLTAGES SYMMETRICAL COMPONENTS WYE VTs DELTA VTs 827844A1.CDR Figure 6–3: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS 6-12 F60 Feeder Protection System GE Multilin...
Page 341
The signal used for frequency estimation is low-pass filtered. The SYSTEM SETUP POWER SYSTEM final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and transients. GE Multilin F60 Feeder Protection System 6-17...
Page 342
The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental ampli- tude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the fundamental: … (EQ 6.2) 6-18 F60 Feeder Protection System GE Multilin...
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the setting in the menu. Refer to the FREQUENCY AND PHASE REFERENCE SETTINGS SYSTEM SETUP POWER SYSTEM Power System section of chapter 5 for additional details. GE Multilin F60 Feeder Protection System 6-19...
= maximum nominal primary RMS value of the +IN and –IN inputs BASE SYNCHROCHECK = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) 6-20 F60 Feeder Protection System GE Multilin...
RTD INPUT xx -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed Channel ID and the bottom line as the value. GE Multilin F60 Feeder Protection System 6-21...
If all 1024 event records have been filled, the oldest record will be removed as a new record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the event trigger. Refer to the menu for clearing event records. COMMANDS CLEAR RECORDS 6-22 F60 Feeder Protection System GE Multilin...
It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the menu for clearing data logger records. COMMANDS CLEAR RECORDS GE Multilin F60 Feeder Protection System 6-23...
If the element is triggered by high impedance fault detection arcing algorithm, then the records are dis- RMS 4 played in the actual values. Refer to High impedance fault detection section in chapter 5 for more information. HIZ 1 HIZ 4 6-24 F60 Feeder Protection System GE Multilin...
6.5 PRODUCT INFORMATION 6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format; MODEL INFORMATION ORDER CODE LINE 1: example order code shown F60-E00-HCH-F8F-H6A Range: standard GE multilin order code format...
Page 350
6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-26 F60 Feeder Protection System GE Multilin...
Range: No, Yes COMMANDS CLEAR FAULT REPORTS? CLEAR RECORDS Range: No, Yes CLEAR EVENT RECORDS? Range: No, Yes CLEAR OSCILLOGRAPHY? Range: No, Yes CLEAR DATA LOGGER? Range: No, Yes CLEAR BREAKER 1 ARCING AMPS? No GE Multilin F60 Feeder Protection System...
Page 352
If an update occurs, the following message is shown. UPDATING... PLEASE WAIT There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER message will be shown. CODE NOT UPDATED F60 Feeder Protection System GE Multilin...
All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE b) MAJOR SELF-TEST ERROR MESSAGES The major self-test errors are listed and described below. GE Multilin F60 Feeder Protection System...
Page 354
PRODUCT SETUP INSTALLATION RELAY SETTINGS c) MINOR SELF-TEST ERROR MESSAGES Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in chap- ter 5 for additional details. F60 Feeder Protection System GE Multilin...
Page 355
Latched target message: No. • Description of problem: The SNTP server is not responding. • How often the test is performed: Every 10 to 60 seconds. • What to do: Check SNTP configuration and network connections. GE Multilin F60 Feeder Protection System...
Page 356
Description of problem: Abnormal restart from modules being removed or inserted while the F60 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. • How often the test is performed: Event driven. • What to do: Contact the factory. F60 Feeder Protection System GE Multilin...
50 Hz system, it consists of a sum of the 25, 75, 125,..., 625 Hz components. If the Energy Algorithm detects a sudden, sustained increase in one of these component energies, it reports this to the Expert Arc Detector algorithm, resets itself, and continues to monitor for another sudden increase. GE Multilin F60 Feeder Protection System...
The duration over which the algorithm inhibits the setting of the overcurrent flag(s) is from the time the even-harmonic level (as a percentage of RMS) increases above the threshold until one second after it falls back below the threshold. GE Multilin F60 Feeder Protection System...
If one phase voltage shows a dip, the block is applied for all phases. Also the High Impedance Oscillography will record that a voltage dip was experienced. The Oscillography record is phase specific. F60 Feeder Protection System GE Multilin...
Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults: ⋅ (EQ 8.7) GE Multilin F60 Feeder Protection System...
Page 362
SYS0 -- - V (EQ 8.14) – – SYS0 -- - V – – SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 F60 Feeder Protection System GE Multilin...
Page 363
FAULT TYPE FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 8–2: FAULT LOCATOR SCHEME GE Multilin F60 Feeder Protection System...
