DHW settings menu for fresh water station
If a fresh water station is installed and configured for the system, this
menu replaces the standard DHW menu.
Setting the DHW temperature ≥ 52 °C can lead to higher electricity cost
as the electric booster heater may be activated.
Menu item
Control range: Function description
Max. DHW temp.
Set the maximum DHW-temperature for the system.
DHW temp. comf.
[15... 65] °C: set the DHW-temperature for the comfort
mode (depending on the installed heat source).
DHW temp. Eco
[15... 65] °C: set the DHW-temperature for the Eco mode
(depending on the installed heat source).
Circulation time
[Yes] | [No]: activate or deactivate the DHW circulation
pump.
Circulation oper.
[Off]: circulation off.
mode
[On]: circulation permanently on (by taking the start
frequency into account).
[As DHW system]: Activate the same time program for
circulation as for DHW heating. Further information and
settings of the customised time program ( user interface
operating instructions).
[Own time program]: activate customised time program
for circulation. Further information and settings of the
customised time program ( user interface operating
instructions).
DHW circ. start
If the DHW circulation pump is active via the time program
freq.
for the DHW circulation pump or if it is permanently
switched on (DHW circulation pump operating mode:
[On]), this setting affects the DHW circulation pump
operation.
[1 x 3 minutes/h] ...[3 x 3 minutes/h]...
[6 x 3 minutes/h]: the DHW circulation pump goes into
operation once ... 6 times per hour for 3 minutes.
[Permanent]: the DHW circulation pump is permanently in
operation.
Circulation pulse
[Yes] | [No]: The circulation pump runs for 3 minutes as
soon as there is a short tap (2-10 seconds). The pump is
then blocked for 10 minutes.
Automat. therm.
[Yes]: the thermal disinfection is started automatically at
disinfect.
the set time.
[No]: the thermal disinfection is not started automatically.
Therm.
[Monday] ... [Tuesday] ... [Sunday]: weekday on which
disinfection day
thermal disinfection is performed.
[Daily heat-up]: thermal disinfection is performed daily.
Therm.
[00:00 ... 02:00 ... 23:45]: time of day for the start of
disinfection time
thermal disinfection at the set day.
Therm.
e.g. [60 ...65...80] °C: temperature to which the DHW
disinfection temp.
volume is heated during thermal disinfection.
Daily heat-up
[Yes]: The DHW volume is automatically heated up daily at
the same time to 60 °C.
[No]: No daily heat-up.
Daily heat-up time [00:00 ... 02:00 ... 23:45]: time for the start of the daily
heat-up.
HPC 410 – 6721832682 (2021/02)
Menu item
Control range: Function description
Fault display
[Yes]: If a fault occurs in the fresh water system, the output
for a fault message is switched on.
[No]: If a fault occurs in the fresh water system, the output
for a fault message is not switched on (always without
power).
[Inverted]:
The fault message output is energized in normal operation,
but If a fault occurs in the fresh water system the output is
deenergized.
Keep hot
[Yes] | [No]: Activate the warm keeping function. If the
fresh water system is far from the buffer tank, it can be kept
warm by circulation. The primary circuit pump starts every
15 minutes until the hot water target temperature is
reached on the flow sensor.
Ht main. sw.-on
Set the temperature difference between set temperature
temp. diff
and actual temperature that is required to start the warm
keeping function.
Sw.diff. ret.
Set the temperature difference between the buffer tank
stratification
temperature (at the level of the return valve) and the
secondary-side cold water inlet temperature for switching
the return valve.
Table 18 Settings in the DHW fresh water station menu
4.5
Menu: Pool settings
Make the pool heating specific settings in this menu. These settings are
only available if the system is designed and configured accordingly and
the type of appliance used supports this setting.
Menu item
Control range: Function description
Pool module
[Yes] | [No]: Set if a pool module is installed.
available?
Pool mixing valve
[10...6000] s: Set the runtime for the pool mixing valve.
Control rate pool
Set the control value that regulates the compressor control
op.
speed. A higher value results in higher speed.
Del. aux. heater
[60...1200] K x min: Set the additional heater switch-on
pool oper.
delay for pool heating. The delay is depending on time and
deviation from desired flow temperature.
Logic external
[Open contact]: Open contact is interpreted as "On".
connection
[Closed contact]: Closed contact is interpreted as "On.
Table 19 Settings in the pool data menu
4.6
Solar thermal system settings
If a solar thermal system is integrated into the heating system via a
module, corresponding menus and menu items are available. Extension
of the menus by the solar thermal system is described in the operating
instructions of the used module.
In the Solar settings menu the sub-menus listed in Tab. 20 are available
with all solar thermal systems.
NOTICE
Risk of system damage!
▶ Charge and vent solar system before commissioning.
Menu item
Purpose of the menu
Change solar
Graphic configuration of the solar thermal system.
configuration
Current solar
Graphic representation of the configured solar thermal
configuration
system.
Service menu
15