GE Industrial Systems INSTALLATION / USER MANUAL Digital Energy™ LP 11U GE Digital Energy General Electric Company CH - 6595 Riazzino (Locarno) Switzerland LP 11U UPS Technology for the Digital World. Uninterruptible Power Supply 5-6-8-10 kVA Telephone +41 (0)91 / 850 51 51...
Page 3
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail. The content of this publication may be subject to modification without prior notice, no liability can be accepted for any error or omission. LX: OPM_LPU_11U_5K0_10K_1US_V030 GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
5.5.2 Utility start 5.5.3 Sleep and wake-up 5.5.4 Overload protection in bypass mode 5.5.5 ECO-Mode 5 5.6 Auto restart 5.5.7 Superior battery management LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy CONTENTS GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
Page 5
8.4 Safety 8.5 Storage 8.6 Recycling the UPS at the end of service life TROUBLESHOOTING ... 39 SPECIFICATIONS ... 40 APPENDIX: INSTALLATION DRAWINGS LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
By opening or removing covers you run the risk of exposure to dangerous voltages! While every care has been taken to ensure the completeness and accuracy of this manual, GE accepts no responsibility or liability for any loss or damage resulting from the use of the information contained in this document.
Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal requirements. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy Kobe HV7-12 or Panasonic LC-R127R2P Kobe HV12-12 or Panasonic LC-RA1212P GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
More than ever before, today's advanced electronic equipment, with complex integrated circuits and other sensitive electronics, needs a stable and continuous AC power supply to operate correctly. While the power coming from the wall outlet is often unreliable, a GE Digital Energy™ LP-U UPS provides the security of completely uninterrupted power.
P.F. = 1 CONVERTER/ OUTPUT RECTIFIER/ CONVERTER BATTERY CHARGER SYSTEM BATTERY ON/OFF MICROPROCESSOR CONTROL GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series SWITCH TO LOAD FILTER OPTION SLOTS FOR: RPA CARD OUTPUT...
OUTPUT RECTIFIER/ CONVERTER BATTERY CHARGER SYSTEM ON/OFF MICROPROCESSOR CONTROL Figure 5 . Bypass operation: Manual bypass GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series MANUAL BYPASS SWITCH TO LOAD FILTER OPTION SLOTS FOR:...
I/O voltages are different from the default (208Vac), performed as well. Proceed with 4.5.4. 12. For a quick start proceed with section 5.2 ‘Start-up’. GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
Page 14
(208Vac), software modifications should be performed as well. Proceed with 4.5.4. 12. For a quick start proceed with section 5.2 ‘Start-up’. GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series possibilities,...
Figure 9. LP 5/6/8/10-11U: Output (grey) / input terminals For the output voltage proceed with 4.5.3. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy Figure 8a. LP 5/6/8/10-11U: Rear view GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
Connect the ground wire to terminal 5. Ground connection is essential! See figure 11. Figure 11. LP 5/6/8/10-11U: 208 Vac output connection Return to either 4.5.1.1 step 5 or 4.5.1.2 step 5 LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy Output tap changed to 240 Volt (park) (park) (connect) Figure 12. LP 5/6/8/10-11U: Figure 12a. LP 5/6/8/10-11U: Rear view GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series Output tap change...
To return to the default screen scroll to the set-up screens first and press 'Enter/Reset'. You can also wait 20 seconds: the time-out period of no key activity. You can now proceed with 5.1 or 5.2. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
Page 20
Re-install the interface card. If the contact is opened, the UPS will generate an ‘EXTERNAL BATTERY FUSE FAILURE’. See 5.3.2 for more information. Proceed with 4.5.1 or 5.2. GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
1-PHASE 3-WIRE INPUT INPUT JUNCTION LP-UPS LP-UPS RPA CARD RPA CARD OUTPUT JUNCTION TO LOAD GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series TERMINATOR LP-UPS RPA CARD YELLOW NETWORK CABLES AS DELIVERED...
Digital Energy Figure 18. Appointing a unique number to each UPS in the system AUTORESTART OFF PRESS ENTER LP 5-11U LOAD 40% AUTORESTART OFF SETTING MISMATCH GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
4. Reinstall the installation input fuse, 5. Connect the output of the UPS to the output junction, 6. Switch on the UPS. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
Option slot for RPA (Redundant Parallel Architecture) Card. Not available yet. DC socket / connector. Battery fuse holder Conduit box Cable inlet GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series 1 = Load on UPS 2 = Load on utility...
