2 Unit Location Considerations

2.1 Unit Dimensions

Models
BOVA24-15
BOVA36-15
BOVA60-15
Table 1
The unit's weight values are on the carton box.
When mounting the outdoor unit on a roof, be sure the roof will support the unit's
weight. Properly selected isolation is recommended to prevent sound or vibration
transmission to the building structure.
Figure 1

2.2 Refrigerant Piping Limits

Liquid
Suction
System
Line
Line
Capacity
Model
Inch O.D.
3/4 Std.
24K
3/8 *
5/8 Opt.
3/4 Std.
36K
3/8 *
5/8 Opt.
7/8 Std.
48K
3/8 *
3/4 Opt.
7/8 Std.
3/4 Opt.
60K
3/8 *
1 1/8 Opt.
Table 2
* Standard line size is recommended;
N/A: Application not recommended;
Refrigerant charge: refer to Sec. 14
6 |
H x W x L (inches)
24-15/16 x 28 x 28
24-15/16 x 28 x 28
33-3/16 x 29-1/8 x 29-1/8
Total Equivalent Length - Feet
25
50
75
100
Maximum Vertical Separation - Feet
25
50
45
40
25
50
45
40
25
50
50
50
25
50
50
50
25
50
50
40
25
50
50
40
25
50
50
40
25
50
50
40
25
40
N/A
N/A
Maximum line equivalent length = 100 feet.
Maximum vertical equivalent length = 50 feet.
Use only the line diameters indicated in Table 2.
If the suction linesets are greater than 50 feet, do not use a larger suction
line than recommended.
Figure 2
Bosch IDS BOVA15 Split System Heat Pump - BTC 761701317 A (02.2022)
Standard Lineset
Lineset 100' Max
Line Length
50' Max
Line Lift
50' Max
Line Lift