ABB ACS560 Quick Installation And Start-Up Manual

ABB ACS560 Quick Installation And Start-Up Manual

General purpose drives standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

ABB GENERAL PURPOSE DRIVES
ACS560 standard control program
Quick installation and start-up guide
English . . . . . . . 3
हिं द ी . . . . . . . . 153
3AXD50000042620 Rev G MUL
EFFECTIVE: 2020-03-03
EN
HI

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS560

  • Page 1 — ABB GENERAL PURPOSE DRIVES ACS560 standard control program Quick installation and start-up guide English ..3 हिं द ी ..153 3AXD50000042620 Rev G MUL EFFECTIVE: 2020-03-03...
  • Page 3 EN - Quick installation and start-up guide This guide instructs how to install and start-up the ACS560 drive of all frame sizes (R0...R8). For complete information, see the drive ACS560 standard control program firmware manual (3AXD50000044997[English]) and ACS560 drives (0.75 to 160 kW, 1.0 to 215 hp) hardware manual (3AXD50000044998[English]).
  • Page 4 4 EN - Quick installation and start-up guide ■ Select the power cables Size the power cables according to local regulations to carry the nominal current given on the type designation label of your drive. See Ratings (page 117). ■ Ensure the cooling The maximum ambient temperature without derating is: •...
  • Page 5 EN - Quick installation and start-up guide 5 Install the drive You can install the drive • to a DIN installation rail with integrated lock. This method applies to frames R0...R2 only. • with screws to a suitable surface (wall or assembly plate). This method applies to all frames R0...R8.
  • Page 6 6 EN - Quick installation and start-up guide ■ Installing a drive with screws (frames R0...R8) All drives of frames R0...R8 can be installed on a wall with screws. See the required screw sizes in below mounting dimensions table. See also Dimensions, weights and free space requirements (page 122) WARNING!
  • Page 7 EN - Quick installation and start-up guide 7 See the example of mounting screws in frame R0 6. Frames R5...R8 only: Remove the front cover with fastening screws (6a), move the cover to the top side (6b) and then up (6c). 7.
  • Page 8 Use a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must be more than 100 Mohm (reference value at 25 °C [77 °F]). For the insulation resistance of other motors, refer to the manufacturer’s instructions.
  • Page 9 EN - Quick installation and start-up guide 9 Connecting the power cables ■ Connection diagram For alternatives, see hardware manual. Use a separate grounding PE cable (2a) or a cable with a separate PE conductor (2b) if the conductivity of the shield does not meet the requirements for the PE conductor (see hardware manual).
  • Page 10 10 EN - Quick installation and start-up guide ■ Connection procedure: frames R0…R2 If the drive is connected on an IT (ungrounded) system, make sure that the EMC filter and Varistor (VAR) is disconnected. For more information, see hardware manual. 1.
  • Page 11 Motor cable Motor cable 2. Prepare the ends of the cable as illustrated in the figure. Two different motor cable EN - Quick installation and start-up guide 11 types are shown in the figures (2a.and 2b). 2. Prepare the ends of the cable as illustrated in the figure. Two different motor cable types are shown in the figures (2a.and 2b).
  • Page 12 12 EN - Quick installation and start-up guide 80 Electrical installation 5. Connect the input power cable as follows: 5. Connect the input power cable as follows: • Connect the twisted shield of the cable to the grounding terminal (5a). •...
  • Page 13 N·m lbf·ft N·m lbf·ft L1. L2. L3 0.5…0.6 1.2…1.5 0.9…1.1 EN - Quick installation and start-up guide 13 6. Connect the braking resistor cable as the motor cable in step 4. 7. Ground the shield 360 degrees (6a). 8. Connect the twisted shield to the grounding terminal (6b) and the conductors to the 8.
  • Page 14 78 Electrical installation 14 EN - Quick installation and start-up guide 78 Electrical installation Connection procedure, frames R0…R2 Connection procedure, frames R0…R2 ■ Connection procedure, frames R3...R4 1. Remove the front cover as follows: 1. Remove the front cover as follows: •...
  • Page 15 Electrical installation 83 EN - Quick installation and start-up guide 15 3. Connect the motor cable as follows: If the power cable is temporarily removed from the grounding shelf, connect the • Ground the shield 360° by tightening the clamp of the power cable grounding shelf motor and input power cables except the 360 degree grounding, and then reinstall the grounding shelf.
  • Page 16 16 EN - Quick installation and start-up guide 84 Electrical installation 5. Connect the input power cable as follows: • Ground the shield 360° by tightening the clamp of the power cable grounding shelf 5. Connect the input power cable as follows: onto the stripped part of the cable (6a).
  • Page 17 6. For R3, connect cable by the motor cable method mentioned instep 3. EN - Quick installation and start-up guide 17 7. Ground the shield 360 degrees (7a). 8. Connect the twisted shield to the grounding terminal (7b). 9. For R3, connect the conductors to the R+ and R- terminals (7c). 9.
  • Page 18 WARNING! If the drive will be connected on an IT (unground 18 EN - Quick installation and start-up guide make sure you have disconnected the EMC filter and ground-t See page 71. If the drive will be connected on a corner-grounded TN ■...
  • Page 19 Note: Frame R8 only: Tighten the screws to the torque given in the figure (9b). • If you connected the connector to only one conductor, ABB recommends to put the conductor under the upper pressure plate. • The connectors are detachable, but ABB recommends not to detach them. If you...
  • Page 20 • If you connect only one conductor to the connector, we recommend that you put it • If you connect only one conductor to the connector, we recommend that you put it under the upper pressure plate. under the upper pressure plate. 20 EN - Quick installation and start-up guide •...
  • Page 21 EN - Quick installation and start-up guide 21 • Remove the combi screw attached to the connector and to its terminal post, and pull the connector off. • Put the conductor under the connector pressure plate and pre-tighten the conductor. Electrical installation 89 Electrical installation 89 •...
  • Page 22 The UDC+ and UDC- terminals (as standard in frames R4…R8) are for using external brake chopper units. Connecting the control cables Connect the cables as described in firmware manual. See the below default I/O connections of ABB standard macro. See other macro connections in the firmware manual.
  • Page 23 EN - Quick installation and start-up guide 23 Default control connections of ABB standard macro ■ Connection diagram...
  • Page 24 24 EN - Quick installation and start-up guide Note: For information of parameters listed in the diagram, see Parameter listing (page 47). Terminal sizes • (frames R0…R8): 0.14…1.5 mm (all terminals) • tightening torques: 0.5…0.6 N·m (0.4 lbf·ft) Notes: Current [0(4)…20 mA, R <...
  • Page 25 BIO-01 I/O extension module (for R0...R2 frames) • Fieldbus module (in frames R0...R2 frames, fieldbus module can be used with BIO-01 also) For information on supported fieldbus modules, see ACS560 product catalog. For more information on optional modules, see hardware manual. ■ Hardware description Product overview The BIO-01 front option module (Option +L515) is an I/O extension module for R0...R2...
  • Page 26 ■ Install BIO-01 The BIO-01 module is automatically identified by the drive firmware. To configure the By default, RIIO-01 module is provided in ACS560 standard R0...R2 drives. You can inputs refer to the ACS480 firmware manual (3AXD50000047399 [English]) remove the RIIO-01 module and can install BIO-01 and/or fieldbus adapter module (+Fxxx).
  • Page 27 EN - Quick installation and start-up guide 27 132 Electrical installation c. Pull the module and remove it. Installing option modules Note: The module can be tightly in position. Note: In US deliveries, options are already installed at the factory. 3.
  • Page 28 28 EN - Quick installation and start-up guide Checking the compatibility with IT (ungrounded) and corner-grounded TN systems ■ EMC filter The internal EMC filter is not suitable for use on an IT (ungrounded) system or on a corner-grounded TN system. Disconnect the EMC filter before connecting the drive to the supply network.
  • Page 29 EN - Quick installation and start-up guide 29 Frame EMC filter Ground- to- Symmetrically Corner groun- IT systems (un- sizes (EMC) phase varis- grounded TN ded TN systems grounded or systems (TN-S high-resistance systems) 1 (VAR) grounded [>30 ohms]) 3 R4…R5 EMC (2 Do not disconnect...
  • Page 30 30 EN - Quick installation and start-up guide Electrical installation 103 Reinstalling covers Reinstalling covers ■ Reinstalling cover, frames size R0…R2 Reinstalling cover, frames size R0…R2 1. Reinstall the cover. 1. Reinstall the cover. 2. Tighten the retaining screw at the bottom with a screwdriver. 2.
  • Page 31 EN - Quick installation and start-up guide 31 ACS560R0-R8 QIG.book Page 20 Wednesday, May 30, 2018 3:45 PM ■ Reinstalling side plates and covers, frames size R5…R8 ACS560R0-R8 QIG.book Page 20 Wednesday, May 30, 2018 3:45 PM 20 EN - Quick installation and start-up guide 1.
  • Page 32 R6...R8 1. Install the side plates (1a) of the cable box. Tighten the retaining screws (1b) with 32 EN - Quick installation and start-up guide a screw driver. 2. Slide the cover (2a) of the cable box on the module from below until the cover snaps into place.
  • Page 33 EN - Quick installation and start-up guide 33 ■ Using the control panel Clip – Press the clip downward to remove the panel from the drive. Display – Shows basic home view 1 by default. See parameter 49.19 Basic panel home view 1.
  • Page 34 34 EN - Quick installation and start-up guide ■ Display The control panel display shows the following elements: Control location and related icons: Indic- ates how the drive is controlled. • Loc: The drive is in local control, that is, controlled from the control panel.
  • Page 35 EN - Quick installation and start-up guide 35 Sub menus The sub-menu items allows you to change settings and set actions. Some sub menus also have menus and/or option lists. Each sub-menu item has access to frequently used parameters. For the complete parameter list, go to Parameter settings Note: The content of the sub menus depend on the drive type.
  • Page 36 36 EN - Quick installation and start-up guide 1) Automatic - Default start 2) Constant - Enables constant mode. Guarantees optimal pre-magnetizing time (the mo- motor start in most cases. It in- tor start is synchronized with cludes the flying start function the release of a mechanical (starting into a rotating motor) brake).
  • Page 37 ABB standard (2- specific I/O connections. wire). See menu description be- low. → Selected macro is ABB standard (2-wire) 1) ABB standard (2-wire) 2) 3-wire macro - Suitable - Default macro for general when the drive is controlled purpose.