Page 364
8.2 FAULT LOCATOR 8 THEORY OF OPERATION F60 Feeder Protection System GE Multilin...
The injected frequency should smoothly ramp through the set threshold, with the ramp starting frequency sufficiently out- side the threshold so the relay becomes conditioned to the trend before operation. For typical interconnected power sys- tems, the recommended testing ramp rate is 0.20 Hz/s. GE Multilin F60 Feeder Protection System...
Page 366
20 ms. The tracking frequency should not be used in timing measurements, as its algorithm involves phase locking, which purposely sets its frequency high or low to allow the F60 sample clock to catch-up or wait as necessary to reach synchro- nism with the power system. F60 Feeder Protection System GE Multilin...
Source 2 ground current RMS 6230 SRC 2 Ig Mag Degrees Source 2 ground current magnitude 6232 SRC 2 Ig Angle Amps Source 2 ground current angle 6233 SRC 2 I_0 Mag Degrees Source 2 zero-sequence current magnitude GE Multilin F60 Feeder Protection System...
Page 368
SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS 6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS 6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude F60 Feeder Protection System GE Multilin...
Page 369
Source 2 phase A power factor 7226 SRC 2 Phase B PF Source 2 phase B power factor 7227 SRC 2 Phase C PF Source 2 phase C power factor 7552 SRC 1 Frequency Source 1 frequency GE Multilin F60 Feeder Protection System...
Page 370
Volts Source 1 phase B voltage seventh harmonic 8096 SRC 1 Vb Harm[6] Volts Source 1 phase B voltage eighth harmonic 8097 SRC 1 Vb Harm[7] Volts Source 1 phase B voltage ninth harmonic F60 Feeder Protection System GE Multilin...
Page 371
Volts Source 2 phase A voltage fourth harmonic 8143 SRC 2 Va Harm[3] Volts Source 2 phase A voltage fifth harmonic 8144 SRC 2 Va Harm[4] Volts Source 2 phase A voltage sixth harmonic GE Multilin F60 Feeder Protection System...
Page 372
Source 2 phase C voltage total harmonic distortion (THD) 8190 SRC 2 Vc Harm[0] Volts Source 2 phase C voltage second harmonic 8191 SRC 2 Vc Harm[1] Volts Source 2 phase C voltage third harmonic F60 Feeder Protection System GE Multilin...
Page 373
Degrees Fault 1 post-fault phase C current angle 9051 Postfault Va Mag [0] Volts Fault 1 post-fault phase A voltage magnitude 9053 Postfault Va Ang [0] Degrees Fault 1 post-fault phase A voltage angle GE Multilin F60 Feeder Protection System...
Page 374
Amps Source 1 phase B current eighth harmonic 10281 SRC 1 Ib Harm[7] Amps Source 1 phase B current ninth harmonic 10282 SRC 1 Ib Harm[8] Amps Source 1 phase B current tenth harmonic F60 Feeder Protection System GE Multilin...
Page 375
Amps Source 2 phase A current fifth harmonic 10344 SRC 2 Ia Harm[4] Amps Source 2 phase A current sixth harmonic 10345 SRC 2 Ia Harm[5] Amps Source 2 phase A current seventh harmonic GE Multilin F60 Feeder Protection System...
Page 376
Source 2 phase C current second harmonic 10407 SRC 2 Ic Harm[1] Amps Source 2 phase C current third harmonic 10408 SRC 2 Ic Harm[2] Amps Source 2 phase C current fourth harmonic A-10 F60 Feeder Protection System GE Multilin...
Page 377
23 actual value 13550 DCMA Inputs 24 Value dcmA input 24 actual value 13552 RTD Inputs 1 Value RTD input 1 actual value 13553 RTD Inputs 2 Value RTD input 2 actual value GE Multilin F60 Feeder Protection System A-11...
Page 378
RTD Inputs 46 Value RTD input 46 actual value 13598 RTD Inputs 47 Value RTD input 47 actual value 13599 RTD Inputs 48 Value RTD input 48 actual value 24459 Active Setting Group Current setting group A-12 F60 Feeder Protection System GE Multilin...
Page 379
45610 GOOSE Analog In 14 IEC 61850 GOOSE analog input 14 45612 GOOSE Analog In 15 IEC 61850 GOOSE analog input 15 45614 GOOSE Analog In 16 IEC 61850 GOOSE analog input 16 GE Multilin F60 Feeder Protection System A-13...