Page 25
DC socket (14Ah only) DC connector Battery fuse holder(s) 7Ah: 2 fuses 14Ah: 4 fuses Gland to fasten cable in conduit box of UPS GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
If not yet switched on, the equipment connected to the UPS can be switched on now; operate as usual. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
The remaining battery runtime (or autonomy) during a utility failure. AUTONOMY TIME LEFT 5:27:00 The total operating time of the UPS. OPERATING TIME 0YEAR 29DAYS LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
The battery temperature is too high due to a battery failure or a too high BATTERY CHARGER ambient temperature TEMP TOO HIGH LX: OPM_LPU_11U_5K0_10K_1US_V030 extreme environmental temperature lack of proper ventilation an overload situation fan failure GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
Page 29
60.0Hz operation is inhibited: if for whatever reason the output converter is unable to deliver the required output, output power is lost. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
First line: service information on charger. ‘1’ = batteries have reached float FLOAT CHARGE: voltage. OUTPUT FAST : Second line: service information on output converter. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
Page 31
Service set-up information about the autorestart function. This function can AUTO RESTART be switched on or off by pressing ‘Enter/Reset’, depending on the actual ENTER/RESET CHNG status. See also 4.5.6. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
If you proceed, the information about the actual battery condition (as a result of a deep battery test) is lost. For more info see section 5.4.3 'Deep Battery Test'. GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
The test could not be executed properly: not all test conditions were fulfilled. TEST FAILED TEST FAILED TEST FAILED TEST FAILED The UPS system was not informed about the actual battery condition! LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
'BATTERY DEPLETED' will be shown. The run time is zero. 5.5.3 Sleep and wake-up GE Digital Energy™ UPS monitoring software allows you to program a 'sleep period' of the UPS by sending two commands to the UPS: - shut down after # minutes, and subsequently: - shut down during # hours.
(-18mV/ C or -32.4mV/ F per 12V battery). As a result poor charging of the batteries under low temperature conditions and overcharging of the batteries under high temperature conditions are prevented. LX: OPM_LPU_11U_5K0_10K_1US_V030 Digital Energy GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series...
When the utility power returns, the systems will automatically start up and will be up and running as soon as possible. For specific information on GE Digital Energy™ connectivity products please contact your dealer or internet: www.gedigitalenergy.com.
The RPA-facility allows to connect 2, 3 or 4 units in parallel. Connecting GE Digital Energy™ LP-U units in parallel is attractive for several reasons. Redundancy: To achieve the highest possible level of power protection in a fault-tolerant network.
Seismic anchors can be ordered separately; contact your local dealer. LX: OPM_LPU_11U_5K0_10K_1US_V030 Connector Nema L14-30R (1) TCBs (8) Connector Nema L6-30R (2) Connector Nema L5-20R (4) GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
It does not contain CFCs (Carbon Fluorine Chloride) of HCFCs (Halogen Carbon Fluorine Chloride). GE Digital Energy, in compliance with environment protection recommends that the UPS equipment, at the end of its service life, must be recycled conforming to the local applicable regulations.
Wait for a few hours, leave the UPS switched on.* Hardware output voltage detection 'Q4' is active. Please contact your dealer. GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
Automatic shut down (or transfer to bypass, if bypass is available) in case of - low/high DC voltage - overtemperature - overload / short circuit GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
Page 43
21/50 22/50 240/14 240/14 240/14 45/90 35/75 33/70 VSDT2 + VSD2 995x313x730 39.2x12.3x28.7 175 Kg 386 Lbs GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series 10-11U 12/12 12Ah 240/7 16/39 240/14 25/57...
Page 44
FCC part 15, class A; EN 50091-2 -10 to +40°C (14 to 104°F) 40 - 50dB(A), the audible noise is load and temperature dependent GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ Digital Energy LP Series...
Page 45
UPS cabinet, dimensions hxwxd: 680 x 310 x 710 mm 26.8 x 12.3 x 28.7 inch Center of gravity, position: GE DE LP 11U UPS: Installation / User Manual 3.0 (US) ™ LP Series 275 mm / 10.8 inch 155 mm / 6.1 inch...
Page 46
Model Heat dissipation Dimensions Linear load 240 Volt 100% load 50% load LP-U Btu/hr Btu/hr Inch 5-11 1950 1329 26.8 6-11 2254 1300 26.8 8-11 3234 1882 26.8 10-11 1090 3719 1896 26.8 5-11/120 V 2187 1451 39.2 6-11/120 V 2539 2051 39.2...
Page 47
LEVELLER POSITION A: FIX UPS TO THE FLOOR POSITION B: LIFT UPS CASTORS FROM THE FLOOR LP 5/6/8/10-11U 208-240V input MANUAL BYPASS SWITCH NORMAL: POSITION 1 (LOAD ON UPS) SERVICE: POSITION 2 (LOAD ON BYPASS) INPUT/OUTPUT TERMINALS OUTPUT INPUT EARTH CONNECTION IS ESSENTIAL CASTORS...
Page 48
CASTORS LEVELLER POSITION A: FIX UPS TO THE FLOOR POSITION B: LIFT UPS CASTORS FROM THE FLOOR LP 5/6-11U 120V input MANUAL BYPASS SWITCH NORMAL: POSITION 1 (LOAD ON UPS) SERVICE: POSITION 2 (LOAD ON BYPASS) INPUT/OUTPUT OUTPUT INPUT EARTH CONNECTION IS ESSENTIAL CONDUIT BOX...