  • Page 38 38 EN - Quick installation and start-up guide 1) DI - Digital Inputs 5) AI1 and AI2 values DI1...DI6 6) AO1 and AO2 values 2) AI - Analog Inputs AI1...AI2 3) RO - Relay Outputs RO1...RO3 4) AO1 - Analog Outputs AO1...AO2...
  • Page 39 EN - Quick installation and start-up guide 39 Diagnostics Displays the active faults and warnings and how to fix and reset. For information about fault and warning codes, see section Diagnostics (page 127). 1) Active Fault - Displays 2) Fault History - Lists the active faults.
  • Page 40 40 EN - Quick installation and start-up guide 1) Access to complete 2) Modified parameters list. parameter list from the main menu. Complete parameter list Contains the complete parameter list. See Parameter listing (page 47). 1) Access to the complete parameter list.
  • Page 41 EN - Quick installation and start-up guide 41 Setting speed or frequency reference In the Options menu , move to the speed or frequency refer- ence (1) item using the arrow buttons. Press the OK button to open the item. Use arrow buttons to set the speed or frequency value.
  • Page 42 42 EN - Quick installation and start-up guide Warning messages The display shows warning message codes when a problem is de- tected. To view the warning messages list: Open the Main menu Select Diagnostics and open the Warning messages list. See list of Warning messages.
  • Page 43 EN - Quick installation and start-up guide 43 Auto configuration of I/O’s and fieldbus module You can configure the connected optional modules or/and fieldbus modules automatically. 1. Switch off the drive and connect the required modules. For more information on optional modules and its installation, see chapter Electrical installation in the hardware manual.
  • Page 44 44 EN - Quick installation and start-up guide Drive and panel communication failure The drive does not respond to the panel commands during commu- nication failure. The drive and the panel are not compatible. Status light Continuous green Indicates that drive is functioning normally. Green, blinking Indicates an active warning in the drive.
  • Page 45 EN - Quick installation and start-up guide 45...
  • Page 46 46 EN - Quick installation and start-up guide...
  • Page 47 Parameter listing 47 Parameter listing Index Name Range/List Unit Default 01 Actual values 01.01 Motor speed used -30000.00…30000.00 01.02 Motor speed estimated -30000.00…30000.00 01.03 Motor speed% -1000.00…1000.00 01.06 Output frequency -500.00…500.00 01.07 Motor current 0.00…30000.00 01.08 Motor current% of motor nom 0.0…1000.0 01.09 Motor current% of drive nom...
  • Page 48 48 Parameter listing Index Name Range/List Unit Default 01.53 Previous day kWh 0.00…100000.00 01.54 Cumulative inverter energy -200000000.0…200000000.0 01.55 Inverter GWh counter (reset- 0…65535 table) 01.56 Inverter MWh counter (reset- 0…1000 table) 01.57 Inverter kWh counter (reset- 0…1000 table) 01.58 Cumulative inverter energy -200000000.0…200000000.0 (resettable)
  • Page 49 Parameter listing 49 Index Name Range/List Unit Default 04.03 Active fault 3 0x0000...0xffff 0x0000 04.06 Active warning 1 0x0000...0xffff 0x0000 04.07 Active warning 2 0x0000...0xffff 0x0000 04.08 Active warning 3 0x0000...0xffff 0x0000 04.11 Latest fault 0x0000...0xffff 0x0000 04.12 2nd latest fault 0x0000...0xffff 0x0000 04.13...
  • Page 50 50 Parameter listing Index Name Range/List Unit Default Name Name Name Any warning Overcurrent Reserved or fault Any warning Reserved Device over- temp flt Any fault DC over- 10...15 Reserved voltage Reserved DC under- voltage 05.21 Diagnostic word 2 0b0000...0b1111 0b0000 Name Name...
  • Page 51 Parameter listing 51 Index Name Range/List Unit Default 06.01 Main control word 0x0000...0xffff 0x0000 Name Name Name Off1 control Ramp in User bit 0 zero Off2 control Reset User bit 1 Off3 control Inching 1 User bit 2 Inching 2 User bit 3 Ramp out Remote cmd...
  • Page 52 52 Parameter listing Index Name Range/List Unit Default 06.17 Drive status word 2 0b0000...0b111 0b0000 Name Name Name Identification Safe refer- 11…12 Reserved run done ence active Magnetized Last speed Start delay active active Torque con- 7...8 Reserved 14...15 Reserved trol Speed con- Jogging act-...
  • Page 53 Parameter listing 53 Index Name Range/List Unit Default 06.20 Constant speed status word 0b0000...0b1111 0b0000 Name Name Name Constant Constant Constant speed 1 speed 4 speed 7 Constant Constant 7...15 Reserved speed 2 speed 5 Constant Constant speed 3 speed 6 06.21 Drive status word 3 0b0000...0b1111...
  • Page 54 54 Parameter listing Index Name Range/List Unit Default Name Name Name Name FECA-01 BIO-01 FMBT-21 served Base unit FPBA-01 RIIO-01 served FCAN-01 FSCA-01 FPNO- served FENA-21 FEIP-21 FEPL-02 served 07.36 Drive configuration 2 0x0000...0xffff 0x0000 Name Name Name Name FLON-01 FCNA-01 CMOD- CHDI-01...
  • Page 55 Parameter listing 55 Index Name Range/List Unit Default 10.09 DI3 ON delay 0.00...3000.00 0.00 10.10 DI3 OFF delay 0.00...3000.00 0.00 10.11 DI4 ON delay 0.00...3000.00 0.00 10.12 DI4 OFF delay 0.00...3000.00 0.00 10.13 DI5 ON delay 0.00...3000.00 0.00 10.14 DI5 OFF delay 0.00...3000.00 0.00 10.15...
  • Page 56 56 Parameter listing Index Name Range/List Unit Default 10.24 RO1 source 0...2, 4...24, 27...35, Ready run[2] 45...48 Not energized[0] Above limit[12] Ext2 active[23] RO/DIO control word bit1[41] Energized[1] Warning[13] Remote control[24] RO/DIO control word bit2[42] Ready run[2] Fault[14] Timed function 1[27] PFC1[45] Enabled[4] Fault (-1) [15]...
  • Page 57 Parameter listing 57 Index Name Range/List Unit Default 10.101 RO1 toggle counter 0...4294967000 10.102 RO2 toggle counter 0...4294967000 10.103 RO2 toggle counter 0...4294967000 11 Standard DIO, FI, FO 11.21 DI5 configuration Digital input[0], Fre- Digital input[0] quency input [1] 11.38 Freq in 1 actual value 0…16000 11.39...
  • Page 58 58 Parameter listing Index Name Range/List Unit Default 12.13 AI1 forced value 0.000…11.000 12.15 AI1 unit selection V[2], mA[10] V[2] 12.16 AI1 filter time 0.000 … 30.000 0.100 12.17 AI1 Min 0.000…11.000 0.000 12.18 AI1 Max 0.000…11.000 10.000 12.19 AI1 scaled at AI1 Min -32768.000 …...
  • Page 59 Parameter listing 59 Index Name Range/List Unit Default Zero[0] DC voltage[7] Abs motor speed AO1 data stor- used[26] age[37] Motor speed used[1] Output power[8] Abs motor AO2 data stor- speed%[27] age[38] Output frequency[3] Freq ref used [14] Abs output fre- Other...
  • Page 60 60 Parameter listing Index Name Range/List Unit Default Zero[1] Min[4] Reserved[7...9] Speed[2] Max[5] Scalar (Hz)[10] Torque[3] Add[6] Forced magn[20] 19.11 Ext1/Ext2 selection 0...8, 19...21, 25...27, EXT1[0] 32...34 EXT1[0] DI2[4] DI6[8] Supervision FBA A connec- 1[25] tion loss[33] EXT2[1] DI3[5] Timed function Supervision EFB connection 1[19]...
  • Page 61 Parameter listing 61 Index Name Range/List Unit Default Always off[0] DI2[3] DI5[6] Timed function Supervision 2[19] 2[25] Always on[1] DI3[4] DI6[7] Timed function Supervision 3[20] 3[26] DI1[2] DI4[5] Timed function Supervision Other... [18] 1[24] 20.04 Ext1 in2 source See parameter 20.03 DI2[3] Ext1 in1 source 20.05...
  • Page 62 62 Parameter listing Index Name Range/List Unit Default Not selected[0] DI3[4] Timed function Supervision Other... [18] 2[25] Selected[1] DI4[5] Timed function Supervision 2[19] 3[26] DI1[2] DI5[6] Timed function FBA A MCW bit 3[20] 3[30] DI2[3] DI6[7] Supervision EFB MCW bit 1[24] 3[32] 20.19...
  • Page 63 Parameter listing 63 Index Name Range/List Unit Default 21.07 Zero speed delay 0…30000 21.08 DC current control 0b0000…0b1111 0b0000 Name Name Name DC hold Post magnet- 2...15 Reserved ization 21.09 DC hold speed 0.00 … 1000.00 5.00 21.10 DC current reference 0.0 …...
  • Page 64 64 Parameter listing Index Name Range/List Unit Default 21.31 Speed compensated stop 0.00…1000.00 0.00 delay 21.32 Speed comp stop threshold 0…100 21.34 Force auto restart Disable[0], Enable[1] Disable[0] 22 Speed reference selection 22.01 Speed reference unlimited -30000.00...30000.00 0.00 22.11 Ext1 speed ref1 0...2, 4, 5, 8, 9, 15...19 AI1 scaled[1] Zero[0]...
  • Page 65 Parameter listing 65 Index Name Range/List Unit Default 22.22 Constant speed sel1 0...7, 18...20, 24...26 DI3[4] Always off[0] DI2[3] DI5[6] Timed function Supervision 2[19] 2[25] Always on[1] DI3[4] DI6[7] Timed function Supervision 3[20] 3[26] DI1[2] DI4[5] Timed function Supervision Other... [18] 1[24] 22.23...
  • Page 66 66 Parameter listing Index Name Range/List Unit Default 22.71 Motor potentiometer function 0...3 Disabled[0] Disabled[0] Enabled (resume always)[2] Enabled (init at stop /power-up)[1] Enable (init to actual)[3] 22.72 Motor potentiometer initial -32768.00 … 32767.00 0.00 value 22.73 Motor potentiometer up 0...7, 18...20, 24...26 Not used[0] source...
