Floor standing oil-fired condensing combination boiler using conventional and room sealed flue (68 pages)
Summary of Contents for Bosch BUDERUS SSB120
Page 1
WARNING: Improper installation, set-up, modification, operation or maintenance of the heating system can cause personal injury and property damage. Follow these instructions precisely. If you require assistance or further information, contact a licensed contractor / gas fitter. WARNING: The operating instructions are part of the technical documents that must be handed over to the owner or operator of the heating system.
► Immediately correct all faults to prevent system damage. Observe these instructions for your safety. ► Only use original Bosch spare parts. Losses caused by the use of The burner and control must be correctly installed and adjusted to ensure parts not supplied by Bosch are excluded from the Bosch warranty.
► The boiler is intended only for the use for which it was specifically • The gas-fired condensing SSB boilers are designed to be used in designed and built. Bosch is hereby excluded from any liability for central heating systems. Any other use is prohibited.
2 .4 Environmental responsibility / disposal Environmental responsibility is one of the fundamental company policies of the Bosch Group. We regard quality of performance, economy and environmental responsibility as equal objectives. Environmental protection laws and regulations are strictly adhered to.
Product description | 11 2 .8 Efficiency Curves 100% 20% input 30% input 100% input Return Water Temperature (°F) @ 36 Degree Rise Fig. 6 Thermal Efficiency Curves SSB85* * Thermal Efficiency curve is for reference only as this is a residential boiler 100% 20% input 30% input...
Page 12
12 | Product description 100% 20% input 30% input 100% input Return Water Temperature (°F) @ 36 Degree Rise Fig. 8 Thermal Efficiency Curves SSB160* * Thermal Efficiency curve is for reference only as this is a residential boiler 6720818456 (2018/06) US...
Regulations | 13 - In the event that the requirements of this subdivision can not be Regulations met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a Observe all rules, regulations, standards and guidelines battery operated carbon monoxide detector with an alarm shall be...
14 | Installation The recommended clearance for ease of installation and service are Installation illustrated in the following picture: 4 .1 Packaging and product identification The SSB is delivered strapped to a pallet, packed and protected in a cardboard carton. NOTICE: The packaging shows the characteristics of the 2”...
Installation | 15 4 .3 Water Chemistry Guidelines In the following table are listed the chemical water specifications. Parameters Units Value NOTICE: If using anti-freeze: General feature Colorless, no sediment ► For freeze protection use only propylene glycol, with Dissolved Oxygen mg/l <...
16 | Installation 4 .4 .1 Low water cut off 4 .4 .4 Pressure relief valve (PRV) ASME approved A low water cut off (LWCO) is installed in the boiler, the manual reset The boiler is supplied with a pressure relief valve (PRV). The relief button is located on the front of the internal control box.
Installation | 17 4 .4 .6 Pump SSB85/120/160 boilers are fitted with a circulator pump. The graph in the following figure shows the head range of the pump depending on the flow rate compared to the relevant pressure drop. SSB85 – UPS15-58 SSB85 pressure drop speed3...
Page 18
18 | Installation SSB120 – UPS25-78 Head available for SSB120 the system at speed3 pressure drop speed3 speed2 speed1 Flow rate / GPM Fig. 13 SSB120 Pump curve SSB160 – UPS25-78 SSB160 pressure drop Head available for the system at speed3 speed3 speed2 speed1...
Installation | 19 4 .4 .7 Condensate removal specific purpose, because the acidic action of condensate will cause a rapid deterioration. The condensate water produced by the boiler during its normal operation is collected by a condensate trap (A) provided with the boiler and •...
20 | Installation The general electrical connection is shown in the following diagram : (**) Boiler Pump CH Pump DHW CASCADE DHW Tank Room Supply 120 V Main in Alarm 120 V Aux Pump LINK Switch Door Sensor Thermostat Sensor 3 Way 1 2 3 4 5 6 7 8 9 10 11 12 13 14 101 102 103 104 105 106 107 108 109...
Installation | 21 4 .5 .5 Electrical wiring diagram Jumper factory installed LOW VOLTAGE HIGH VOLTAGE HIGH IN / OUT VOLTAGE PUMP CH PUMP DHW 120 V Supply CASCADE Room MAIN PUMP ALLARM 120 V AUX Sensor MAIN IN Tank LINK SWITCH DOOR...
