DOK-SYTROX-MPAS1******-IT01-EN-P
Rexroth Sytronix SvP 70xx Motor-Pump Unit MPAS1
6.5
Product Storage
6.6
Storage Times
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Store the products in their original package at a dry, dust free, vibration free
and light protected place without direct solar radiation. Please observe
classes 1K2, 1B1, 1C1,1S1,1M2 specified for storage acc. to DIN EN
60721-3-2.
Please observe the following classification limitations:
●
Storage temperature -20 ... +60 ℃
●
Relative air humidity 5 ... 95 %
●
Absolute air humidity 1 ... 29 g/m³
●
No condensation
●
No ice formation/freezing
●
No occurrence of salt mist
NOTICE
●
Protect the products from dampness and corrosion.
●
Store them only in rainproof and dry rooms.
Before storage, discharge the liquid coolant from liquid-cooled
motors to avoid frost damage.
Additional measures must be taken on commissioning to preserve proper
functioning – irrespective of the storage time which may be longer than the
warranty period of our products. However, this does not involve any
additional warranty claims.
Motors
Bearing time / months
Measures for commissioning
> 1
> 12
> 60
●
●
●
Control all parts to be free of damage.
●
●
Check all electrical contacts to be free from corrosion.
Let the motor run in without load for one hour at 800 ... 1,000
●
●
Upm. In the case of a mounted pump, ensure that the pump does
not run dry.
Measure the insulation resistance. Dry the winding at a value of <
●
●
1kOhm per volt rated voltage.
●
Exchange bearings.
●
Exchange encoders.
Tab. 6-5:
Measures before commissioning motors that have been stored over a
prolonged period of time
Bosch Rexroth AG
Transport and Storage
Damage due to moisture and humidity!
37/83