  • Page 67 Parameter listing 67 Index Name Range/List Unit Default 23.11 Ramp set selection 0...7, 20 DI5[6] Acc/Dec time 1[0] DI2[3] DI5[6] EFB DCU CW bit 10[20] Acc/Dec time 2[1] DI3[4] DI6[7] Other[bit]... DI1[2] DI4[5] FBA A[18] 23.12 Acceleration time 1 0.000 …1800.000 20.000 23.13 Deceleration time 1...
  • Page 68 68 Parameter listing Index Name Range/List Unit Default 25.33 Speed controller autotune Off[0], On[1] Off[0] 25.34 Speed controller autotune Smooth[0], Normal[1], Normal[1] mode Tight[2] 25.37 Mechanical time constant 0.00...1000.00 0.00 25.38 Autotune torque step 0.00...100.00 10.00 25.39 Autotune speed step 0.00...100.00 10.00 25.40...
  • Page 69 Parameter listing 69 Index Name Range/List Unit Default Torque reference DI1[3] DI4[6] Other... 1[0] Torque reference DI2[4] DI5[7] 2[1] Follow Ext1/Ext2 se- DI3[5] DI6[8] lection[2] 26.17 Torque ref filter time 0.000…30.000 0.000 26.18 Torque ramp up time 0.000…60.000 0.000 26.19 Torque ramp down time 0.000…60.000 0.000...
  • Page 70 70 Parameter listing Index Name Range/List Unit Default 28.02 Frequency ref ramp output -500.00 … 500.00 0.00 28.11 EXT1 frequency ref1 0...2, 4, 5, 8, 9, 15...19 AI scaled[1] Zero[0] FB A ref1[4] EFB ref2[9] Frequency in- Other... put[17] AI1 scaled[1] FB A ref2[5] Motor poten- Control panel...
  • Page 71 Parameter listing 71 Index Name Range/List Unit Default 28.23 Constant frequency sel2 See parameter 28.22 DI4[4] Constant frequency sel1 28.24 Constant frequency sel3 See parameter 28.22 Always off[0] Constant frequency sel1 28.26 Constant frequency 1 -500.00 … 500.00 5.00 28.27 Constant frequency 2 -500.00 …...
  • Page 72 72 Parameter listing Index Name Range/List Unit Default 28.73 Freq deceleration time 1 0.000 …1800.000 20.000 28.74 Freq acceleration time 2 0.000 …1800.000 60.000 28.75 Freq deceleration time 2 0.000 …1800.000 60.000 28.76 Freq ramp in zero source 0...7 Inactive[1] Act- Inact- DI1[2]...
  • Page 73 Parameter listing 73 Index Name Range/List Unit Default 30.02 Torque limit status 0b0000…0b1111 0b0000 Name Name Name Name Under- Internal Thermal IGBT voltage current overtem- perature Over- Load Max cur- IGBT voltage angle rent overload Minimum Motor User cur- 13…15 torque pullout rent...
  • Page 74 74 Parameter listing Index Name Range/List Unit Default Zero[0] PID[15] Minimum Other... scaled[1] scaled[2] served[3...14] torque 2[16] 30.22 Max torque 2 source Maximum torque 2[16] Zero[0] PID[15] Maximum Other... scaled[1] scaled[2] served[3...14] torque 2[16] 30.23 Minimum torque 2 -1600.0 … 0.0 -300.0 30.24 Maximum torque 2...
  • Page 75 Parameter listing 75 Index Name Range/List Unit Default 31 Fault functions 31.01 External event 1 source 0, 1, 3...8 Inactive (true)[1] Active Inactive DI1[3] DI2[4] DI3[5] DI4[6] DI5[7] DI6[8] (false)[0] (true)[1] 31.02 External event 1 type Fault[0], Warning[1] Fault[0] 31.03 External event 2 source See parameter 31.01 Inactive (true)[1]...
  • Page 76 76 Parameter listing Index Name Range/List Unit Default Name Name Name Overcurrent 4...9 Reserved External fault Overvoltage Selectable External fault fault Under- External fault External fault voltage AI supervi- External fault sion fault 31.13 Selectable fault 0x0000…0xffff 0x0000 31.14 Number of trials 0…5 31.15 Total trials time...
  • Page 77 Parameter listing 77 Index Name Range/List Unit Default 31.36 Aux fan fault function Fault[0], Warning[1], No Warning[1] action[2] Note: This parameter is only applicable for frames R3 or larger. 32 Supervision 32.01 Supervision status 0b0000…0b1111 0b0000 Name Name Name Supervision Supervision 6...15 Reserved...
  • Page 78 78 Parameter listing Index Name Range/List Unit Default 32.15 Supervision 2 function See parameter 32.05 Disabled[0] Supervision 1 function 32.16 Supervision 2 action No action[0], Warning[1], No action[0] Fault[2], Fault if run- ning[3] 32.17 Supervision 2 signal See parameter 32.07 Current[4] Supervision 1 signal 32.18...
  • Page 79 Parameter listing 79 Index Name Range/List Unit Default 32.40 Supervision 4 high -21474836.00 … 0.00 21474836.00 32.41 Supervision 4 hysteresis 0.00...100000.00 0.00 32.45 Supervision 5 function See parameter 32.05 Disabled[0] Supervision 1 function 32.46 Supervision 5 action No action[0], Warning[1], No action[0] Fault[2], Fault if run- ning[3]...
  • Page 80 80 Parameter listing Index Name Range/List Unit Default 34 Timed functions 34.01 Timed functions status 0b0000…0b1111 0b0000 Timed function 3 Name Name Name Name Timed Timed Timed 3...15 function function function served 34.02 Timer status 0b0000…0b1111 0b0000 Name Name Name Name Name Timer...
  • Page 81 Parameter listing 81 Index Name Range/List Unit Default Name Name Name Name Monday Friday Season Holidays Tuesday Saturday Season Work- days Wednes- Sunday Season 14...15 served Thursday Season Excep- tions 34.12 Timer 1 start time 00:00:00…23:59:59 00:00:00 34.13 Timer 1 duration 00 00:00…07 00:00 00:00:00 34.14...
  • Page 82 82 Parameter listing Index Name Range/List Unit Default 34.30 Timer 7 start time 00:00:00…23:59:59 00:00:00 34.31 Timer 7 duration 00 00:00…07 00:00 00:00:00 34.32 Timer 8 configuration See parameter 34.11 0b0111 Timer 1 configuration 34.33 Timer 8 start time 00:00:00…23:59:59 00:00:00 34.34 Timer 8 duration...
  • Page 83 Parameter listing 83 Index Name Range/List Unit Default Name Name Name Name Excep- Excep- Excep- Excep- tion 1 tion 5 tion 9 tion 13 Excep- Excep- Excep- Excep- tion 2 tion 6 tion 10 tion 14 Excep- Excep- Excep- Excep- tion 3 tion 7 tion 11...
  • Page 84 84 Parameter listing Index Name Range/List Unit Default Name Name Name Name Name Timer Timer Timer Timer 12...15 served Timer Timer Timer Timer Timer Timer Timer Timer 34.101 Timed function 2 See parameter 34.100 0b0000 Timed function 1 34.102 Timed function 3 See parameter 34.100 0b0000 Timed function 1...
  • Page 85 Parameter listing 85 Index Name Range/List Unit Default Disabled[0] 3 × Pt100 analog I/O[7] 3 × Pt1000 analog I/O[15] Estimated temperature[1] Direct temperature[11] NI 1000[16] KTY84 analog I/O KTY83 analog I/O[12] PTC analog I/O [20] 1 × Pt100 analog I/O[5] 1 ×...
  • Page 86 86 Parameter listing Index Name Range/List Unit Default Not selected[0] Motor torque[6] Speed ref ramp Process PID out[16] out[11] Motor speed used[1] DC voltage[7] Torque ref used[13] Other... Output frequency[3] Output power[8] Freq ref used[14] Motor current[4] Speed ref ramp Reserved[15] in[10] 36.02...
  • Page 87 Parameter listing 87 Index Name Range/List Unit Default Disabled[0] Warning[1] Fault[2] Warning/Fault[3] 37.04 ULC underload actions See parameter 37.03 Disabled[0] ULC overload actions 37.11 ULC speed table point 1 -30000.0… 30000.0 150.0 37.12 ULC speed table point 2 -30000.0… 30000.0 750.0 37.13 ULC speed table point 3...
  • Page 88 88 Parameter listing Index Name Range/List Unit Default 40.06 Process PID status word 0b0000…0b1111 0b0000 Name Name Name Name Name Track- Dead- Intern- active sleep band al set- mode mode active point active Set- Sleep Output 13...15 point boost limit served frozen high...
  • Page 89 Parameter listing 89 Index Name Range/List Unit Default Not selected[0] Motor potentiomet- Control panel (ref EFB ref1[19] er[8] saved)[13] Internal setpoint[2] Freq in scaled[10] Control panel (ref EFB ref2[20] copied)[14] AI1 scaled[3] AI1 percent[11] FB A ref1[15] Setpoint data stor- age[24] AI2 scaled[4] AI2 percent[12]...
  • Page 90 90 Parameter listing Index Name Range/List Unit Default 40.30 Set 1 setpoint freeze enable See parameter 40.19 Set Not selected[0] 1 internal setpoint sel1 40.31 Set 1 deviation inversion Not inverted (Ref - Not inverted (Ref Fbk)[0], Inverted (Fbk - - Fbk)[0] Ref)[1] 40.32...
  • Page 91 Parameter listing 91 Index Name Range/List Unit Default 40.53 Set 1 trimmed ref pointer 0...4 Not selected[0] Not selec- AI1 scaled[1] AI2 scaled[2] FB A ref1[3] FB A ref2[4] Other... ted[0] 40.54 Set 1 trim mix 0.000...1.000 0.000 40.55 Set 1 trim adjust -100.000...100.000 1.000 40.56...
  • Page 92 92 Parameter listing Index Name Range/List Unit Default ft 3 /m[21] User text[0] inH2O[7] I/min[14] gal/m[28] ft 3 /h[22] %[1] °C[8] I/h[15] in wg[29] m 3 /s[16] bar[2] °F[9] ppm[23] MPa[30] m 3 /m[17] kPa[3] mbar[10] inHg[24] ftWC[31] m 3 /h[11] km 3 /h[18] Pa[4] kCFM[25]...