22 | Installation 4 .6 Gas supply piping LP ORIFICE INSTALLATION (SSB85 – SSB120) Natural Gas to LP conversion Verify that the type and the pressure of the gas supplied correspond with those required for the boiler. When field converting the boiler from Natural The heating unit is factory preset for operating with natural gas.
Installation | 23 LP ORIFICE INSTALLATION (SSB160) Natural Gas to LP conversion The heating unit is factory preset for operating with natural gas. This set-up can be changed using the conversion kits supplied by the manufacturer. NOTICE: This change may only be performed by an authorized Servicing Center, according to the following procedure.
24 | Installation • Photo processing plants; ► The exhaust vent and the combustion air inlet lines must be supported to prevent sagging per the vent manufacturer’s instructions. • Auto body shops; ► Do not mix components from different systems. The vent system could •...
Installation | 25 4 .7 .2 Connecting flue gas accessories Approved vent systems are: • Twin pipe, concentric pipe and 1 pipe using room air PVC / CPVC / • Stainless Steel • Approved materials PVC, CPVC, Stainless Steel, PP and PP-Flex (M&G Duravent PolyPro and Centrotherm InnoFlue) •...
Page 26
26 | Installation Fig. 28 Direct vent (sealed combustion) It is not recommended to terminate vent above any door or window, condensate can freeze causing ice formations. [1] Forced air inlet Do not use chimney as a raceway if another boiler or fireplace is vented [2] Gravity air inlet into or through chimney.
Page 27
Installation | 27 Pipe diameter per boiler Standard Material Item Standard [USA] [Canada] 2” (60mm) 2” (60mm) 2” (60mm) PVC schedule 40, Flue gas or ANSI/ASTM D1785 3” (80mm) 3” (80mm) 3” (80mm) combustion air 4” (100mm) 4” (100mm) 4” (100mm) 2”...
Installation | 29 Defining the correct value to assign to par N° 99 follow this example: When using a SSB85 with 2” (60 mm) PP venting material the maximum equivalent length is 50 feet for both vent and combustion air piping. Consider the equivalent length of vent pipe is 36 ft.
Page 30
30 | Installation Fig. 32 Horizontal venting system (sealed combustion); X≥4” (102 mm); Y ≥12” (305 mm) Fig. 34 Vertical venting system (sealed combustion); X > 12” ; Y 12” above maximum snow level or at least 24” whichever is greater Fig.
Page 31
Installation | 31 Fig. 38 Horizontal concentric system (sealed combustion) Fig. 36 Horizontal venting system (sealed combustion) ; 3 is a wall termination Fig. 37 Horizontal venting system (sealed combustion); X≥4” (102 mm) Fig. 39 Vertical venting system (sealed combustion) ; ); X > 12” (305 mm);...
Page 32
32 | Installation H>2.2 inch w.c. Fig. 40 Vertical venting system (sealed combustion) Fig. 42 Recommended additional condensate drain for high vent stack Flexible vent and combustion air pipe H>2.2 inch w.c. Fig. 41 Vertical venting system (sealed combustion) Fig. 43 Recommended additional condensate drain for long horizontal vent piping 6720818456 (2018/06) US...
Installation | 33 4 .7 .6 Multiple boiler Air intake Vent WARNING: Do not connect SSB models 85, 120 and 160 to a shared/common or cascade vent system. Each boiler Vent must have a separate, dedicated vent system. Air intake When installing multiple air and vent terminations, be sure that: •...
34 | Commissioning (for single application) 5 .2 Setting date and time Commissioning (for single application) Press the “menu” button and select “Settings” using the UP/DOWN button. Menu Domestic Hot Water Information Settings System Test Fig. 52 Press the “OK” button and select “General Settings” using the UP/DOWN button.
Commissioning (for single application) | 35 Entering in “Time Zone Settings” menu it is possible to set the time zone parameter as shown in the following figure: CH setpoint cannot be changed when outdoor reset function is enabled. See section “5.5 Parameters list” for detailed instructions regarding outdoor reset.
