Troubleshooting; False Alarms; Quick Solution To Solve False Alarms; False Alarms Under 4 Seconds Concerning The Whole Detection Area - Bosch AVIOTEC IPSTARLIGHT 8000 Operation Manual

Hide thumbs Also See for AVIOTEC IPSTARLIGHT 8000:
Table of Contents

Advertisement

AVIOTEC IP starlight 8000
9

Troubleshooting

The following issues can be solved in the detection settings (Configuration > Alarm > Fire
detection).
9.1

False Alarms

9.1.1

Quick solution to solve false alarms

A fast way to identify and solve region-stable false alarms in the camera image is automasking.
The system automatically generates predefined masks from the alarm memory.
Navigate to Configuration > Alarm > Fire detection.
2. Select Automask.
3. Select Set to confirm the changes.
See also
9.1.2

False alarms under 4 seconds concerning the whole detection area

In this case the general settings of the fire detection have to be adjusted.
Problem
Small bounding boxes of flame detection
cause false alarms.
Short false alarms for smoke detection.
Short false alarms for flame detection.
9.1.3

False alarms at small constant areas

Individual image areas are affected and have to be adjusted.
Problem
Objects cause flickering motion, e.g. shadow
of a flag in the wind.
Bosch Sicherheitssysteme GmbH
Adjustments of image regions, page 41
Solution
Increase the minimum flame size.
(Flames > Min. size)
Increase the duration of smoke detection.
(Smoke> Verification time [s])
Increase the duration of flame detection.
(Flames > Verification time [s])
Solution
Mask out the disturbing image area (for
flame).
Flame detection will be deactivated in this
mask.