  • Page 93 Parameter listing 93 Index Name Range/List Unit Default 41.16 Set 2 setpoint 1 source See parameter 40.16 Set AI percent[11] 1 setpoint 1 source 41.17 Set 2 setpoint 2 source See parameter 40.17 Set Not selected[0] 1 setpoint 2 source 41.18 Set 2 setpoint function See parameter 40.18 Set...
  • Page 94 94 Parameter listing Index Name Range/List Unit Default 41.38 Set 2 output freeze enable See parameter 40.38 Set Not selected[0] 1 output freeze enable 40.39 Set 1 deadband range 0.0 … 200000.0 40.40 Set 1 deadband delay 0.0 … 3600.0 41.43 Set 2 sleep level 0.0 …...
  • Page 95 Parameter listing 95 Index Name Range/List Unit Default Off[0] Follow DI2[4] DI4[6] DI6[8] Ext1/Ext2 selec- tion [2] On[1] DI1[3] DI3[5] DI5[7] Other... 41.79 Set 2 units See parameter 40.79 Set Depends °C[8] 1 units on selec- tion 41.80 Set 1 PID output min source None[0], Set2 output Set2 output min[1], other...
  • Page 96 96 Parameter listing Index Name Range/List Unit Default 44.06 Brake control enable 0...7, 18...20, 24...26 Not selected[0] Not selected[0] DI2[3] DI5[6] Timed function Supervision 2[19] 2[25] Selected[1] DI3[4] DI6[7] Timed function Supervision 3[20] 3[26] DI1[2] DI4[5] Timed function Supervision Other... [18] 1[24] 44.08...
  • Page 97 Parameter listing 97 Index Name Range/List Unit Default 45.18 CO2 conversion factor 0.000 … 65.535 tn/ MWh 0.500 45.19 Comparison power 0.0 … 10000000.0 0.00 45.21 Energy calculations reset Done[0], Reset[1] Done[0] 45.24 Hourly peak power value -3000.00 … 3000.00 0.00 45.25 Hourly peak power time...
  • Page 98 98 Parameter listing Index Name Range/List Unit Default 46.12 Filter time output frequency 2…20000 46.13 Filter time motor torque 2…20000 46.14 Filter time power 2…20000 46.21 At speed hysteresis 0.00 … 30000.00 50.00 46.22 At frequency hysteresis 0.00 … 1000.00 2.00 46.31 Above speed limit...
  • Page 99 Parameter listing 99 Index Name Range/List Unit Default 49.03 Baud rate 1...5 115.2 kbps[4] 38.4 kbps[1] 57.6 kbps[2] 86.4 kbps[3] 115.2 kbps[4] 230.4 kbps[5] 49.04 Communication loss time 0.3 … 3000.0 10.0 49.05 Communication loss action 0...3 Fault[1] No action[0] Fault[1] Last speed[2] Speed ref safe[3]...
  • Page 100 100 Parameter listing Index Name Range/List Unit Default 49.221 Basic panel home view 6 See parameter 49.19 Auto[0] Basic panel home view 50 Fieldbus adapter (FBA) 50.01 FBA A enable Disable[0], Enable[1] Disable[0] 50.02 FBA A comm loss func 0...5 No action[0] No action[0] Fault[1]...
  • Page 101 Parameter listing 101 Index Name Range/List Unit Default 50.16 FBA A status word 0.0.0.0.0...FF.FF.FF.FF 0.0.0.0 50.17 FBA A actual value 1 -2147483648 … 2147483647 50.18 FBA A actual value 2 -2147483648 … 2147483647 51 FBA A settings 51.01 FBA A type 0, 1, 32, 37, 101, 128, None[0] 132, 135, 136, 485,...
  • Page 102 102 Parameter listing Index Name Range/List Unit Default … … … … 52.12 FBA A data in12 See parameter 52.01 None FBA A data in1 53 FBA A data out 53.01 FBA A data out1 0...3, 11...13, 21 None[0] None[0] Ref1 16bit[2] CW 32bit[11] Ref2 32bit[13]...
  • Page 103 0.0…6000.0 58.17 Transmit delay 0…65535 58.18 EFB control word 0000h…FFFFh 58.19 EFB status word 0000h…FFFFh 58.25 Control profile ABB Drives[0], DCU ABB Drives[0] Profile[5] 58.26 EFB ref1 type 0…5 Speed or fre- quency[0] Speed or fre- Transpar- General[2] Torque[3] Speed[4]...
  • Page 104 104 Parameter listing Index Name Range/List Unit Default 58.28 EFB act1 type See parameter 58.26 Speed or fre- quency[0] 58.29 EFB act2 type See parameter 58.26 Speed or fre- quency[0] 58.31 EFB act1 transparent source 58.32 EFB act2 transparent source 58.33 Addressing mode Mode 0[0], Mode 1[1],...
  • Page 105 Parameter listing 105 Index Name Range/List Unit Default Name Name Name Override en- Override dir- Test mode abled ection is re- active verse Override act- Override 13...15 Reserved stop mode is active Override dir- 5...11 Reserved ection is for- ward 70.02 Override enable Off[0], On[1]...
  • Page 106 106 Parameter listing Index Name Range/List Unit Default 71 External PID 1 71.01 External PID act value -200000.00…200000.00 0.00 71.02 Feedback act value -200000.00…200000.00 0.00 71.03 Setpoint act value -200000.00…200000.00 0.00 71.04 Deviation act value -200000.00…200000.00 0.00 71.06 PID status word 0000h…FFFFh Name Name...
  • Page 107 Parameter listing 107 Index Name Range/List Unit Default 71.31 Deviation inversion See parameter 40.31 Set Not inverted (Ref 1 deviation inversion. - Fbk)[0] 71.32 Gain 0.01...100.00 1.00 71.33 Integration time 0.0...999.0 60.0 71.34 Derivation time 0.000...10.000 0.000 71.35 Derivation filter time 0.0...10.0 71.36 Output min...
  • Page 108 108 Parameter listing Index Name Range/List Unit Default Name Name Name PFC 1 run- PFC 3 run- 4...15 Reserved ning ning PFC 2 run- PFC 4 run- ning ning 76.02 PFC system status 0...9, 100...103, PFC disabled[0] 200...202, 300...302, 400, 500, 600, 700, 800, 801, PFC disabled[0] PFC inactive...
  • Page 109 Parameter listing 109 Index Name Range/List Unit Default 76.13 Pump/fan status 3 See parameter 76.11 0b0000 Pump/fan status 1 76.14 Pump/fan status 4 See parameter 76.11 0b0000 Pump/fan status 1 76.21 PFC configuration Off[0], PFC[2], SPFC[3] Off[0] 76.25 Number of motors 1…4 76.26 Min number of motors allowed...
  • Page 110 110 Parameter listing Index Name Range/List Unit Default 76.73 Autochange level 0.0…300.0 100.0 76.74 Autochange auxiliary PFC All motors[0], Aux motors Aux motors only[1] only[1] 76.81 PFC interlock 1 0...10 Available. PFC motor is available Interlocked. PFC DI2[3] DI5[6] Timed function 2[9] motor is not in use[0] Available.
  • Page 111 95.04 Control board supply Internal 24V[0], External Internal 24V[0] 24V[1] 95.15 Special HW settings 0b0000…0b1111 0b0000 Name Name Name Reserved ABB Sine fil- 2...15 Reserved 95.20 HW options word 1 0b0000…0b1111 0b0000 Name Name Name Name Supply 1…12 du/dt fil- 14…15...
  • Page 112 PID[14] SPFC[18] Jigar[30] ABB standard[1] Panel PID[15] Pharma Applica- tion[19] 3-wire[11] PFC[16] Plastic Extrusion[20] Motor potentiometer ABB standard (vec- Torque control[28] [13] tor)[17] 96.05 Macro active See parameter 96.04 ABB standard[1] Macro select 96.06 Parameter restore 0, 2, 8, 32, 62, 512,...
  • Page 113 Parameter listing 113 Index Name Range/List Unit Default 96.07 Parameter save manually Done[0], Save[1] Done[0] 96.08 Control board boot No action[0], Reboot[1] No action[0] 96.10 User set status 0...11 n/a[0] n/a[0] Faulted[3] User3 IO active[6] User2 backup[9] Loading[1] User1 IO active[4] User4 IO active[7] User3 backup[10] Saving[2]...
  • Page 114 Disable[0], Enable[1] Disable[0] 96.100 Change user pass code 10000000…99999999 96.101 Confirm user pass code 10000000…99999999 96.102 User lock functionality 0000h…FFFFh 0000h Disable ABB Disable file Disable panel Disable OEM Disable OEM access levels[0] download[2] Bluetooth[7] access level access level 1[11] 3[13] Freeze paramet- Reserved[3...6]...
  • Page 115 Parameter listing 115 Index Name Range/List Unit Default 98.03 Rr user 0.00000…0.50000 p.u. 0.00000 p.u 98.04 Lm user 0.00000…10.00000 p.u. 0.00000 p.u 98.05 SigmaL user 0.00000…1.00000 p.u. 0.00000 p.u 98.09 Rs user SI 0.00000…100.00000 0.00000 ohm 98.10 Rr user SI 0.00000…100.00000 0.00000 ohm 98.11...
  • Page 116 116 Parameter listing...
  • Page 117 ■ IEC ratings Drive Nom- Max. Output ratings Frame Type inal cur- size Nominal use Light overload Heavy-duty use ACS560 rent I 1N I max I Ld P Ld I Hd P Hd (Con- (Con- tinu- tinu- ous) ous) 3 phases U N = 400 V (380…415 V) 02A6-4 0.75...
  • Page 118 118 Technical data Drive Nom- Max. Output ratings Frame Type inal cur- size Nominal use Light overload Heavy-duty use ACS560 rent I 1N I max I Ld P Ld I Hd P Hd (Con- (Con- tinu- tinu- ous) ous) 206A-4...
  • Page 119 Technical data 119 Drive type Input uR and aR Minim- ACS560 current um short I 2 t Rated Rated Bussmann circuit current voltage designation 60269 cur- type size rent A 2 s 145A-4 1000 145.0 46500 170M3816 169A-4 1280 169.0...
  • Page 120 120 Technical data Drive type Input gG (IEC 60269) Minim- ACS560 current um short I 2 t Rated Rated ABB desig- circuit current voltage nation type 60269 cur- size rent A 2 s 246A-4 6400 246.0 920000 OFAF000H355 293A-4 7800 293.0...
