Split-type Air-Conditioner MXZ-4E83VA MXZ-5E102VA MXZ-2E53VAHZ For INSTALLER Installation Manual English is original. • This manual only describes the installation of outdoor unit. English When installing the indoor unit, refer to the installation manual of indoor unit.
Page 2
49 dB (A) 51 dB (A) 25 A 3-core 4-core 230 V 50 Hz 25 m / 80 m 15 m 25 / 80 20 g/m 52 dB (A) 56 dB (A) MXZ-5E102VA 2.5 mm 1.0 / 1.5 mm MXZ-2E53VAHZ 16 A/25 A 20 m / 30 m 20 / 30 45 dB (A) 47 dB (A) *1 Connect to the power switch which has a gap of 3 mm or more when open to *9 If the outdoor unit is installed higher than the indoor unit, max. height dif- ference is reduced to 10 m.
Page 3
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table. (Unit: mm (inch)) Optional different-diameter joints (port size of outdoor unit → diameter of connection pipe) Port size of outdoor unit MXZ- MXZ-...
Page 4
1-5. INSTALLATION DIAGRAM ACCESSORIES (MXZ-4E83/5E102VA only) After the leak test, apply insulat- Check the following parts before installation. ing material tightly so that there is no gap. (1) Drain socket (2) Drain cap When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically PARTS TO BE PROVIDED AT YOUR SITE...
Page 5
Service panel Screws Connecting order • Connect the terminal block in following order. A → B → C → D → E → P MXZ-5E102VA A → B → C → D → P MXZ-4E83VA MXZ-2E53VAHZ A → B → P Power supply Terminal block for...
Page 6
3. FLARING WORK AND PIPE CONNECTION 3-1. FLARING WORK 1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2) 2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3) Good No good • Aim the copper pipe downward while removing burrs to prevent burrs Copper pipe from dropping in the pipe. 3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (Not possible to put them on after flaring work.) Tilted Uneven Burred 4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown Fig. 2 Fig.
Page 7
(for R410A) To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 40°C) during cold season. But never use naked fire or steam. Refrigerant gas cylinder for R410A with siphon Model Indoor unit MXZ-5E102VA Refrigerant (liquid) A – E MXZ-4E83VA A – D Electronic scale for refrigerant charging MXZ-2E53VAHZ A –...
Page 8
4-6. TEST RUN • Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate properly. • If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires cannot be detected. Thus, be sure to perform the test run one by one. About the restart protective mechanism Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. Wiring/piping correction function This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi- nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below. Make sure that the following is done. • Power is supplied to the unit. • Stop valves are open. Note: During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not a malfunction.
Page 9
декларира на своя собствена отговорност, че климатиците и термопомпите, описани по-долу, за употреба в жилищни, търговски и леки промишлени условия: MITSUBISHI ELECTRIC, MXZ-4E83VA, MXZ-5E102VA, MXZ-2E53VAHZ Note: Its serial number is on the nameplate of the product.
Page 10
Travellers Lane, Hatfield, Herts., AL10 8XB, England, U.K. Polish Branch Krakowska 50, PL-32-083 Balice, Poland MITSUBISHI ELECTRIC TURKEY ELEKTRİK ÜRÜNLERI A.Ş. Şerifali Mah. Kale Sok. No: 41 34775 Ümraniye, İstanbul / Turkey HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN...