hit counter script
Mitsubishi Electric MXZ-2B52VA Installation Manual
Mitsubishi Electric MXZ-2B52VA Installation Manual

Mitsubishi Electric MXZ-2B52VA Installation Manual

Split-type air-conditioner
Hide thumbs Also See for MXZ-2B52VA:

Advertisement

Quick Links

Split-type Air-Conditioner
MXZ-2B52VA
INSTALLATION MANUAL
• Refer to the installation manual of each indoor unit for indoor
unit installation.
IMPORTANT NOTES
TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD
AS/NZS 3000 ELECTRICAL INSTALLATIONS (Wiring Rules),
THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND
OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL
CONTRACTOR.
CONTENTS
1. BEFORE INSTALLATION ..............................................................................2
2. OUTDOOR UNIT INSTALLATION .................................................................4
3. FLARING WORK AND PIPE CONNECTION . ................................................5
5. RELOCATION AND MAINTENANCE ............................................................7
FOR INSTALLER
English

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric MXZ-2B52VA

  • Page 1: Table Of Contents

    Split-type Air-Conditioner MXZ-2B52VA INSTALLATION MANUAL English • Refer to the installation manual of each indoor unit for indoor unit installation. IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS/NZS 3000 ELECTRICAL INSTALLATIONS (Wiring Rules), THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR. CONTENTS 1. BEFORE INSTALLATION ................2 2. OUTDOOR UNIT INSTALLATION ..............4 3. FLARING WORK AND PIPE CONNECTION ..........5 4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN ......5 5. RELOCATION AND MAINTENANCE ............7 FOR INSTALLER...
  • Page 2: Before Installation

    Max. pipe length Model Rated Fre- Breaker Indoor/outdoor Max. Refrigerant adjust- Power supply per indoor unit / per indoor unit / Voltage quency capacity connecting wire height difference ment A *7 for multi-system for multi system 4-core MXZ-2B52VA 230 V 50 Hz 15 A 3-core 2.0 mm 20 m / 30 m 15 m 20 / 30 20 g/m 1.0/1.5 mm *1 Connect to the power switch which has a gap of 3 mm or more when open *6 Refrigerant pipe bending radius must be 100 mm or more. to interrupt the source power phase. (When the power switch is shut off, it *7 If pipe length exceeds 20 m, additional refrigerant (R410A) charge is re- must interrupt all phases.) quired. (No additional charge is required for pipe length less than 20 m.) *2 Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoor Additional refrigerant = A × (pipe length (m) - 20) connecting wire in conformity with the wire specifications specified in the *8 Insulation material : Heat resisting foam plastic 0.045 specific gravity installation manual of the indoor unit.
  • Page 3: Selecting The Installation Location

    1-4. SELECTING PIPE SIZE AND OPTIONAL DIFFERENT-DIAMETER JOINTS The diameter of connection pipes differs according to the type and capacity of indoor units. Match the diameters of connection pipes for indoor and outdoor units according to the following table. • If the diameter of connection pipes does not match the diameter of pipe end connections, use optional different-diameter joints. (Unit: mm) Indoor unit Outdoor unit Capacity Connection pipe size (Wall thickness) : Liquid / Gas 22/25/35 Union size 6.35(0.8) / 9.52(0.8) Room (Liquid / Gas) Optional different-diameter joint : Liquid / Gas A, B 6.35 / 9.52 - / - 1-5. SELECTING THE INSTALLATION LOCATION • Where it is not exposed to strong wind. Note: • Where airflow is good and dustless. When operating the air conditioner in low outside temperature, be sure • Where rain or direct sunshine can be avoided as much as possible. to follow the instructions described below. • Where neighbours are not annoyed by operation sound or hot air. • Never install the outdoor unit in a place where its air inlet/outlet side • Where rigid wall or support is available to prevent the increase of op- may be exposed directly to wind. eration sound or vibration.
  • Page 4: Drain Piping For Outdoor Unit

    1-7. DRAIN PIPING FOR OUTDOOR UNIT Please perform the drain piping work only when draining from one place. 1) Provide drain piping before indoor and outdoor piping connection. 2) Connect drain hose I.D.15 mm as shown in the illustration. 3) Make sure to provide drain piping with a downhill grade for easy drain flow. Note: Install the unit horizontally. Do not use the drain socket in the cold regions. Drain may freeze and it makes the fan stop. The outdoor unit produces condensate during the heating operation. Select the installation place to ensure to prevent the outdoor unit and/or the grounds from being wet by drain water Drain hose or damaged by frozen drain water. Drain socket 2. OUTDOOR UNIT INSTALLATION Terminal block 2-1. CONNECTING WIRES FOR OUTDOOR UNIT for power supply 1) Remove the service panel.
  • Page 5: Flaring Work And Pipe Connection

    3. FLARING WORK AND PIPE CONNECTION 3-1. FLARING WORK 1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2) 2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3) No good Good • Put the end of the copper pipe to downward direction as you Copper remove burrs in order to avoid to let burrs drop in the piping. pipe 3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (Not possible to put them on after flaring work.) Tilted Uneven Burred 4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension Fig. 1 Fig. 2 shown in the table. Select A mm from the table according to the tool you use. Flaring tool 5) Check Copper pipe • Compare the flared work with Fig. 6.
  • Page 6 4-2. GAS CHARGE Perform gas charge to unit. 1) Connect gas cylinder to the service port of stop valve. 2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder. Union 3) Replenish specified amount of the refrigerant, while operating the air Stop valve Indoor conditioner for cooling. Liquid pipe unit Gas pipe Note: Union In case of adding refrigerant, comply with the quantity specified for the Outdoor Indoor refrigerating cycle. unit Liquid pipe unit Gas pipe...
  • Page 7: Relocation And Maintenance

    4-5. TEST RUN • Be sure to perform the test run for each unit. Make sure each indoor unit operates properly following the installation manual attached to the unit. • If you perform the test run for all indoor units at once, you cannot detect any erroneous connection, if any, of the refrigerant pipes and the indoor/outdoor unit connecting wires. Make sure that the following is done. • Power is supplied to the unit. • Stop valves are open. About the restart protective mechanism Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 4-6. EXPLANATION TO THE USER • Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner. (how to use the remote controller, how to remove the air fil- ters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.). • Recommend the user to read the OPERATING INSTRUCTIONS carefully. 5. RELOCATION AND MAINTENANCE 5-1. PUMPING DOWN When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmos- phere. 1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit. 2) Fully close the stop valve on the liquid pipe side of the outdoor unit. 3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/cm 4) Start the emergency COOL operation on all the indoor units. To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.) 5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm 6) Stop the emergency COOL operation.
  • Page 8 HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN JG79A299H01...

Table of Contents