Page 380
A.1 PARAMETER LIST APPENDIX A A-14 F60 Feeder Protection System GE Multilin...
Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin F60 Feeder Protection System...
No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC F60 Feeder Protection System GE Multilin...
1 to 127 though only a small subset is generally needed. The relay supports some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail. FUNCTION CODE MODBUS DEFINITION GE MULTILIN DEFINITION Read holding registers Read actual values or settings Read holding registers...
DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high F60 Feeder Protection System GE Multilin...
PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin F60 Feeder Protection System...
Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT F60 Feeder Protection System GE Multilin...
Page 387
“Number of Fault Reports' register. If the value changes, then the master reads all the new files. The contents of the file is in standard HTML notation and can be viewed via any commercial browser. GE Multilin F60 Feeder Protection System...
Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be re-entered after disconnecting and re-connecting on TCP/IP. F60 Feeder Protection System GE Multilin...
0 (Off) 0419 Virtual Input 26 State 0 to 1 F108 0 (Off) 041A Virtual Input 27 State 0 to 1 F108 0 (Off) 041B Virtual Input 28 State 0 to 1 F108 0 (Off) GE Multilin F60 Feeder Protection System...
Page 390
...Repeated for Digital Counter 7 0838 ...Repeated for Digital Counter 8 FlexStates (Read Only) 0900 FlexState Bits (16 items) 0 to 65535 F001 Element States (Read Only) 1000 Element Operate States (64 items) 0 to 65535 F502 B-10 F60 Feeder Protection System GE Multilin...
Page 391
Source 1 Phase A Current RMS 0 to 999999.999 0.001 F060 1802 Source 1 Phase B Current RMS 0 to 999999.999 0.001 F060 1804 Source 1 Phase C Current RMS 0 to 999999.999 0.001 F060 GE Multilin F60 Feeder Protection System B-11...
Page 392
Source 1 Positive Sequence Voltage Angle -359.9 to 0 degrees F002 1A29 Source 1 Negative Sequence Voltage Magnitude 0 to 999999.999 0.001 F060 1A2B Source 1 Negative Sequence Voltage Angle -359.9 to 0 degrees F002 B-12 F60 Feeder Protection System GE Multilin...
Page 393
Energy Clear Command 0 to 1 F126 0 (No) Source Frequency (Read Only) (6 modules) 1D80 Frequency for Source 1 F003 1D82 Frequency for Source 2 F003 1D84 Frequency for Source 3 F003 GE Multilin F60 Feeder Protection System B-13...
Page 394
21A9 Breaker 1 Flashover Status Closed A 0 to 65535 F300 21AA Breaker 1 Flashover Status Closed B 0 to 65535 F300 21AB Breaker 1 Flashover Status Closed C 0 to 65535 F300 B-14 F60 Feeder Protection System GE Multilin...
Page 395
Fault 1 Prefault Phase A Current Angle -359.9 to 0 degrees F002 2343 Fault 1 Prefault Phase B Current Magnitude 0 to 999999.999 0.001 F060 2345 Fault 1 Prefault Phase B Current Angle -359.9 to 0 degrees F002 GE Multilin F60 Feeder Protection System B-15...
Page 396
285B Reserved (8 items) 0 to 0.1 F001 2863 ...Repeated for Source 2 28C6 ...Repeated for Source 3 2929 ...Repeated for Source 4 298C ...Repeated for Source 5 29EF ...Repeated for Source 6 B-16 F60 Feeder Protection System GE Multilin...
Page 397
DCMA Inputs 3 Value -9999999 to 9999999 F004 34C6 DCMA Inputs 4 Value -9999999 to 9999999 F004 34C8 DCMA Inputs 5 Value -9999999 to 9999999 F004 34CA DCMA Inputs 6 Value -9999999 to 9999999 F004 GE Multilin F60 Feeder Protection System B-17...
Page 398
-32768 to 32767 °C F002 3510 RTD Input 33 Value -32768 to 32767 °C F002 3511 RTD Input 34 Value -32768 to 32767 °C F002 3512 RTD Input 35 Value -32768 to 32767 °C F002 B-18 F60 Feeder Protection System GE Multilin...
Page 399
Gateway IP Address 0 to 4294967295 F003 56554497 408D Network Address NSAP F074 409A DNP Channel 1 Port 0 to 4 F177 0 (None) 409B DNP Channel 2 Port 0 to 4 F177 0 (None) GE Multilin F60 Feeder Protection System B-19...