36 | Commissioning (for single application) Selecting “Boiler Status” and pressing “OK” for the following values: Press the “OK” button. At this point is request a password [Password is required for boiler settings only]: • Flow Temperature • Return Temperature Password •...
Page 37
Commissioning (for single application) | 37 Below is a list of parameters: Number Description Unit Default Step CH Setpoint °C / °F 176 °F 68 °F 194 °F 0.9 °F Design Supply Temp °C / °F 176 °F 68 °F 194 °F 1.8 °F Baseline Supply Temp...
Page 38
38 | Commissioning (for single application) Number Description Unit Default Step Frost Protection Off / On Disabled Disabled Enabled Frost Protection Setpoint °C / °F 50 °F 33.8 °F 68 °F 0.9 °F DHW Max Limit °C / °F 140 °F 104 °F 158 °F 0.9 °F...
Commissioning (for single application) | 39 5 .7 Adjusting and setting CO limits NOTICE: Please verify parameter 99 is to be set first. CO2 + CO2 + Insert a combustion analyzer probe into the test port “A” as shown in Fig. Fig.
40 | Troubleshooting The fan will run at the minimum speed. Troubleshooting To adjust the CO value at the minimum power turn the screw “B” shown in Fig. 70 and in Fig. 71. WARNING: Close the gas cock prior to working on the gas Verify that the value of CO is stable and is within the range indicated in train or “boiler”.
Troubleshooting | 41 6 .1 .1 Lockout errors If an error is a “Lockout” error, it is necessary to press “RESET” button (after eliminating the reason for the failure) to restart the boiler. In the following table the “Lockout” errors are listed: Error Int .
42 | Troubleshooting Error Int . nr . Description Checks Solutions a- Check the integrity of Three times flame lost during one the wire connections of the a- If wires are damaged, replace "Too Many Flame Failures" demand spark and the earth on heat them exchanger "Flow Switch Not Closed Error"...
Page 43
Troubleshooting | 43 Error Int . nr . Description Checks Solutions a- Change the pump or restart it a- Check the pump to verify b- Open the valves on hydraulic the flow circulation circuit b- Check if the valves on “Overheat Error”...
44 | Troubleshooting 6 .2 Errors not shown on display Symptoms Possible solutions Check gas type. Combustion noise too loud; rumbling noises Check inlet gas pressure; adjust as needed. Check flue gas system; clean or repair as needed. Check gas/air ratio in the combustion air and flue gas; replace gas valve as needed. Set pump speed correctly to match maximum output.
Maintenance | 45 Time interval Maintenance Maintenance Annually * Verify startup Annually * Verify the flame 7 .1 General Annually * Check relief valve Annually * Inspect the burner gasket NOTICE: The installer must inform the user about the (*) Annually or every 2000 hours. Which occurs first. contents of this section.
46 | Installation schemes The following system diagrams are showing primary/secondary piping. As Installation schemes alternative a appropriate sized low loss header can also be used. When using primary/secondary piping please follow the following guidelines: The following shows possible system diagrams. Secondary Secondary NOTICE: Application drawings in this manual are...
Installation schemes | 47 Wiring diagram for multiple zone with indirect tank (pump for each zone): Boiler Pump CH Pump DHW Alarm 120 V Aux 120 V Main in Pump CASCADE Outdoor DHW Tank Room Supply LINK Switch air sensor Sensor Thermostat Sensor...
48 | Installation schemes 8 .2 Multiple zone with indirect tank (valve for each zone) Purge Drain Zone relay Outdoor air sensor (provided with boiler Pressure By-pass installed by others) Heating zone Auto-Fill Eliminator Flow Check Condensate drain Room Thermostat Expansion Tank Relief valve...
Installation schemes | 49 Wiring diagram for multiple zone with indirect tank (valve for each zone): Boiler Pump CH Pump DHW Alarm 120 V Aux 120 V Main in Pump CASCADE Outdoor DHW Tank Room Supply LINK Switch air sensor Sensor Thermostat Sensor...
50 | Installation schemes 8 .3 Cascade Each cascade boiler has to be identified by an address (parameter N° 73 “Boiler Address” )different from the others. To define these address follow The SSB boilers can be connected together to form a cascade with a the steps below: maximum of 16 boilers.
