Ds7432 Eight Input Remote Module; Ds7465(I) Input/Output Module; Dip Switch Settings; Ds7432 Point Type Configuration - Bosch D8125MUX Operation And Installation Manual

Multiplex bus interface
Hide thumbs Also See for D8125MUX:
Table of Contents

Advertisement

D8125MUX | Operation and Installation Guide | 3.0

3.12 DS7432 Eight Input Remote Module

This device type reserves eight points on the
multiplex bus. Each D8125MUX supports fifteen
DS7432s on the D9412GV2, D9412G, D9412, and
D9112 Control Panels, up to eight on the D7412GV2,
D7412G, D7412, and D7212 Control Panels, and up
to four on the D7212GV2 and D7212G Control
Panels. The DS7432s occupy groups of eight points;
however, when programming the DS7432 with the
multiplex point programmer, program them as four
sets of dual points. For example, if using a DS7432
on the system for Points 9 through 16, program
Points 9, 11, 13, and 15 as dual points with the even
points being added automatically. Program starting
point locations for the DS7432 on the D9412GV2,
D9412G, D9412, and D9112 Control Panels as
follows: 9, 17, 25, 33, 41, 49, 57, 65, 73, 81, 89, 97,
105, 113, 121. Refer to Table 14.
Table 14: DIP Switch Settings
Zonex 1/
1
2
Zonex 2
9/129
Open
Open
17/137
Open
Open
25/145
Open
Open
33/153
Open
Open
41/161
Open
Open
49/169
Open
Open
57/177
Open
Open
65/185
Open
Closed
73/193
Open
Closed
81/201
Open
Closed
89/209
Open
Closed
97/217
Open
Closed
105/225
Open
Closed
113/233
Open
Closed
121/241
Open
Closed
Points 127/128 and 247/248 cannot be
programmed when using DS7432s
(D9412GV2, D9412G, D9412, or D9112).
Program starting point locations for the DS7432 on
the D7412GV2, D7412G, D7412, D7212 as follows:
9, 17, 25, 33, 41, 49, 57, and 65. Program starting
point locations for the DS7432 on the D7212GV2 and
D7212G as follows: 9, 17, 25, and 33. Failure to
observe this programming requirement will result in
intermittent missing conditions. All eight points on the
DS7432 must also have a Point Index assigned to
them. If any of the eight point inputs are not required
20
DIP Switch
3
4
5
Open
Open
Closed
Open
Closed
Open
Open
Closed
Closed
Closed
Open
Open
Closed
Open
Closed
Closed
Closed
Open
Closed
Closed
Closed
Open
Open
Open
Open
Open
Closed
Open
Closed
Open
Open
Closed
Closed
Closed
Open
Open
Closed
Open
Closed
Closed
Closed
Open
Closed
Closed
Closed
Installation
on the device, place the 47 kΩ EOL resistor on the
point input terminals. Refer to Table 15 for
information on configuring the point type. Tamper
conditions on multiplex points are treated as Missing
conditions by the control panel. Removing the cover
and activating the tamper results in a missing
condition for all eight points.
Table 15: DS7432 Point Type Configuration
Device Type
DS7432 Eight Input
Remote Module
3.13

DS7465(i) Input/Output Module

This device type reserves a single point on the MUX
bus and provides a Form C (NO, C, NC) relay output.
The relay output number assigned to this module is
the same as the point number assigned to it. For
example, if this device was programmed as Point 27,
the relay number is also 27.
The relay output on this module is a fully
programmable relay and follows the relay
programming of the control panel.
The maximum number of DS7465i Modules that can
be placed on the control panels is 56 as points 9
through 64 for the D9412GV2, D7412GV2, D9412G,
D7412G, D9412, D7412, D7212, and D9112; and 16
as points 9 through 24 for the D7212GV2 and
D7212G. Place the DS7465(i) on the D8125MUX
connected to Zonex 1.
If only the relay is required for the installation, assign
a Point Index for the programmed point location, and
place a 47 kΩ EOL resistor on the point input
terminals. Refer to Table 16 for point type
configuration.
Table 16: DS7465(i) Point Type Configuration
Device Type
DS7465(i) Input/Output
Module
Tamper conditions on multiplex points are treated as
Missing conditions by the control panel. Using
DS7465i Input and Output Modules on the system
does not interfere with the use of D8129 OctoRelay
Modules.
Bosch Security Systems, Inc. | 10/09 | F01U034973-02
Point Type
Point Response
6
Configurable
(NO or NC)
Point Type
Point Response
3
Configurable
(NO or NC)