Page 400
DNP object 23 default variation 0 to 3 F523 0 (1) 4146 DNP object 30 default variation 1 to 5 F001 4147 DNP object 32 default variation 0 to 5 F525 0 (1) B-20 F60 Feeder Protection System GE Multilin...
Page 401
...Repeated for User-Programmable LED 6 428C ...Repeated for User-Programmable LED 7 428E ...Repeated for User-Programmable LED 8 4290 ...Repeated for User-Programmable LED 9 4292 ...Repeated for User-Programmable LED 10 4294 ...Repeated for User-Programmable LED 11 GE Multilin F60 Feeder Protection System B-21...
Page 402
4481 Phase CT 1 Secondary 0 to 1 F123 0 (1 A) 4482 Ground CT 1 Primary 1 to 65000 F001 4483 Ground CT 1 Secondary 0 to 1 F123 0 (1 A) B-22 F60 Feeder Protection System GE Multilin...
Page 403
Synchrocheck 1 Maximum Angle Difference 0 to 100 degrees F001 4786 Synchrocheck 1 Maximum Frequency Difference 0 to 2 0.01 F001 4787 Synchrocheck 1 Dead Source Select 0 to 5 F176 1 (LV1 and DV2) GE Multilin F60 Feeder Protection System B-23...
Page 404
User Programmable Pushbutton 1 Autoreset Function 0 to 1 F102 0 (Disabled) 4E25 User Programmable Pushbutton 1 Local Lock 0 to 65535 F300 4E26 User Programmable Pushbutton 1 Message Priority 0 to 2 F220 0 (Disabled) B-24 F60 Feeder Protection System GE Multilin...
Page 405
...Repeated for RTD Input 30 563A ...Repeated for RTD Input 31 564D ...Repeated for RTD Input 32 5660 ...Repeated for RTD Input 33 5673 ...Repeated for RTD Input 34 5686 ...Repeated for RTD Input 35 GE Multilin F60 Feeder Protection System B-25...
Page 406
Phase Time Overcurrent 1 Signal Source 0 to 5 F167 0 (SRC 1) 5902 Phase Time Overcurrent 1 Input 0 to 1 F122 0 (Phasor) 5903 Phase Time Overcurrent 1 Pickup 0 to 30 0.001 F001 1000 B-26 F60 Feeder Protection System GE Multilin...
Page 407
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules) 5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 F102 0 (Disabled) 5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 F167 0 (SRC 1) GE Multilin F60 Feeder Protection System B-27...
Page 408
...Repeated for Ground Instantaneous Overcurrent 6 5E60 ...Repeated for Ground Instantaneous Overcurrent 7 5E70 ...Repeated for Ground Instantaneous Overcurrent 8 5E80 ...Repeated for Ground Instantaneous Overcurrent 9 5E90 ...Repeated for Ground Instantaneous Overcurrent 10 B-28 F60 Feeder Protection System GE Multilin...
Page 409
Autoreclose 1 Dead Time Shot 1 0 to 655.35 0.01 F001 624C Autoreclose 1 Dead Time Shot 2 0 to 655.35 0.01 F001 624D Autoreclose 1 Dead Time Shot 3 0 to 655.35 0.01 F001 GE Multilin F60 Feeder Protection System B-29...
Page 410
Overfrequency (Read/Write Setting) (4 modules) 64D0 Overfrequency 1 Function 0 to 1 F102 0 (Disabled) 64D1 Overfrequency 1 Block 0 to 65535 F300 64D2 Overfrequency 1 Source 0 to 5 F167 0 (SRC 1) B-30 F60 Feeder Protection System GE Multilin...
Page 411
0 (SRC 1) 7042 Phase Overvoltage 1 Pickup 0 to 3 0.001 F001 1000 7043 Phase Overvoltage 1 Delay 0 to 600 0.01 F001 7044 Phase Overvoltage 1 Reset Delay 0 to 600 0.01 F001 GE Multilin F60 Feeder Protection System B-31...
Page 412
Breaker 1 Arcing Current Source 0 to 5 F167 0 (SRC 1) 72C2 Breaker 1 Arcing Current Initiate A 0 to 65535 F300 72C3 Breaker 1 Arcing Current Initiate B 0 to 65535 F300 B-32 F60 Feeder Protection System GE Multilin...
Page 413
1 to 999 A/2cycle F001 7A0C Hi-Z Loss of Load Threshold 5 to 100 F001 7A0D Hi-Z 3-Phase Event Threshold 1 to 1000 F001 7A0E Hi-Z Voltage Supervision Threshold 0 to 100 F001 GE Multilin F60 Feeder Protection System B-33...