Page 51
Installation schemes | 51 A recommended scheme for cascade installation is as follow: Purge Drain Indirect Heating Tank Heating Tank (optional) zone Return Outdoor air return sensor Auto-Fill Eliminator Indirect tank sensor (tank not shown) Condensate drain Room Thermostat Expansion Tank Relief valve pressure...
Page 52
52 | Installation schemes For this installation the wiring is shown in figure below: Pump DHW Boiler Pump CH CASCADE DHW Tank Room Supply 120 V Main in Alarm 120 V Aux Pump LINK Switch Door Sensor Thermostat Sensor 3 Way 1 2 3 4 5 6 7 8 9 10 11 12 13 14 101 102 103 104 105 106 107 108 109 110 111 112...
Installation schemes | 53 8 .3 .1 Settings (*) NOTICE: The maximum amp load for each pump (in Set the parameters as indicated in the following table (for the parameter addition to the boiler pump) is 1 A when 1 or 2 pumps are list see section “5.5 Parameters list”): connected.
54 | Commissioning log for the appliance Commissioning log for the appliance Please complete a separate log for each appliance. Home owner/operator: Last name, first name Number, Street Telephone/fax ZIP code, town System installer: Order number: Appliance type FD (Date of manufacture): Date commissioned: �...
Page 55
Commissioning log for the appliance | 55 Modified service functions: (select the modified service functions and enter the values here). Example: Vent Length Parameter changed from 1 to 2 Heating control 850 MIN: Vent length setting (par.99 “Flue length range”) � 1 | � 2 | � 3 | � 4 Gas type setting (par 98 “Gas Type”) �...
Page 56
56 | Spare parts Spare parts Fig. 83 6720818456 (2018/06) US...
Page 57
7-738-004-907 Mounting bracket control board panel ■ ■ ■ 7-738-004-908 Alignment pin front side panels ■ ■ ■ 7-738-004-924 Logo Bosch front door ■ ■ ■ 7-738-005-176 Handle front panel ■ ■ ■ 7-738-004-920 Lock and lever front panel ■...
Page 58
58 | Spare parts Shown on Fig. 86 - Fig. 87 Fig. 84 6720818456 (2018/06) US...
Page 59
Spare parts | 59 Item (→ Fig. 84) Description Order number High limit sensor and screws ■ ■ ■ 7-738-004-926 Universal temperature detector and washer ■ ■ ■ 7-738-004-930 O-ring temperature detector 0.51x0.1in 13x2.62mm ■ ■ ■ 7-738-004-931 Automatic air vent 3/8" ■...
Page 61
Spare parts | 61 Item (→ Fig. 85) Description Order number Enclosure user interface ■ ■ ■ 7-738-005-037 Circuit Board user interface ■ ■ ■ 7-738-005-038 Keypad ■ ■ ■ 7-738-005-039 Service plug cover ■ ■ ■ 7-738-005-040 On Off power switch ■...
Page 63
Spare parts | 63 Item (→ Fig. 86) Description Order number Heat exchanger SSB85 ■ 7-738-005-154 Heat exchanger SSB120 ■ 7-738-005-155 Washer for ignition electrode ■ ■ 7-738-005-034 Ignition electrode with washer ■ ■ 7-738-005-397 Sight glass for combustion ■ ■...
Page 64
64 | Spare parts SSB160 ONLY Fig. 87 6720818456 (2018/06) US...
Page 65
Spare parts | 65 Item (→ Fig. 87) Description Order number Heat exchanger SSB160 ■ 7-738-005-156 Washer for ignition electrode ■ 7-738-005-034 Ignition electrode with washer ■ 7-738-005-397 Sight glass for combustion ■ 7-738-005-031 Gasket premix burner tube ■ 7-738-004-985 Premix burner tube ■...
Page 66
66 | Spare parts Notes 6720818456 (2018/06) US...
Page 67
Spare parts | 67 Notes 6720818456 (2018/06) US...
Page 68
United States and Canada Bosch Thermotechnology Corp. 50 Wentworth Avenue Londonderry, NH 03053 Tel. 603-552-1100 Fax 603-965-7581 www.boschheatingandcooling.com U.S.A. Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances.