5.5 CONTROL ELEMENTS
The signals related to the locked rotor pickups and operations for the three locked rotor elements can be viewed at Actual
> Status > Control Elements > Locked Rotor and they are as follows:
Table 5–88: LOCKED ROTOR STATUS
The block signals for the locked rotor element can be configured at: Setpoint > Relay Configuration > Protection
Elements
Table 5–89: LOCKED ROTOR BLOCKS
Note:
The element works with primary values.
5
The element will pickup if at least one of the three phase currents is above the adjusted level. The operation value will be
the higher of the three.
The reset level is 97% to 98% of the pickup level.
The F650 includes eight pulse counters, each pulse counter stores the activation number of the input set to that pulse
counter. This value can be multiplied for a factor selectable by setting.
The inputs used in this pulse counter function can be selected from all the available in the F650 device. Take into account
that the input/output settings are both set for the generic input as well as for the pulse counter input, e.g. Debounce time.
The settings for this function can be found at Setpoint > Control Elements > Pulse Counters
Table 5–90: PULSE COUNTERS SETTINGS
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
Pulse counter enabling setting
Name of the pulse counter
Multiplier factor for the pulse counter
Overflow value for the pulse counter
Board selection for the pulse counter
Input index inside the selected board
Note: X is the pulse counter index, up to 8.
Pulse Counters settings are:
CntPulses Enabled:
CntPulses Name:
5-110
LOCKED ROTOR STATUS
LOCKED ROTOR1 PKP
LOCKED ROTOR1 OP
LOCKED ROTOR2 PKP
LOCKED ROTOR2 OP
LOCKED ROTOR3 PKP
LOCKED ROTOR3 OP
LOCKED ROTOR BLOCKS
LOCKED ROTOR1 BLK
LOCKED ROTOR2 BLK
LOCKED ROTOR3 BLK
NAME
DEFAULT VALUE
CntPulses Enabled X
DISABLED
CntPulses Name X
Pulse Counter X
CntPulses Factor X
1.000
CntPulses Overflow X
65535
CntPulses Board Origin X
F
CntPulses Input Origin X
1
Enable/disable each pulse counter.
Each pulse counter can have a configurable user name.
F650 Digital Bay Controller
5 SETTINGS

5.5.10 PULSE COUNTERS

STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
N/A
0.001 [0.000 : 65000.000]
1
[0 : 1000000]
N/A
[F,G,H,I]
1
[1 : 32]
GEK-106310AB