Page 414
7E33 ...Repeated for Underfrequency 4 7E44 ...Repeated for Underfrequency 5 7E55 ...Repeated for Underfrequency 6 Neutral Overvoltage (Read/Write Grouped Setting) (3 modules) 7F00 Neutral Overvoltage 1 Function 0 to 1 F102 0 (Disabled) B-34 F60 Feeder Protection System GE Multilin...
Page 415
8403 EGD Fast Producer Exchange 1 Data Rate 50 to 1000 F001 1000 8404 EGD Fast Producer Exchange 1 Data Item 1 (20 items) 0 to 65535 F001 8418 Reserved (80 items) F001 GE Multilin F60 Feeder Protection System B-35...
Page 416
“Dig Element 1“ 8A09 Digital Element 1 Input 0 to 65535 F300 8A0A Digital Element 1 Pickup Delay 0 to 999999.999 0.001 F003 8A0C Digital Element 1 Reset Delay 0 to 999999.999 0.001 F003 B-36 F60 Feeder Protection System GE Multilin...
Page 417
8D84 ...Repeated for Digital Element 46 8D98 ...Repeated for Digital Element 47 8DAC ...Repeated for Digital Element 48 Trip Bus (Read/Write Setting) 8E00 Trip Bus 1 Function 0 to 1 F102 0 (Disabled) GE Multilin F60 Feeder Protection System B-37...
Page 418
...Repeated for FlexElement™ 3 903C ...Repeated for FlexElement™ 4 9050 ...Repeated for FlexElement™ 5 9064 ...Repeated for FlexElement™ 6 9078 ...Repeated for FlexElement™ 7 908C ...Repeated for FlexElement™ 8 90A0 ...Repeated for FlexElement™ 9 B-38 F60 Feeder Protection System GE Multilin...
Page 419
...Repeated for dcmA Output 24 Direct Input/Output Names (Read/Write Setting) (96 modules) 9400 Direct Input 1 Name 0 to 96 F205 “Dir Ip 1” 9406 Direct Output 1 Name 1 to 96 F205 “Dir Out 1” GE Multilin F60 Feeder Protection System B-39...
Page 420
Teleprotection Output 1-n Operand (16 items) 0 to 65535 F300 9B70 Teleprotection Output 2-n Operand (16 items) 0 to 65535 F300 Teleprotection Inputs/Outputs Commands (Read/Write Command) 9B90 Teleprotection Clear Lost Packets 0 to 1 F126 0 (No) B-40 F60 Feeder Protection System GE Multilin...
Page 421
FlexCurve C (120 items) 0 to 65535 F011 A680 FlexCurve D (120 items) 0 to 65535 F011 Non Volatile Latches (Read/Write Setting) (16 modules) A700 Non-Volatile Latch 1 Function 0 to 1 F102 0 (Disabled) GE Multilin F60 Feeder Protection System B-41...
Page 422
0 to 2 F109 0 (Self-reset) A908 Frequency Rate of Change 1 Events 0 to 1 F102 0 (Disabled) A909 Frequency Rate of Change 1 Source 0 to 5 F167 0 (SRC 1) B-42 F60 Feeder Protection System GE Multilin...
Page 423
F001 IEC 61850 GGIO4 analog input points configuration settings (read/write) AF10 IEC 61850 GGIO4 analog input 1 value F600 AF11 IEC 61850 GGIO4 analog input 1 deadband 0.001 to 100 0.001 F003 100000 GE Multilin F60 Feeder Protection System B-43...
Page 425
IEC 61850 GGIO2.CF.SPCSO20.ctlModel Value 0 to 2 F001 B254 IEC 61850 GGIO2.CF.SPCSO21.ctlModel Value 0 to 2 F001 B255 IEC 61850 GGIO2.CF.SPCSO22.ctlModel Value 0 to 2 F001 B256 IEC 61850 GGIO2.CF.SPCSO23.ctlModel Value 0 to 2 F001 GE Multilin F60 Feeder Protection System B-45...
Page 426
...Repeated for Report 3 B2F5 ...Repeated for Report 4 B31C ...Repeated for Report 5 B343 ...Repeated for Report 6 B36A ...Repeated for Report 7 B391 ...Repeated for Report 8 B3B8 ...Repeated for Report 9 B-46 F60 Feeder Protection System GE Multilin...
