hit counter script
Bosch AVIOTEC IPSTARLIGHT 8000 Operation Manual

Bosch AVIOTEC IPSTARLIGHT 8000 Operation Manual

Hide thumbs Also See for AVIOTEC IPSTARLIGHT 8000:

Advertisement

Quick Links

AVIOTEC IP starlight 8000
FCS-8000-VFD-B
en
Operation manual

Advertisement

Table of Contents
loading

Summary of Contents for Bosch AVIOTEC IPSTARLIGHT 8000

  • Page 1 AVIOTEC IP starlight 8000 FCS-8000-VFD-B Operation manual...
  • Page 3: Table Of Contents

    Adjustment of detection settings General settings Adjustments of image regions Relay settings Troubleshooting False Alarms 9.1.1 Quick solution to solve false alarms 9.1.2 False alarms under 4 seconds concerning the whole detection area Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 4: En | Table Of Contents

    Image quality Camera Maintenance 10.1 Cleaning 10.2 Repair 10.3 Reset Technical data Appendices 12.1 Maximum detection distances for margin areas 12.1.1 Flame detection 12.1.2 Smoke detection 12.2 Commissioning report Index 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 5: Safety Instructions

    In case of unusual behavior, smoke, noise or smell coming out of the lens, shut off the power immediately and pull out the lens cable. Notify the installer or sales agent from which you purchased the product. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 6 Notice! Respect data protection. The relevant data protection and privacy rules are to be complied with. Notice! Avoid backlight. Backlight can disturb the video-based fire detection algorithm. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 7 Ensure that you are always using the latest version of the operation manual and the current camera firmware. The manufacturer will not be held liable for any damages resulting from the use of older versions. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 8: Introduction

    For more information please contact the nearest Bosch Security Systems location or visit www.boschsecurity.com . All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
  • Page 9: Focal Length

    (red). The maximum distance to a detectable fire may be reached by adjusting the largest focal length which decreases the width of the field of view to the minimum (green). Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 10: Monitoring Area

    The angle between a fire on the ground and the line of sight to the camera is important for the flame and smoke detection. This angle needs to be 37.5% or less, otherwise flame or smoke will not be detected. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 11 Angle for vertical alignment of the camera The vertical alignment of the camera is also important for the video-based fire detection. A flat angle is recommended. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 12 | Introduction AVIOTEC IP starlight 8000 Angle for horizontal alignment of the camera Align the camera according to your application by adjusting the angle of the horizontal alignment of the camera. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 13: System Overview

    The camera offers a number of flexible power and mounting options to meet your site-specific installation requirements. 3.1.1 Power supply Power over Ethernet (PoE) Notice! Use only PoE approved devices. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 14: Uninterruptible Power Supply

    Sometimes obstructions cannot be prevented, e.g. building construction factors or huge machine parts. In this case it is necessary to analyze whether there is any need for further video-based fire detection cameras. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 15: Flame Detection Characteristics

    The minimum motion speed of smoke is 0.7% of the picture height per second and the minimum width of a smoke plume is 2.3% of Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 16 Objects with a similar movement pattern of smoke might cause false alarms, e.g. escalators or conveyor belts. Smoke density A minimum smoke density is required to identify the smoke plume. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 17 σ and the contrast for the background σ Exemplary images for smoke densities are shown in the following table: Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 18: Intelligent Video Analytics

    The software also supports geolocation, that is it outputs tracked objects in relation to camera position for subsequent visualization on maps. It allows you to record all of the object information and change the rules even after the fact for fully configurable forensic search. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 19: Video Management System

    A Video Management System is a unique enterprise IP video security solution that provides seamless management of digital video, audio, and data across any IP network. It nevertheless offers interfaces and standards to integrate AVIOTEC IP starlight 8000. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 20: Planning

    Minimum distance to fire Installation height The table below demonstrate exemplarily the minimum distances to fire or smoke depending on the installation height: Installation height [m] Minimum distance to fire [m] 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 21: Maximum Distances

    The tables below demonstrate exemplarily the maximum distances to a fire depending on fire size and opening angle of the camera lens: Maximum distance to fire in m (Flame detection) Opening angle [°] Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 22: Image Margin Area

    28.1 42.8 55.7 56.2 85.6 111.4 Image margin area Due to the optical distorsion of the lens, there are deviating maximum detection distances at the margin area of the picture. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 23 The following table shows exemplarily the deviation in percent from the maximum detection distances at the middle of the picture: Margin area Opening angle of the lens 100° 90° 60° 45° Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 24: Immediate Environment Of The Camera

    To protect privacy, individual masks on the video screen can be defined to cover up areas in which privacy has to be guaranteed. Privacy defined masks remain stored after a reset of the camera, even after upgrading to a new firmware. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 25: Installation

    Camera shake might lead to false alarms. Avoid vibrations of the camera and the camera environment. Lens mounting Notice! Only use the supplied lens. Do not use other lenses. A reliable functioning of the product cannot be guaranteed with other lenses. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 26 Screw the lens onto the camera. Plug the lens connector into the camera (it automatically detects the type of lens). DC iris lens Damp - Damp + Drive + Drive - 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 27: Camera Mounting

    Tighten the mounting bracket lock ring to fix the camera in the desired position. Setting the field of view After the camera is mounted to the surface, the field of view can be set. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 28 Manually adjust the focus on the lens to obtain the sharpest image possible. The camera lens has a motorized automatic back focus to adjust the focus at a later time via the camera menu. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 29: Wiring Of The Camera

    Use STP Category 5e cable with RJ45 connectors (the camera network socket is Auto MDIX compliant). The LEDs beside the Ethernet connection indicate network connection (green lit) and IP traffic (orange flashing). Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 30 UL 14-30 AWG). Loosen the screws of the supplied 2-pole connector and insert the stripped wires, then tighten the screws again. Insert the 2-pole connector into the camera power socket. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 31: Camera Integration

    There are several possibilities to connect the camera. Various combinations are possible. The individual customer network properties determine the performance and scalability of the system. Camera Network switch, PoE-ready Client PC Video Recording Manager (VRM) Router Internet Monitoring Center Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 32: Local Area Network

    Recording and archiving functionality in the network can be realized by a video recording manager (VRM). Fire cause analysis and traceability due to legal matters are only two examples of a recording solution. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 33: Monitoring Center

    Notice! No direct connection to fire services in EN54 compliant installations. Authorities can allow a connection to fire services after verifying alarms in a monitoring center. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 34 There are no existing EN standards concerning the video-based fire detection. The alarm contact assignment is shown in the figure below: 7 mm (0.28 in) MENU CVBS Alarm 4 5 6 ≤2 mm 1 2 3 (0.08 in) 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 35 The alarm output of the camera can be connected to a fire alarm control panel. The camera alarm output is triggered by a relay that is normally open. In case of alarm the relay is closed. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 36: Mobile Devices

    Mobile Devices Another advantage of the network integration of the video-based fire detection is the expandability to mobile devices, such as tablets or smartphones. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 37 AVIOTEC IP starlight 8000 Camera integration | en Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 38: Access Via Web Interface

    For certain applications, the DHCP server must support the fixed assignment between IP address and MAC address, and must be appropriately set up so that, once an IP address is assigned, it is retained each time the system is rebooted. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 39: Adjustment Of Detection Settings

    15 seconds. Small values cause faster detection (higher risk of false alarms), larger values decrease false alarms. Adjustments of image regions Notice! There is no fire detection in privacy defined masks created in the Intelligent Video Analytics. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 40 The value must be set from 5 to 120 seconds. Default value is 30 seconds. Move the mask to the desired area in the picture. Change shape and size to your specific needs. Select Set to confirm the changes. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 41 Select On and press Set. Automasks for Flame were deleted. To delete the automasks for Smoke detection from the alarm memory: Navigate to Fire detection > Smoke > Detection. Select Off and press Set. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 42: Relay Settings

    You can click the button to switch the alarm output manually (for example, for testing purposes). A green check mark appears to indicate that the relay switches. Notice! Check carefully the toggle settings before you continue. Press Set to apply the settings. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 43: Troubleshooting

    Problem Solution Objects cause flickering motion, e.g. shadow Mask out the disturbing image area (for of a flag in the wind. flame). Flame detection will be deactivated in this mask. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 44: Vibrations At The Camera Site

    – Check the detection area – Check minimum/maximum distance to fire Image quality Interference of the camera image Small image areas or the whole image area are affected by interferences. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 45: Camera

    The device is not properly connected to the network. Check the cable connections in this case. – The device is not correctly integrated into the network. Check the IP address, subnet mask, and gateway address. Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 46: Maintenance

    Use the factory reset button to restore the unit to its original settings. Any changes to the settings are overwritten by the factory defaults. A reset may be necessary, for example, if the unit has invalid settings that prevent it from functioning as desired. 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 47: Technical Data

    78 x 66 x140 mm (3.07 x 2.6 x 5.52 inch) without lens Weight 855 g (1.88 lb) without lens Color RAL 9006 Metallic Titanium Tripod Mount Bottom and top 1/4-inch 20 UNC Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 48 SMTP, iSCSI, UPnP (SSDP), DiffServ (QoS), LLDP, SOAP, Dropbox, CHAP, digest authentication Encryption TLS 1.0, SSL, DES, 3DES Ethernet 10/100 Base-T, auto-sensing, half/full duplex Connectivity ONVIF Profile S , Auto-MDIX 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 49: Appendices

    Due to the optical distorsion of the lens, there are deviating maximum detection distances at the margin area of the picture. Figure 12.1: Definition of margin areas of the picture Horizontal margin area Vertical margin area Corner area Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 50: Flame Detection

    38.56 m 32.97 m 61.46 m 46.27 m 39.57 m 1.75 71.71 m 53.98 m 46.16 m 81.95 m 61.69 m 52.75 m 2.25 92.20 m 69.41 m 59.35 m 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 51 68.74 m 66.47 m 81.41 m 76.38 m 73.86 m 1.25 101.77 m 95.47 m 92.33 m 122.12 m 114.57 m 110.79 m 1.75 142.47 m 133.66 m 129.26 m Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 52: Smoke Detection

    16.39 m 12.34 m 10.55 m 19.12 m 14.40 m 12.31 m 21.85 m 16.45 m 14.07 m 24.59 m 18.51 m 15.83 m 27.32 m 20.56 m 17.58 m 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 53 21.61 m 20.28 m 19.61 m 27.02 m 25.35 m 24.51 m 32.42 m 30.42 m 29.41 m 37.83 m 35.49 m 34.32 m 43.23 m 40.55 m 39.22 m Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 54: Commissioning Report

    Camera installation and configuration protocol General Camera name (Configuration -> General - > Identification) Firmware version (Configuration -> Service -> System Overview) Date/Time setting o Synchronized (Configuration -> General -> Date/Time) Mounting height 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 55 AVIOTEC IP starlight 8000 Appendices | en Field of view (Please add a screenshot) Screenshot location (e.g. network folder) Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 56 Off (Configuration -> Alarm -> Fire detection) Min size Verification time [s] Smoke detection o On o Off (Configuration -> Alarm -> Fire detection) Min size Verification time [s] 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 57 AVIOTEC IP starlight 8000 Appendices | en Masks (smoke, flame, smoke time o Yes o No region) (Please add a screenshot) Privacy Masks o Yes o No (Please add a screenshot) Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 58 No with the customer Minimum and maximum distances o Yes o No calculated and documented for the customer Obstructions in the picture taken into o Yes o No account 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 59 No Field of view (Please add a screenshot) Smoke test results (test video) Distance to monitor Illumination Smoke detected o Yes o No Field of view (Please add a screenshot) Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 60 (Please add a screenshot) Smoke/flame test results (test video) Distance to monitor Illumination Smoke detected o Yes o No Flame detected o Yes o No Field of view (Please add a screenshot) 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 61 AVIOTEC IP starlight 8000 Appendices | en Place: Issuer: Date: Signature: Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200...
  • Page 62: Index

    Video Management System, 19 Verification time [s], 39 flickering, 45 focal length, 9 Illumination, 8, 24 masking add mask, 40 add smoke time region, 40 introduction, 40 monitoring area, 9, 10 2017.06 | 6.0 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH...
  • Page 64 Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany www.boschsecurity.com © Bosch Sicherheitssysteme GmbH, 2017...

This manual is also suitable for:

Aviotec ip starlight 8000Fcs-8000-vfd-b

Table of Contents