  • Page 121 Technical data 121 Typical power cable sizes Drive type Frame size ACS560 Cu cable type Cu cable type AI cable AI cable type type mm 2 mm 2 AWG/kcmil AWG/kcmil 3-phase U N = 400 V (380…480 V) 02A6-4 3 × 1.5 + 1.5 03A3-4 3 ×...
  • Page 122 122 Technical data Dimensions, weights and free space requirements Frame size Dimensions and weight IP20 Weight 14.9 28.3 42.4 Standard frame size (R0-R8)
  • Page 123 Technical data 123 Symbols IP20 Height of front side Height of back side (without cable connecting box) Width Depth See the detailed dimension drawings in the drive hardware manual...
  • Page 124 124 Technical data Applicable standards The drive complies with the following standards. The compliance with the European Low Voltage Directive is verified according to standard EN 61800-5-1. EN 60204-1:2006 + Safety of machinery. Electrical equipment of machines. Part 1: AC:2010 General requirements.
  • Page 125 Technical data 125 ■ Compliance with the European Low Voltage Directive...
  • Page 126 126 Technical data The compliance with the European Low Voltage Directive has been verified according to standard EN 61800-5-1:2007. The declaration of conformity (3AXD10000549832) is available on the Internet. See section Document library on the Internet on the inside of the back cover.
  • Page 127 Diagnostics 127 Diagnostics Warning messages Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) 64FF Fault reset A fault has been reset. Event. Informative only. A2B1 Overcurrent Output current exceeded Check motor load, acceleration times, internal fault limit.
  • Page 128 128 Diagnostics Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) A490 Incorrect temper- Sensor type mismatch Check the temperature setting para- ature sensor meters. setup A491 External temperat- Measured temperature 1 Check the parameter 35.02 Measured ure 1 exceeded warning limit.
  • Page 129 Check safety circuit connections and active. parameter 95.04 Control board sup- ply. A5EA Measurement cir- Fault in drive internal tem- Contact your local ABB representat- cuit temperature perature measurement. ive. A5EB PU board power- Power unit power supply Contact your local ABB representat- fail failure.
  • Page 130 (aux code visible only on assistant control panel and drive composer) A5EF PU state feed- State feedback from output Contact your local ABB representat- back phases not matching with ive. control signals. A5F0 Charging feed- Charging feedback signal Check the feedback signal coming back missing.
  • Page 131 Diagnostics 131 Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) A6A7 System time not System time is not set. A6B0 User lock is open The user lock is open, ie. Close the user lock by entering an in- user lock configuration valid pass code in parameter 96.02...
  • Page 132 132 Diagnostics Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) A7AC I/O Module intern- Calibration data is not Replace I/O module. al error stored in the I/O module. Analog signals are not working with full accuracy.
  • Page 133 Diagnostics 133 Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) A79C BC IGBT excess Brake chopper IGBT temper- Let chopper cool down. Check ambi- temperature ature exceeded internal ent temperature, cooling fan, air flow, warning limit.
  • Page 134 134 Diagnostics Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) A8A1 RO life warning The relay has changed Change the control board or stop us- states more than the recom- ing the relay output.
  • Page 135 Diagnostics 135 Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) A8BE ULC overload User load curve: Signal has See parameter 37.03 ULC overload warning been too long over the actions.
  • Page 136 136 Diagnostics Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) 0003 Underload occurred Check the load. between speed point 37.13 ULC speed table point 3 and 37.14 ULC speed table point 4.
  • Page 137 Diagnostics 137 Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) AF90 Speed controller The speed controller autot- Check the auxiliary code (format autotuning une routine did not com- XXXX YYYY). “YYYY” indicates the plete successfully.
  • Page 138 138 Diagnostics Code Warning/Aux Cause What to do (hex) code (aux code visible only on assistant control panel and drive composer) AFEB Run enable miss- No run enable signal is re- Check setting of parameter 20.12 Run ceived. enable 1 source. Switch on the signal or check wiring of selected source.
  • Page 139 BU earth leakage Total earth leakage of invert- Check there are no power factor cor- er modules is excessive. rection capacitors or surge absorbers in motor cable. Measure insulation resistances of motor cables and motor. Contact your local ABB representat- ive.
  • Page 140 140 Diagnostics Code Fault / Aux. code Cause What to do (hex) aux code visible only on assist- ant control panel and drive com- poser)) 3130 Input phase loss Intermediate circuit DC Check input power line fuses and voltage is oscillating due to there is no input power supply imbal- missing input power line ance.
  • Page 141 Diagnostics 141 Code Fault / Aux. code Cause What to do (hex) aux code visible only on assist- ant control panel and drive com- poser)) 4210 IGBT overtemper- Estimated drive IGBT tem- Check ambient conditions, air flow ature perature is excessive. and fan, dust pick-up in heatsink fins and motor power.
  • Page 142 STO output of the module and the STO event/fault/warning is not terminal. generated. 5090 STO hardware STO hardware diagnostics Contact ABB for hardware replace- failure detected an hardware fail- ment. ure. 5091 Safe torque off Safe torque off function is Check safety circuit connections active.
  • Page 143 If the problem persists, contact ABB. 6487 Stack overflow Internal fault. Reboot the control unit. If the problem persists, contact ABB. 64A3 Application load- Application file incompatible Check the auxiliary code. See actions or corrupted. for each code below.
  • Page 144 See the drive-specific log generated by Automation Builder. 64A1 Internal file load File read error. Reboot the control unit. If the problem persists, contact ABB. 64A4 Rating ID fault Rating ID load error. Contact ABB. 64A6 Adaptive program Fault in adaptive program.
  • Page 145 6682 EFB configuration Embedded fieldbus (EFB) Reload the firmware or replace the file configuration file could not unit. Contact ABB. be read. 6683 EFB invalid para- Embedded fieldbus (EFB) Check parameter group 58 Embedded meterization parameter settings inconsist- fieldbus.
  • Page 146 Check that the acknowledgment sig- nal (if used) matches the actual status of the brake. 7100 Excitation current Excitation current feedback Contact your local ABB representat- low or missing ive. 7121 Motor stall Motor is operating in stall Check motor load, drive ratings and region.
  • Page 147 Diagnostics 147 Code Fault / Aux. code Cause What to do (hex) aux code visible only on assist- ant control panel and drive com- poser)) 7183 BR excess tem- Brake resistor temperature Stop drive. Let resistor cool down. perature has exceeded the limit. Check resistor overload protection function settings and fault limit set- tings.
  • Page 148 (hex) aux code visible only on assist- ant control panel and drive com- poser)) Other Contact your local ABB representat- ive, quoting the auxiliary code. 7510 FBA A communic- Cyclical communication Check the status of fieldbus commu- ation (Program- between drive and fieldbus nication.
  • Page 149 Diagnostics 149 Code Fault / Aux. code Cause What to do (hex) aux code visible only on assist- ant control panel and drive com- poser)) Overload occurred between Check the load. speed point 37.12 ULC speed table point 2 and 37.13 ULC speed table point 3.
  • Page 150 150 Diagnostics Code Fault / Aux. code Cause What to do (hex) aux code visible only on assist- ant control panel and drive com- poser)) 80B5 Signal supervi- Fault generated by the sig- Check the source of the fault (paramet- sion 6 nal supervision function 6.
  • Page 151 Diagnostics 151 Code Fault / Aux. code Cause What to do (hex) aux code visible only on assist- ant control panel and drive com- poser)) 1 - Maximum current limit too low B - (Asynchronous motors only) Speed dropped to zero during ID run. 2 - Maximum speed limit or calculated C - (Permanent magnet motors only).
  • Page 153 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड This guide instructs how to install and start-up the ACS560 drive of all frame sizes (R0...R8). For complete information, see the drive ACS560 standard control program firmware manual (3AXD50000044997[English]) and ACS560 drives (0.75 to 160 kW,...
  • Page 154 154 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ पावर के ब ल् स का चयन करे ं अपने ड् र ाइव के टाइप डे ज़ िगने श न ले ब ल पर दिए गए नॉमिनल करे ं ट को ले जाने के लिए स् थ ानीय नियमों के रे...
  • Page 155 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 155 ड् र ाइव इं स ् ट ाल करे ं आप ड् र ाइव इं स ् ट ाल कर सकते है ं •...
  • Page 156 156 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ पे ं च के साथ ड् र ाइव इं स ् ट ाल करना (फ़् र े म R0...R8) All drives of frames R0...R8 can be installed on a wall with screws. See the required आयाम...
  • Page 157 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 157 फ् र ै म R0 मे ं माउं ट करने वाले पे ं च का नीचे उदाहरण दे ख े ं । 6.
  • Page 158 Use a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must be more than 100 Mohm (reference value at 25 °C [77 °F]). For the insulation resistance of other motors, refer to the manufacturer’s instructions.
  • Page 159 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 159 पावर के ब लों को कने क ् ट करना ■ कने क ् श न आरे ख विकल् प ों के लिए, हार् ड वे य र मै न ् य ु अ ल दे ख े ं । एक...
  • Page 160 160 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ कने क ् श न प् र क् र िया: फ् र े म R0…R2 If the drive is connected on an IT (ungrounded) system, make sure that the EMC filter and Varistor (VAR) is disconnected.
  • Page 161 Motor cable Motor cable 2. Prepare the ends of the cable as illustrated in the figure. Two different motor cable HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 161 types are shown in the figures (2a.and 2b). 2.
  • Page 162 162 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 80 Electrical installation 5. इनपु ट पावर के ब ल को निम् न अनु स ार कने क ् ट करे ं : 5.
  • Page 163 N·m lbf·ft N·m lbf·ft L1. L2. L3 0.5…0.6 1.2…1.5 0.9…1.1 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 163 6. Connect the braking resistor cable as the motor cable in step 4. 7.
  • Page 164 78 Electrical installation 164 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 78 Electrical installation Connection procedure, frames R0…R2 Connection procedure, frames R0…R2 ■ कने क ् श न प् र क् र िया, फ् र े म R3 ... R4 1.
  • Page 165 Electrical installation 83 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 165 3. Connect the motor cable as follows: If the power cable is temporarily removed from the grounding shelf, connect the •...
  • Page 166 166 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 84 Electrical installation 5. इनपु ट पावर के ब ल को निम् न अनु स ार कने क ् ट करे ं : •...
  • Page 167 6. For R3, connect cable by the motor cable method mentioned instep 3. HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 167 7. Ground the shield 360 degrees (7a). 8. Connect the twisted shield to the grounding terminal (7b). 9.
  • Page 168 WARNING! If the drive will be connected on an IT (unground 168 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड make sure you have disconnected the EMC filter and ground-t See page 71.
  • Page 169 Electrical installation 87 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 169 Motor cable मोटर के ब ल Electrical installation 87 6. Cut an adequate hole into the rubber grommet. Slide the grommet onto the cable. 6.
  • Page 170 • If you connect only one conductor to the connector, we recommend that you put it • If you connect only one conductor to the connector, we recommend that you put it under the upper pressure plate. under the upper pressure plate. 170 HI -त्...
  • Page 171 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 171 Electrical installation 89 Electrical installation 89 • कने क ् ट र को वापिस टर् म िनल पोस् ट पर रखे ं । कॉम् ब ी पे ं च को डाले ं , और हाथ से कम से कम दो बार Terminals L1, L2 and L3 Terminals L1, L2 and L3 घु...
  • Page 172 फर् म वे य र मै न ु अ ल मे ं वर् ण ित के ब ल् स को कने क ् ट करे ं । ABB मानक मै क ् र ो के नीचे डिफ़ ॉ ल् ट...
  • Page 173 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 173 डिफ़ ॉ ल् ट I/O कने क ् श न (ABB स् ट ॅ ं ड र् ड मै क ् र ो) ■...
  • Page 174 174 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड टिप् प णी आरे ख मे ं सू च ीबद् ध पै र ामीटर की जानकारी के लिए, दे ख े ं पै...
  • Page 175 BIO-01 also) समर् थ ित फ़ ी ल् ड बस मॉड् य ू ल के बारे मे ं जानकारी के लिए, ACS560 उत् प ाद कै ट लॉग दे ख े ं । For more information on optional modules, see hardware manual.
  • Page 176 2. मौजू द ा RIIO-01 मॉड् य ू ल निकाले ं । निकाल दे न ा, टिप् प णी RIIO-01 मॉड् य ू ल मानक ACS560-01 R0 ... R2 ड् र ाइव मे ं डिफ़ ॉ ल् ट रू प से उपलब् ध है ।...
  • Page 177 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 177 132 Electrical installation c. मॉड् य ू ल को खीं च े ं और इसे हटा दे ं । Installing option modules टिप्...
  • Page 178 178 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड IT (अनग् र ाउं ड ड) और कोने मे ं ग् र ाउं ड ड TN सिस् ट मों की अनु क ू ल ता की जां च करना...
  • Page 179 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 179 फ् र े म के EMC फ़ ि ल् ट र Ground- to- सममित आधार पर कोने पर ग् र ाउं ड ड TN IT सिस्...
  • Page 180 180 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड Electrical installation 103 कवरों को पु न र् स ् थ ापित करना Reinstalling covers ■ कवरों को पु न र् स ् थ ापित करना, फ् र े म आकार R0…R2 Reinstalling cover, frames size R0…R2 1.
  • Page 181 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 181 ACS560R0-R8 QIG.book Page 20 Wednesday, May 30, 2018 3:45 PM ■ साइड प् ल े ट ् स और कवरों को पु न र् स ् थ ापित करना, फ् र े म आकार R5…R8 ACS560R0-R8 QIG.book Page 20 Wednesday, May 30, 2018 3:45 PM 20 EN - Quick installation and start-up guide 1.
  • Page 182 R6...R8 1. Install the side plates (1a) of the cable box. Tighten the retaining screws (1b) with 182 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड a screw driver. 2. Slide the cover (2a) of the cable box on the module from below until the cover snaps into place.
  • Page 183 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 183 ■ नियं त ् र ण पै न ल का प् र योग क् ल िप - ड् र ाइव से पै न ल हटाने के लिए क् ल िप को नीचे की...
  • Page 184 184 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ डिस् प ् ल े नियं त ् र ण पै न ल डिस् प ् ल े निम् न तत् व दिखाता है : नियं...
  • Page 185 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 185 सबमे न ू सबमे न ू आइटम आपको से ट िं ग बदलने और कार् य वाहित से ट करने की अनु म ति दे त ी है ं । कु छ सबमे न ू मे ं मे न ू और/या...
  • Page 186 186 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 1) स् व चालित - डिफ़ ॉ ल् ट प् र ारं भ 2) लगातार - निरं त र प् र ी- मोड।...
  • Page 187 दे ख े ं । → चु न ा हु आ मै क ् र ो ABB स् ट ै ं ड र् ड (2 -तार) है । 1) ABB मानक (2-तार) - 2) 3-वायर मै क ् र ो - उपयु क ् त जब...
  • Page 188 188 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 1) DI - डिजिटल इनपु ट 5) AI1 और AI2 मान DI1...DI6 6) AO1 और AO2 मान 2) AI - एनालॉग इनपु ट AI1...AI2 3) RO - रिले...
  • Page 189 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 189 डायग् न ोस् ट िक सक् र िय फ़ ॉ ल् ट और चे त ावनियाँ और उन् ह े ं कै स े ठीक और रिसे ट किया जाए यह दिखाता है । फ़ ॉ ल् ट और चे त ावनी कोड...
  • Page 190 190 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 1) पू ण र् मानदं ड सू च ी 2) सं श ोधित मानदं ड सू च ी। पू र ् ण मानदं ड सू च ी शािमल...
  • Page 191 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 191 गति या फ् र िक् व े ं स ी रे फ रे ं स से ट करना विकल् प मे न ू मे ं , तीर...
  • Page 192 192 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड चे त ावनी सं द े श डिस् प ् ल े समस् य ा का पता चलने पर चे त ावनी सं द े श कोड दिखाता है । चे...
  • Page 193 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 193 ईन् प ु ट / आउटपु ट और फील् ड बस मॉड् य ू ल की ऑटो कॉन् फ ़ ि गरे श न आप...
  • Page 194 194 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ड् र ाइव और पै न ल सं च ार विफलता ड् र ाइव सं च ार विफलता के दौरान पै न ल कमां ड के प् र ति उत् त र नहीं दे त ी है । ड्...
  • Page 195 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 195...
  • Page 196 196 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड...
  • Page 197 पै र ामीटर सू च ी 197 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 01 वास् त विक मू ल ् य 01.01 मोटर गति प् र यु क ् त -30000.00…30000.00 01.02 अनु...
  • Page 198 198 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 01.51 पिछला घं ट ा kWh 0.00…100000.00 01.52 वर् त मान दिन kWh 0.00…100000.00 01.53 पिछला दिन kWh 0.00…100000.00 01.54 सं च यी इन् व र् ट र ऊर् ज ा -200000000.0…200000000.0 01.55 इनवर्...
  • Page 199 पै र ामीटर सू च ी 199 सू च ी नाम रे ं ज यू न िट चू क 04.01 ट् र िपिं ग फॉल् ट 0x0000...0xffff 0x0000 04.02 सक् र िय फॉल् ट 2 0x0000...0xffff 0x0000 04.03 सक् र िय फॉल् ट 3 0x0000...0xffff 0x0000 04.06...
  • Page 200 200 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम कोई भी अधिक करं ट का आरक् ष ित चे त ावनी या फॉल् ट फॉल् ट कोई भी आरक्...
  • Page 201 पै र ामीटर सू च ी 201 सू च ी नाम रे ं ज यू न िट चू क 06 कं ट ् र ोल और स् ट े ट स शब् द 06.01 मु ख ् य कं ट ् र ोल शब् द 0x0000...0xffff 0x0000 नाम...
  • Page 202 202 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 06.16 ड् र ाइव स् ट े ट स शब् द 1 0b0000...0b1111 0b0000 नाम नाम नाम सक् ष म प् र ारं भ किया Ext1 सक्...
  • Page 203 पै र ामीटर सू च ी 203 सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम चलाने के लिए आरक् ष ित आपातकालीन तै य ार नहीं Off2 कं ट ् र ोल स् थ ान आपातकालीन...
  • Page 204 204 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 06.29 MSW बिट 10 चयन गलत[0].सही[1], सीमा से सीमा से ऊपर[2] ऊपर[2], Other... 06.30 MSW बिट 11 चयन गलत[0], सही[1], बाहरी बाहरी...
  • Page 205 पै र ामीटर सू च ी 205 सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम नाम 6…15 आरक् ष ित 10.02 DI विलं ब ित स् थ िति पै र ामीटर दे ख े ं 10.01 DI 0b0000 स्...
  • Page 206 206 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 10.24 RO1 सोर् स 0...2, 4...24, 27...35, चलाने के लिए 45...48 तै य ार[2] सक् र िय नहीं [ 0] सीमा से ऊपर[12] Ext2 सक्...
  • Page 207 पै र ामीटर सू च ी 207 सू च ी नाम रे ं ज यू न िट चू क 10.102 RO2 ॉगल काउं ट र 0...4294967000 10.103 RO2 ॉगल काउं ट र 0...4294967000 11 स् ट ै ण ् ड र् ड DIO, FI, FO 11.21 DI5 कॉन्...
  • Page 208 208 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 12.13 AI1 फोर् स ् ड मान 0.000…11.000 12.15 AI1 यू न िट चयन V[2], mA[10] V[2] 12.16 AI1 फ़िल् ट र टाइम 0.000 …...
  • Page 209 पै र ामीटर सू च ी 209 सू च ी नाम रे ं ज यू न िट चू क शू न ् य [0] DC वोल् ट े ज [7] एब् स लू ट मोटर गति AO1 डे ट ा स् ट ोरे ज [37] प्...
  • Page 210 210 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 19.01 वास् त विक ऑपरे श न मोड 1, 2, 10, 20 स् क े ल र (Hz)[10] शू न ् य [1] न्...
  • Page 211 पै र ामीटर सू च ी 211 सू च ी नाम रे ं ज यू न िट चू क हमे श ा बं द [0] DI2[3] DI5[6] समयबद् ध फं क ् श न सु प रविज़न 2[25] 2[19] हमे श ा बने रहे ं [ 1] DI3[4] DI6[7] समयबद्...
  • Page 212 212 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क चयनित नहीं [ 0] DI3[4] समयबद् ध फं क ् श न सु प रविज़न 2[25] अन् य ... [18] चयनित[1] DI4[5] समयबद्...
  • Page 213 पै र ामीटर सू च ी 213 सू च ी नाम रे ं ज यू न िट चू क 21.08 DC करं ट कं ट ् र ोल 0b0000…0b1111 0b0000 नाम नाम नाम DC होल् ड चु म ् ब कीकरण के 2...15 आरक्...
  • Page 214 214 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 21.32 गति पू र ित स् ट ॉप सीमा 0…100 21.34 ऑटो रिस् ट ार् ट फोर् स करे ं अक् ष म करे ं [ 0], सक् ष म करे ं [ 1] अक्...
  • Page 215 पै र ामीटर सू च ी 215 सू च ी नाम रे ं ज यू न िट चू क 22.22 स् थ िर गति sel1 0...7, 18...20, 24...26 DI3[4] हमे श ा बं द [0] DI2[3] DI5[6] समयबद् ध फं क ् श न सु...
  • Page 216 216 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 22.71 मोटर पोटे न ् श िओमीटर फं क ् श न 0...3 अक् ष म[0] अक् ष म[0] तै य ार किया गया (हमे श ा पु न : चालू करे ं ) [2] सक्...
  • Page 217 पै र ामीटर सू च ी 217 सू च ी नाम रे ं ज यू न िट चू क 23.13 डीएक् स े ल े र े श न समय 1 0.000 …1800.000 20.000 23.14 एक् स े ल रे श न समय 2 0.000 …1800.000 60.000 23.15...
  • Page 218 218 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 25.53 टॉर् क प् र ॉप रे फ रे ं स -30000.0 … 30000.0 25.54 टॉर् क इं ट ीग् र ल रे फ रे ं स -30000.0 …...
  • Page 219 पै र ामीटर सू च ी 219 सू च ी नाम रे ं ज यू न िट चू क 26.19 टॉर् क रै म ् प डाउन टाइम 0.000…60.000 0.000 26.20 Torque reversal 0...13 हमे श ा बं द [0] हमे...
  • Page 220 220 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क शू न ् य [0] FB A रे फ रे ं स 1[4] EFB रे फ रे ं स 2[9] फ् र ीक् व े ं स ी अन्...
  • Page 221 पै र ामीटर सू च ी 221 सू च ी नाम रे ं ज यू न िट चू क 28.24 स् थ िर फ् र िक् व े ं स ी sel3 पै र ामीटर दे ख े ं 28.22 स् थ िर हमे...
  • Page 222 222 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 28.74 फ् र िक् व े ं स ी एक् स े ल रे श न समय 2 0.000 …1800.000 60.000 28.75 फ्...
  • Page 223 पै र ामीटर सू च ी 223 सू च ी नाम रे ं ज यू न िट चू क 30.02 टॉर् क सीमा स् ट े ट स 0b0000…0b1111 0b0000 नाम नाम नाम नाम कम आतं र िक थर् म ल IGBT वोल्...
  • Page 224 224 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क शू न ् य [0] आरक् ष ित PID[15] न् य ू न तम अन् य ... स् क े ल ् ड [1] स्...
  • Page 225 पै र ामीटर सू च ी 225 सू च ी नाम रे ं ज यू न िट चू क 31.03 बाहरी घटना 2 स् र ोत पै र ामीटर दे ख े ं 31.01 बाहरी निष् क ् र िय (सही)[1] इवे...
  • Page 226 226 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 31.19 मोटर फे ज़ हानि कोई कार् य वाही नहीं [ 0], फॉल् ट [1] फॉल् ट [1] 31.22 STO सं क े त रन/स् ट ॉप 0...5 फॉल्...
  • Page 227 पै र ामीटर सू च ी 227 सू च ी नाम रे ं ज यू न िट चू क 32.05 सु प रविज़न 1 फं क ् श न 0...7 अक् ष म[0] अक् ष म[0] उच् च [2] एब् स लू ट उच् च [4] एब्...
  • Page 228 228 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 32.26 सु प रविज़न 3 एक् श न कोई कार् य वाही नहीं [ 0], कोई कार् य वाही चे त ावनी[1],फॉल् ट [2], फॉल् ट नहीं...
  • Page 229 पै र ामीटर सू च ी 229 सू च ी नाम रे ं ज यू न िट चू क 32.55 सु प रविज़न 6 फं क ् श न पै र ामीटर दे ख े ं 32.05 अक् ष म[0] सु...
  • Page 230 230 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम मौसम 1 मौसम 4 अपवाद छु ट ् ट ी मौसम 2 4...9 आरक् ष ित 12...15 आरक् ष ित मौसम...
  • Page 231 पै र ामीटर सू च ी 231 सू च ी नाम रे ं ज यू न िट चू क 34.24 टाइमर 5 आरं भ समय 00:00:00…23:59:59 00:00:00 34.25 टाइमर 5 अवधि 00 00:00…07 00:00 00:00:00 34.26 टाइमर 6 कॉन् फ़ िगरे श न पै...
  • Page 232 232 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 34.63 मौसम 4 आरं भ तिथि 34.70 सक् र िय अपवादों की सं ख ् य ा 0…16 34.71 अपवाद के प् र कार 0b0000…0b1111 0b0000 नाम...
  • Page 233 पै र ामीटर सू च ी 233 सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम नाम नाम टाइमर टाइमर टाइमर टाइमर 12...15 आरक् ष ित Timer टाइमर टाइमर टाइमर टाइमर टाइमर टाइमर टाइमर 34.101 समयबद्...
  • Page 234 234 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क अक् ष म[0] 3 × Pt100 analog I/O[7] 3 × Pt1000 analog I/O[15] अनु म ानित तापमान[1] सीधा तापमान[11] NI 1000[16] KTY84 analog I/O KTY83 analog I/O[12] PTC analog I/O [20]...
  • Page 235 पै र ामीटर सू च ी 235 सू च ी नाम रे ं ज यू न िट चू क चयनित नहीं [ 0] मोटर टॉर् क [6] गति रे फ रे ं स रै म ् प प् र ोसे स PID आउट[16] आउट[11] मोटर...
  • Page 236 236 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क अक् ष म[0] चे त ावनी[1] फॉल् ट [2] चे त ावनी/फॉल् ट [3] 37.04 ULC निम् न लोड एक् श न पै...
  • Page 237 पै र ामीटर सू च ी 237 सू च ी नाम रे ं ज यू न िट चू क 40.06 प् र ोसे स PID स् ट े ट स शब् द 0b0000…0b1111 0b0000 नाम नाम नाम नाम नाम ट् र ै क िं ग डे...
  • Page 238 238 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क चयनित नहीं [ 0] मोटर पोटे ं श ियोमीटर[8] कं ट ् र ोल पै न ल (रे फ रे ं स EFB रे...
  • Page 239 पै र ामीटर सू च ी 239 सू च ी नाम रे ं ज यू न िट चू क 40.30 से ट 1 से ट प् व ॉइं ट फ् र ीज़ सक् ष म पै र ामीटर दे ख े ं 40.19 से ट 1 चयनित...
  • Page 240 240 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 40.53 Set 1 trimmed ref pointer 0...4 चयनित नहीं [ 0] चयनित नहीं [ 0] AI1 स् क े ल ् ड [1] AI2 स्...
  • Page 241 पै र ामीटर सू च ी 241 सू च ी नाम रे ं ज यू न िट चू क ft 3 /m[21] उपयोगकर् त ा पाठ inH2O[7] I/min[14] gal/m[28] ft 3 /h[22] %[1] °C[8] I/h[15] in wg[29] m 3 /s[16] bar[2] °F[9] ppm[23]...
  • Page 242 242 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 41.15 से ट 2 आउटपु ट स् क े ल िं ग -200000.00 … 0.00 200000.00 41.16 से ट 2 से ट प् व ॉइं ट 1 सोर् स पै...
  • Page 243 पै र ामीटर सू च ी 243 सू च ी नाम रे ं ज यू न िट चू क 41.36 से ट 2 आउटपु ट न् य ू न तम -200000.00 … 0.00 200000.00 41.37 से ट 2 आउटपु ट अधिकतम -200000.00 …...
  • Page 244 244 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 41.60 से ट 2 पीआईडी सक् र ियण स् र ोत 0...8 On[1] बं द [0] Ext1/Ext2 चयन DI2[4] DI4[6] DI6[8] का...
  • Page 245 पै र ामीटर सू च ी 245 सू च ी नाम रे ं ज यू न िट चू क 44.06 ब् र े क नियं त ् र ण सक् ष म 0...7, 18...20, 24...26 चयनित नहीं [ 0] चयनित नहीं [ 0] DI2[3] DI5[6] समयबद्...
  • Page 246 246 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 45.18 CO2 कन् व र् ज़ न फै क ् ट र 0.000 … 65.535 tn/ MWh 0.500 45.19 तु ल नात् म क पॉवर 0.0 …...
  • Page 247 पै र ामीटर सू च ी 247 सू च ी नाम रे ं ज यू न िट चू क 46.12 फ़िल् ट र समय आउटपु ट फ् र िक् व े ं स ी 2…20000 46.13 फ़ ि ल् ट र समय मोटर टोक़ 2…20000 46.14 फ़िल्...
  • Page 248 248 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 49.03 बॉड दर 1...5 115.2 kbps[4] 38.4 kbps[1] 57.6 kbps[2] 86.4 kbps[3] 115.2 kbps[4] 230.4 kbps[5] 49.04 सं च ार हानि समय 0.3 …...
  • Page 249 पै र ामीटर सू च ी 249 सू च ी नाम रे ं ज यू न िट चू क 50.02 FBA A सं च ार हानि फं क ् श न 0...5 कोई कार् य वाही नहीं [ 0] कोई कार् य वाही फॉल्...
  • Page 250 250 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क कोई नहीं [ 0] DeviceNet[37] PROFInet IO[132] RS-485 comm[485] PROFIBUS-DP[1] ControlNet[101] EtherCAT[135] BACnet[47808] CANopen[32] Ethernet[128] ETH Pwrlink[136] 51.02 FBA A Par2 0…65535 …...
  • Page 251 पै र ामीटर सू च ी 251 सू च ी नाम रे ं ज यू न िट चू क कोई नहीं [ 0] रे फ रे ं स 1 16बिट[2] CW 32बिट[11] रे फ रे ं स 1 अन् य ... 32बिट[13] CW 16बिट[1] रे...
  • Page 252 EFB स् ट े ट स शब् द 0000h…FFFFh 58.25 कं ट ् र ोल प् र ोफाइल ABB ड् र ाइव् स [0], DCU ABB ड् र ाइव् स [0] प् र ोफाइल[5] 58.26 EFB रे फ रे ं स 1 टाइप...
  • Page 253 पै र ामीटर सू च ी 253 सू च ी नाम रे ं ज यू न िट चू क कोई नहीं [ 0] SW 16बिट[4] रे फ रे ं स 1 Act2 32बिट[16] AO1 डे ट ा 32बिट[12] स् ट ोरे ज [32] CW 16बिट[1] Act1 16बिट[5] रे...
  • Page 254 254 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क उपयोग नहीं DI2[3] DI5[6] -DI2[9] -DI5[12] किया[0] Used[1] DI3[4] DI6[7] -DI3[10] -DI6[13] DI1[2] DI4[5] -DI1[8] -DI4[11] अन् य ... 70.04 रे फ रे ं स सोर् स ओवरराइड करे ं 0...6 फ्...
  • Page 255 पै र ामीटर सू च ी 255 सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम PID सक् र िय 3...6 आरक् ष ित आरक् ष ित आरक् ष ित आउटपु ट सीमा 10...11 डे...
  • Page 256 256 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 71.36 आउटपु ट न् य ू न तम -200000.00... 200000.00 -200000.00 71.37 आउटपु ट अधिकतम -200000.00... 200000.00 200000.00 71.38 आउटपु ट फ् र ीज़ सक् ष म पै...
  • Page 257 पै र ामीटर सू च ी 257 सू च ी नाम रे ं ज यू न िट चू क 76.02 PFC सिस् ट म स् ट े ट स 0...9, 100...103, PFC अक् ष म[0] 200...202, 300...302, 400, 500, 600, 700, 800, 801, PFC अक्...
  • Page 258 258 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 76.26 अनु म ति प् र ाप् त मोटर की न् य ू न तम 0…4 सं ख ् य ा 76.27 अनु...
  • Page 259 पै र ामीटर सू च ी 259 सू च ी नाम रे ं ज यू न िट चू क इं ट रलॉक। PFC मोटर DI2[3] DI5[6] समयबद् ध फं क ् श न 2[9] उपयोग मे ं नहीं है [ 0] उपलब्...
  • Page 260 24V[1] 95.15 विशे ष HW से ट िं ग 0b0000…0b1111 0b0000 नाम नाम नाम आरक् ष ित ABB साइन 2...15 आरक् ष ित फिल् ट र 95.20 हार् ड वे य र विकल् प शब् द 1 0b0000…0b1111 0b0000 नाम...
  • Page 261 मै क ् र ो चयन पू र ा किया[0] पू र ा किया[0] PID[14] SPFC[18] Jigar[30] ABB मानक[1] पै न ल/PID[15] फार् म ा अनु प ् र योग[19] 3-wire[11] PFC[16] प् ल ास् ट िक उभार[20] मोटर पोटे ं श ियोमीटर[13] ABB मानक...
  • Page 262 262 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क लागू / नहीं [ 0] फॉल् ट े ड [3] उपयोगकर् त ा 3 I/O उपयोगकर् त ा 2 सक् र िय [4] बै...
  • Page 263 96.102 यू ज़ र लॉक व् य वहारिकता 0000h…FFFFh 0000h ABB एक् स े स स् त र फ़ाइल डाउनलोड पै न ल ब् ल ू ट ू थ OEM एक् स े स स् त र OEM एक् स े स स् त र...
  • Page 264 264 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 98.05 SigmaL यू ज़ र 0.00000…1.00000 p.u. 0.00000 p.u 98.09 Rs यू ज़ र SI 0.00000…100.00000 0.00000 ohm 98.10 Rr यू ज़ र SI 0.00000…100.00000 0.00000 ohm 98.11...
  • Page 265 प् र कार करं ट आकार सां क े त िक प् र योग लाइट ओवरलोड है व ी-ड् य ू ट ी प् र योग ACS560 उपयोग I 1N I max I आ ई ए ल ड ी P Ld...
  • Page 266 प् र कार करं ट आकार सां क े त िक प् र योग लाइट ओवरलोड है व ी-ड् य ू ट ी प् र योग ACS560 उपयोग I 1N I max I आ ई ए ल ड ी P Ld...
  • Page 267 तकनीकी डे ट ा 267 ड् र ाइव प् र कार इनपु ट करं ट uR और aR न् य ू न तम ACS560 शॉर् ट I 2 t रे ट ड करं ट रे ट ड बसमै न सर् क िट...
  • Page 268 न् य ू न तम प् र कार शॉर् ट I 2 t रे ट ड करं ट रे ट ड वोल् ट े ज IEC 60269 ACS560- सर् क िट निर् ध ारण आकार वर् त मान प् र कार A 2 s 3-फे...
  • Page 269 आदर् श पावर के ब ल के आकार ड् र ाइव प् र कार फ् र े म आकार ACS560 Cu के ब ल प् र कार Cu के ब ल प् र कार AI के ब ल प् र कार...
  • Page 270 270 तकनीकी डे ट ा आयाम, वजन और खाली जगह की आवश् य कताएं फ् र े म आकार आयाम और वजन IP20 वजन 14.9 28.3 42.4 मानक फ् र े म आकार (R0-R8)
  • Page 271 तकनीकी डे ट ा 271 चिह् न IP20 अगले हिस् स े की ऊँ च ाई पिछले हिस् स े की ऊँ च ाई (के ब ल को जोड़ न े वाले बॉक् स के बिना) चौड़ ा ई गहराई ड्...
  • Page 272 272 तकनीकी डे ट ा लागू मानक ड् र ाइव निम् न लिखित मानकों का पालन करती है । यू र ोपीय कम वोल् ट े ज निदे श कों के साथ अनु प ालन की मानक EN 61800-5-1 के अनु स ार पु ष ् ट ि की जाती है । मशीन...
  • Page 273 तकनीकी डे ट ा 273 ■ यू र ोपीय कम वोल् ट े ज निदे श का अनु प ालन...
  • Page 274 274 तकनीकी डे ट ा The compliance with the European Low Voltage Directive has been verified according to standard EN 61800-5-1:2007. The declaration of conformity (3AXD10000549832) is available on the Internet. See section Document library on the Internet on the inside of the back cover.
  • Page 275 डायग् न ोस् ट िक 275 डायग् न ोस् ट िक चे त ावनी सं द े श कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक्...
  • Page 276 276 डायग् न ोस् ट िक कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 277 A5EA मे ज़ रमे ं ट सर् क िट ड् र ाइव आतं र िक तापमान माप मे ं अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । तापमान फॉल् ट । A5EB PU बोर्...
  • Page 278 A5F1 अनावश् य क माप डु प ् ल िके ट माप सीमा से परे है ं । अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । A5F2 अधिक तापमान hw अत् य धिक हार् ड वे य र तापमान।...
  • Page 279 डायग् न ोस् ट िक 279 कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 280 280 डायग् न ोस् ट िक कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 281 डायग् न ोस् ट िक 281 कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 282 282 डायग् न ोस् ट िक कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 283 डायग् न ोस् ट िक 283 कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 284 284 डायग् न ोस् ट िक कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 285 डायग् न ोस् ट िक 285 कोड चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (hex) (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई दे...
  • Page 286 मोटर के ब ल् स और मोटर के इन् स ु ल े श न प् र तिरोध को मापे ं । अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । 3130 इनपु ट फे ज़ हानि...
  • Page 287 डायग् न ोस् ट िक 287 कोड Fault / Aux. code कारण क् य ा करे ं (hex) aux code visible only on assistant control panel and drive composer)) 3181 वायरिं ग या अर् थ गलत इनपु ट पॉवर और मोटर इनपु...
  • Page 288 STO हार् ड वे य र मे ं STO हार् ड वे य र डायग् न ोस् ट िक से हार् ड वे य र बदलने के लिए ABB से सं प र् क करे ं । फॉल् ट हार् ड वे य र विफलता का पता चला...
  • Page 289 5096 अधिक तापमान hw अत् य धिक हार् ड वे य र तापमान। अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । 5098 I/O सं च ार हानि मानक I / O के लिए सं च ार...
  • Page 290 आं त रिक गलती नियं त ् र ण यू न िट रीबू ट करे ं । यदि समस् य ा बनी रहती है , तो ABB प् र तिनिधि से सं प र् क करे ं । 64A3 एप् ल िके श न लोड हो...
  • Page 291 कर नियं त ् र ण यू न िट रीबू ट करे ं । 96.08 कं ट ् र ोल किया जा सकता है । बोर् ड बू ट यदि समस् य ा बनी रहती है , तो ABB प् र तिनिधि से सं प र् क करे ं ।...
  • Page 292 आं त रिक गलती फॉल् ट रिसे ट करे ं । यदि फॉल् ट बनी रहती है , तो ओवरफ् ल ो ABB प् र तिनिधि से सं प र् क करे ं । 6885 टे क ् स ् ट फ़ाइल...
  • Page 293 उत् त े ज ना वर् त मान उत् त े ज ना वर् त मान प् र तिक् र िया अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । कम या गायब है...
  • Page 294 294 डायग् न ोस् ट िक कोड Fault / Aux. code कारण क् य ा करे ं (hex) aux code visible only on assistant control panel and drive composer)) 73B0 इमरजे ं स ी रै म ् प इमरजे ं स ी स् ट ॉप अपे क ् ष ित समय पू...
  • Page 295 डायग् न ोस् ट िक 295 कोड Fault / Aux. code कारण क् य ा करे ं (hex) aux code visible only on assistant control panel and drive composer)) स् प ीड पॉइं ट 37.14 ULC स् प ीड लोड की जां च करे ं । टे...
  • Page 296 296 डायग् न ोस् ट िक कोड Fault / Aux. code कारण क् य ा करे ं (hex) aux code visible only on assistant control panel and drive composer)) 80B2 सु प रविज़न 3 सिग् न ल सिग् न ल सु प रविज़ न फं क ् श न 3 फॉल्...
  • Page 297 डायग् न ोस् ट िक 297 कोड Fault / Aux. code कारण क् य ा करे ं (hex) aux code visible only on assistant control panel and drive composer)) FF61 ID रन मोटर पहचान रन सफलतापू र ् व क मानदं...
  • Page 299 Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 300 3AXD50000042620G © 2020 ABB Oy. All rights reserved. Specifications subject to change without notice.