Page 427
...Repeated for Contact Input 11 BB58 ...Repeated for Contact Input 12 BB60 ...Repeated for Contact Input 13 BB68 ...Repeated for Contact Input 14 BB70 ...Repeated for Contact Input 15 BB78 ...Repeated for Contact Input 16 GE Multilin F60 Feeder Protection System B-47...
Page 428
...Repeated for Contact Input 65 BD08 ...Repeated for Contact Input 66 BD10 ...Repeated for Contact Input 67 BD18 ...Repeated for Contact Input 68 BD20 ...Repeated for Contact Input 69 BD28 ...Repeated for Contact Input 70 B-48 F60 Feeder Protection System GE Multilin...
Page 429
...Repeated for Virtual Input 16 BEF0 ...Repeated for Virtual Input 17 BEFC ...Repeated for Virtual Input 18 BF08 ...Repeated for Virtual Input 19 BF14 ...Repeated for Virtual Input 20 BF20 ...Repeated for Virtual Input 21 GE Multilin F60 Feeder Protection System B-49...
Page 430
...Repeated for Virtual Output 3 C148 ...Repeated for Virtual Output 4 C150 ...Repeated for Virtual Output 5 C158 ...Repeated for Virtual Output 6 C160 ...Repeated for Virtual Output 7 C168 ...Repeated for Virtual Output 8 B-50 F60 Feeder Protection System GE Multilin...
Page 431
...Repeated for Virtual Output 57 C2F8 ...Repeated for Virtual Output 58 C300 ...Repeated for Virtual Output 59 C308 ...Repeated for Virtual Output 60 C310 ...Repeated for Virtual Output 61 C318 ...Repeated for Virtual Output 62 GE Multilin F60 Feeder Protection System B-51...
Page 432
...Repeated for Contact Output 2 C458 ...Repeated for Contact Output 3 C464 ...Repeated for Contact Output 4 C470 ...Repeated for Contact Output 5 C47C ...Repeated for Contact Output 6 C488 ...Repeated for Contact Output 7 B-52 F60 Feeder Protection System GE Multilin...
Page 433
...Repeated for Contact Output 56 C6E0 ...Repeated for Contact Output 57 C6EC ...Repeated for Contact Output 58 C6F8 ...Repeated for Contact Output 59 C704 ...Repeated for Contact Output 60 C710 ...Repeated for Contact Output 61 GE Multilin F60 Feeder Protection System B-53...
Page 434
...Repeated for Direct Input 7 C8AC ...Repeated for Direct Input 8 C8B0 ...Repeated for Direct Input 9 C8B4 ...Repeated for Direct Input 10 C8B8 ...Repeated for Direct Input 11 C8BC ...Repeated for Direct Input 12 B-54 F60 Feeder Protection System GE Multilin...
Page 435
...Repeated for Direct Output 27 CA46 ...Repeated for Direct Output 28 CA48 ...Repeated for Direct Output 29 CA4A ...Repeated for Direct Output 30 CA4C ...Repeated for Direct Output 31 CA4E ...Repeated for Direct Output 32 GE Multilin F60 Feeder Protection System B-55...
Page 436
...Repeated for Remote Input 4 CFC8 ...Repeated for Remote Input 5 CFD2 ...Repeated for Remote Input 6 CFDC ...Repeated for Remote Input 7 CFE6 ...Repeated for Remote Input 8 CFF0 ...Repeated for Remote Input 9 B-56 F60 Feeder Protection System GE Multilin...
Page 437
...Repeated for Remote Output 23 D27C ...Repeated for Remote Output 24 D280 ...Repeated for Remote Output 25 D284 ...Repeated for Remote Output 26 D288 ...Repeated for Remote Output 27 D28C ...Repeated for Remote Output 28 GE Multilin F60 Feeder Protection System B-57...
Page 438
...Repeated for Remote Device 8 D3A0 ...Repeated for Remote Device 9 D3A4 ...Repeated for Remote Device 10 D3A8 ...Repeated for Remote Device 11 D3AC ...Repeated for Remote Device 12 D3B0 ...Repeated for Remote Device 13 B-58 F60 Feeder Protection System GE Multilin...
A FlexCurve is an array of 120 consecutive data points (x, y) which are interpolated to generate a smooth curve. The y-axis is the user defined trip or operation time setting; the x-axis is the pickup ratio GE Multilin F60 Feeder Protection System B-59...
Page 440
0 = Restore, 1 = Synchronize, 2 = Sync/Restore F108 ENUMERATION: OFF/ON 0 = Off, 1 = On F086 ENUMERATION: DIGITAL INPUT DEFAULT STATE 0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On B-60 F60 Feeder Protection System GE Multilin...
