Siemens FC20 Operation

Siemens FC20 Operation

Fire control panel & fire terminal

Advertisement

Quick Links

Operation (short) MP 2.1
FC20xx Fire control panel
FT2040 Fire terminal
ALARM Procedure
with Alarm Verification Concept (AVC), suggested possible procedure, subject to local requirements
Fx20xx
Fire brigade in
001 ALARM
Autom. FIRE ALARM
Main Building
Ground Floor
ALARM
1/01 Meeting Room
Commands
FAULT
ISOLATION
DETECTOR TEST
System
On
Fault
Action / Condition
1.
Press <Acknowledge> on the PMI before allowed
response time (t1) runs out (Password required)
2.
Read top line on display:
"Fire brigade in" "mm:ss"
3.
Read fire location on display.
Go to the fire location.
4.
5.
Decide: MAJOR INCIDENT or minor incident.
6.
MAJOR INCIDENT:
or actuate nearest manual call point.
Read top line on display:
● "Remote transmission activated"
● "Fire brigade called !"
● "Call fire brigade !"
Remote transmission switched off / not available or
defective.
R
Minor incident:
(Password required)
During the alarm, optionally press
7.
<Sounders Evacuate> on the PMI.
(Password required)
Document ID: 009906_d_en_GB
2.
00:02:51
Zone no.2
00:02:51
3.
Execute
Switch to
More
Standard view
Options
Scroll alarms
Remote alarm
Active
Fault / Off
Sounders
7.
Active Evacuate
Fault / Off
Control function
Active
Fault / Of
A
Press <Alarm delay off>
Press <Reset>.
ALARM-Procedure
Switching off detector zones / detectors
Switching on detector zones / detectors
Procedure in case of Fault
~
1
h i
001
g
4
s
q r
p
7
*
Silence buzzer
1.
Acknowledge
R
Reset
A
Alarm delay off
Premises manned
Consequence / Status
Buzzer is turned off, alarm is acknowledged.
Countdown t2 for the investigation of the cause of alarm starts.
Remaining time is shown as countdown before building
evacuation and Fire Brigade call.
Information on the cause of ALARM,
damage limitation.
If required, initiation of suitable emergency measures.
The remote transmission for fire alarm is activated
immediately.
● Transmission to fire brigade not confirmed yet.
● ALARM transmitted to fire brigade.
● Fire brigade must be called by phone!
No automatic transmission to fire brigade.
Dial the following no.:
Fire detection system is in normal condition unless another event
occurs.
It may be necessary to vent the room before resetting is possible.
Elements that cannot be reset can be switched off temporarily.
Deactivates the acoustic alarm devices during the alarm.
(Reactivation is possible by pressing the button again)
Edition: 05.2009
b c
e f
d
a
2
3
n o
k l
j
m
5
6
z
v
x y
u
t
w
8
9
0
#
C
ok
6.
5
Decide
. 4.
Go to fire location
Page 1
Page 2
Page 4
Page 4
1 of 4

Advertisement

loading

Summary of Contents for Siemens FC20

  • Page 1 Operation (short) MP 2.1 ALARM-Procedure Page 1 Switching off detector zones / detectors Page 2 FC20xx Fire control panel Switching on detector zones / detectors Page 4 FT2040 Fire terminal Procedure in case of Fault Page 4 ALARM Procedure with Alarm Verification Concept (AVC), suggested possible procedure, subject to local requirements Fx20xx Fire brigade in 00:02:51...
  • Page 2 Switching off detector zones / detectors The following example represents a possible operation sequence: DANGER System parts that have been switched off make it impossible to detect fires or faults! Fire may spread unhindered. ⇒ The area that has been switched off must be manually supervised. ⇒...
  • Page 3 Switching off a detector (Password required) Step Result ⇒ Main menu Access level 2.1 Press the button to open the main menu. Exit with <C> (Password required) Message summary Element search Functions Event memory Favorites Logout / change level Topology Settings / administration Function Function...
  • Page 4: Procedure In Case Of Fault

    Switching on detector zones / detectors (Password required) ⇒ When there is no event with a higher priority, isolations (switched off) are directly indicated on the display. You may then directly proceed with Step 3 below. ⇒ When all zones within a section (a zone is a detector in this system’s terminology) are turned off, the section is additionally indicated as switched off.
  • Page 5: Alarm Procedure

    Operation (short) MP 2.1 ALARM-Procedure Page 1 Switching off detector zones / detectors Page 2 FC20xx Fire control panel Switching on detector zones / detectors Page 4 FT2040 Fire terminal Procedure in case of Fault Page 4 ALARM Procedure no Alarm Verification Concept (AVC), suggested possible procedure, subject to local requirements Fx20xx Call Fire Brigade! 001 ALARM...
  • Page 6 Switching off detector zones / detectors The following example represents a possible operation sequence: DANGER System parts that have been switched off make it impossible to detect fires or faults! Fire may spread unhindered. ⇒ The area that has been switched off must be manually supervised. ⇒...
  • Page 7 Switching off a detector (Password required) Step Result ⇒ Main menu Access level 2.1 Press the button to open the main menu. Exit with <C> (Password required) Message summary Element search Functions Event memory Favorites Logout / change level Topology Settings / administration Function Function...
  • Page 8 Switching on detector zones / detectors (Password required) ⇒ When there is no event with a higher priority, isolations (switched off) are directly indicated on the display. You may then directly proceed with Step 3 below. ⇒ When all zones (a zone is a detector in this system’s terminology) are turned off, the section is additionally indicated as switched off.