Page 442
Ground Instantaneous Overcurrent 12 Synchrocheck 2 Ground Time Overcurrent 1 Cold load pickup 1 Ground Time Overcurrent 2 Cold load pickup 2 Ground Time Overcurrent 3 Setting Group Ground Time Overcurrent 4 Reset B-62 F60 Feeder Protection System GE Multilin...
Page 443
Digital Element 45 Digital Counter 1 Digital Element 46 Digital Counter 2 Digital Element 47 Digital Counter 3 Digital Element 48 Digital Counter 4 Trip Bus 1 Digital Counter 5 Trip Bus 2 GE Multilin F60 Feeder Protection System B-63...
Page 445
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A, Maintenance Alert 6 = Notched 2 A Maintenance Alert Maintenance Alert F142 ENUMERATION: EVENT RECORDER ACCESS FILE TYPE 0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause GE Multilin F60 Feeder Protection System B-65...
Page 446
4 = Group 4, 5 = Group 5, 6 = Group 6 Ethernet Port 1 Offline Ethernet Port 2 Offline F155 Ethernet Port 3 Offline ENUMERATION: REMOTE DEVICE STATE Ethernet Port 4 Offline 0 = Offline, 1 = Online B-66 F60 Feeder Protection System GE Multilin...
Page 447
0 = A, 1 = B, 2 = C F166 ENUMERATION: AUXILIARY VT CONNECTION TYPE 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca GE Multilin F60 Feeder Protection System B-67...
Page 448
ARCING LOSS OF LOAD DOWNED CONDUCTOR ARCING SUSPECTED ARCING F188 OVERCURRENT ENUMERATION: HI-Z CAPTURE TRIGGER TYPES DOWNED CONDUCTOR EXTERNAL bitmask trigger type None Loss Of Load Arc Suspected Arcing Overcurrent Down Conductor B-68 F60 Feeder Protection System GE Multilin...
Page 453
ENUMERATION: REAL TIME CLOCK DAY [13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64) [14] REMOTE INPUTS (1 to 32) value [28] INSERT (via keypad only) [32] END Sunday [34] NOT (1 INPUT) GE Multilin F60 Feeder Protection System B-73...
Page 454
Each bit contains the operate state for an element. See the F124 format code for a list of element IDs. The operate bit for element ID 11TH 23RD X is bit [X mod 16] in register [X/16]. 12TH 24TH 13TH 25TH B-74 F60 Feeder Protection System GE Multilin...
Page 455
UR_UINT16: FLEXANALOG PARAMETER Corresponds to the modbus address of the value used when this parameter is selected. Only certain values may be used as Flex- Analogs (basically all metering quantities used in protection). GE Multilin F60 Feeder Protection System B-75...
Page 456
B.4 MEMORY MAPPING APPENDIX B B-76 F60 Feeder Protection System GE Multilin...
System Specification Description (SSD) file. The entire substation con- figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ- ual ICD files and the SSD file. GE Multilin F60 Feeder Protection System...
GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available from GGIO4 in order to obtain the analog values provided by GGIO4. F60 Feeder Protection System GE Multilin...
The following list describes the protection elements for all UR-series relays. The F60 relay will contain a subset of protec- tion elements from this list. • PDIF: bus differential, transformer instantaneous differential, transformer percent differential GE Multilin F60 Feeder Protection System...
Page 460
IEC 61850 control model. • XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. F60 Feeder Protection System GE Multilin...
F60. This attribute is programmed through the setting and its LOCATION default value is “Location”. This value should be changed to describe the actual physical location of the F60. GE Multilin F60 Feeder Protection System...
The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a F60 relay with an MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc. F60 Feeder Protection System GE Multilin...
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the F60. The F60 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data transfer between devices. GE Multilin F60 Feeder Protection System...
Page 464
Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIG- settings menu: URABLE GOOSE 1 F60 Feeder Protection System GE Multilin...
(for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can be different for each Ethernet frame depending on the intended destination of the frame. GE Multilin F60 Feeder Protection System...
DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block. These strings are automatically populated and interpreted by the F60; no settings are required. C-10 F60 Feeder Protection System GE Multilin...
An ICD file is generated for the F60 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
It can also import a system SCL file (SCD) to set communication configuration parame- ters (that is, required addresses, reception GOOSE datasets, IDs of incoming GOOSE datasets, etc.) for the IED. The IED configurator functionality is implemented in the GE Multilin EnerVista UR Setup software. C.5.2 CONFIGURING IEC 61850 SETTINGS Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED.
Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
Page 470
Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 F60 Feeder Protection System GE Multilin...
Page 471
RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin F60 Feeder Protection System C-15...
Page 472
BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 F60 Feeder Protection System GE Multilin...
C.5.5 ABOUT SCD FILES System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI version 4.6 or above and ASE Visual SCL Beta 0.12).
Page 474
Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 F60 Feeder Protection System GE Multilin...
Page 475
IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin F60 Feeder Protection System...
The following procedure describes how to update the F60 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item. Select the saved SCD file and click Open. C-20 F60 Feeder Protection System GE Multilin...
Page 477
The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
Page 481
(QueryLogByTime or QueryLogAfter) c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin F60 Feeder Protection System C-25...
RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing C-26 F60 Feeder Protection System GE Multilin...
Page 483
T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer GE Multilin F60 Feeder Protection System C-27...
Page 484
ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-28 F60 Feeder Protection System GE Multilin...
Address Field of the Link: Balanced Transmision Not Present (Balanced Transmission Only) Unbalanced Transmission One Octet Two Octets Structured Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin F60 Feeder Protection System...
Page 486
<18> := Packed start events of protection equipment with time tag M_EP_TB_1 <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1 <20> := Packed single-point information with status change detection M_SP_NA_1 F60 Feeder Protection System GE Multilin...
Page 487
<103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1 <104> := Test command C_TS_NA_1 <105> := Reset process command C_RP_NA_1 <106> := Delay acquisition command C_CD_NA_1 <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin F60 Feeder Protection System...
Page 488
•Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 F60 Feeder Protection System GE Multilin...
Page 490
P_ME_NC_1 <113> P_AC_NA_1 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization: Remote initialization Cyclic Data Transmission: Cyclic data transmission Read Procedure: Read procedure F60 Feeder Protection System GE Multilin...
Page 491
Mode A: Local freeze with spontaneous transmission Mode B: Local freeze with counter interrogation Mode C: Freeze and transmit by counter-interrogation commands Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously Counter read Counter freeze without reset GE Multilin F60 Feeder Protection System...
Page 492
Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs F60 Feeder Protection System GE Multilin...
D.1.2 IEC 60870-5-104 POINT LIST The IEC 60870-5-104 data points are configured through the SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin F60 Feeder Protection System...
Page 494
D.1 IEC 60870-5-104 APPENDIX D D-10 F60 Feeder Protection System GE Multilin...
Transmitted: 292 Transmitted: configurable up to 2048 Received: Received: 2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries: None None Fixed at 3 Configurable Configurable Requires Data Link Layer Confirmation: Never Always Sometimes Configurable GE Multilin F60 Feeder Protection System...
Page 496
FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. F60 Feeder Protection System GE Multilin...
Page 497
Configurable (attach explanation) Configurable (attach explanation) Default Object: 16 Bits (Counter 8) Default Variation: 1 32 Bits (Counters 0 to 7, 9) Point-by-point list attached Other Value: _____ Point-by-point list attached Sends Multi-Fragment Responses: GE Multilin F60 Feeder Protection System...
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. F60 Feeder Protection System GE Multilin...
Page 499
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. GE Multilin F60 Feeder Protection System...
Page 500
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. F60 Feeder Protection System GE Multilin...
Page 501
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. GE Multilin F60 Feeder Protection System...
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 F60 Feeder Protection System GE Multilin...
A counter freeze command has no meaning for counters 8 and 9. F60 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values. E-10 F60 Feeder Protection System GE Multilin...
Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin F60 Feeder Protection System E-11...
Page 506
E.2 DNP POINT LISTS APPENDIX E E-12 F60 Feeder Protection System GE Multilin...
AE ....Accidental Energization, Application Entity FWD....Forward AMP ....Ampere ANG ....Angle G ....Generator ANSI....American National Standards Institute GE....General Electric AR ....Automatic Reclosure GND....Ground ASDU ..... Application-layer Service Data Unit GNTR..... Generator ASYM ..... Asymmetry GOOSE..
Page 511
....With Option RST ....Reset WRT....With Respect To RSTR ..... Restrained RTD....Resistance Temperature Detector X .....Reactance RTU....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR....Transformer s ..... second Z......Impedance, Zone S..... Sensitive GE Multilin F60 Feeder Protection System...
24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory.