Page 1
PDU8000 Modular Integrated PDC V1.0 User Manual Issue Date 2019-04-15 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
PDU8000 Modular Integrated PDC V1.0 User Manual About This Document About This Document Overview This document describes the precautions and methods for installing, configuring, commissioning, and maintaining the integrated power distribution cabinet (PDC), providing guidelines for the integrated PDC operation and maintenance (O&M).
Page 4
PDU8000 Modular Integrated PDC V1.0 User Manual About This Document Symbol Description Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury.
PDU8000 Modular Integrated PDC V1.0 User Manual Contents Contents About This Document ........................ii 1 User Manual Usage ........................1 2 Safety Precautions ......................... 2 2.1 General Safety Precautions ............................2 2.2 Electrical Safety ................................3 2.3 Environmental Safety ..............................4 2.4 Mechanical Safety ................................
Page 7
PDU8000 Modular Integrated PDC V1.0 User Manual Contents 5.4.5 Combining Cabinets ..............................35 5.4.6 Verifying the Installation............................37 5.5 Connecting Cables ..............................38 5.5.1 Cable Connection Precautions ..........................38 5.5.2 Connecting the Ground Cable for the PDC ......................41 5.5.3 Connecting Input Power Cables for the PDC ......................42 5.5.4 Connecting Output Power Cables for the PDC ......................
You are not allowed to modify configuration parameters without permission when using the integrated PDC. If a modification is necessary, contact Huawei technical support. Huawei shall not be responsible for any loss caused by unauthorized configuration modification.
Only qualified professionals are allowed to remove safety facilities and check the equipment. Only personnel certified or authorized by Huawei are allowed to replace or change the equipment or components (including software). Any fault or error that might cause safety problems must be reported immediately to a supervisor.
PDU8000 Modular Integrated PDC V1.0 User Manual 2 Safety Precautions The device (or system) must be connected permanently to the protection ground before operation. Before operating the device, check its electrical connection to ensure that it is securely grounded.
PDU8000 Modular Integrated PDC V1.0 User Manual 2 Safety Precautions Power Cable Do not install or remove power cables when the device is on. Transient contact between the core of the power cable and the conductor may generate electric arcs or sparks, which may cause fire or injury to human eyes.
PDU8000 Modular Integrated PDC V1.0 User Manual 2 Safety Precautions Be careful to prevent injury when moving heavy objects. A power distribution cabinet is heavy. It is recommended that you move it with the help of a tool such as the pallet truck.
PDU8000 Modular Integrated PDC V1.0 User Manual 3 Overview Overview 3.1 Product Model Figure 3-1 Product Model 3.2 Introduction The integrated PDC is an intelligent AC PDC especially designed for small- and medium-sized modular data centers. It combines air conditioner PDC, and IT PDC, features space saving, cost saving, and high integration, and applies to the power supply and distribution system of small- and medium-sized modular data centers.
Page 14
PDU8000 Modular Integrated PDC V1.0 User Manual 3 Overview Figure 3-2 Position of the PDC in the power supply and distribution network a modular data center Figure 3-3 Position of the PDC in the power supply and distribution network Both IT power distribution input of the integrated PDC and power distribution input of the air conditioner have single-input and dual-input scenarios.
PDU8000 Modular Integrated PDC V1.0 User Manual 3 Overview Figure 3-5 Integrated PDC front panel (1) IT power distribution (2) IT power distribution (3) IT power distribution input indicator input circuit breaker SPD and SPD circuit breaker (4) IT power distribution...
PDU8000 Modular Integrated PDC V1.0 User Manual 3 Overview High operation reliability and continuity Compact and space-saving design Reasonable and practical integration of functional units Comprehensive and intelligent power management Uniform and elegant appearance 3.4 Technical Specifications...
Page 18
PDU8000 Modular Integrated PDC V1.0 User Manual 3 Overview Item Specifications 160/250 IT power distribution One 3-pole 160 A MCCB input input mode One 3-pole 250 A MCCB input Two 3-pole 160 A MCCB inputs Two 3-pole 250 A MCCB inputs Air conditioner power ...
Page 19
PDU8000 Modular Integrated PDC V1.0 User Manual 3 Overview Type Circuit Breaker Capacity Derating Coefficient 160 A Table 3-3 Output circuit breaker derating Type Circuit Breaker Capacity Derating Coefficient Fixed circuit breaker 63 A 0.75 40 A Hot-swappable circuit 63 A 0.65...
PDU8000 Modular Integrated PDC V1.0 User Manual 4 Components Components 4.1 MDU The monitor display unit (MDU) allows you to set power distribution cabinet (PDC) parameters, view the running status and alarms, and upgrade software. The MDU does not support web pages.
Page 21
PDU8000 Modular Integrated PDC V1.0 User Manual 4 Components State Color Meaning Green A warning has been generated, or the PDC is running properly. The MDU is powered off. Figure 4-2 Rear view of an MDU (1) MUS05A (2) FE...
PDU8000 Modular Integrated PDC V1.0 User Manual 4 Components Port Function Remarks PIN 4: Connects to the positive terminal of the receive end on the MDU PIN 5: Connects to the negative terminal of the receive end on the MDU...
Page 23
PDU8000 Modular Integrated PDC V1.0 User Manual 4 Components Table 4-3 Indicator description Indicator Status Description Blinking at long Green indicator Normal intervals Blinking at short Communication failure intervals Abnormal power supply Red indicator Steady on The PDC generates alarms, such as...
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Installation Guide 5.1 Site Requirements The PDC site requirements are as follows: Far away from dust, smoke, harmful gas, and corrosive, flammable, or explosive objects. Free of interference from strong electromagnetic fields.
When the customer organizes construction personnel, ensure that: Construction personnel have been trained and qualified by Huawei to master methods for system installation and commissioning, and have obtained work permits before they begin to install and commission equipment.
Check that the installation environment meets the requirements before installation. For details about the check items, see the site requirements. Huawei will not be liable for any consequences caused if the installation environment does not meet the requirements. 5.3 Unpacking and Checking Context ...
Page 29
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-1 Removing the L-shaped bracket Ensure that the sliding plates are properly installed. Otherwise, the sliding plates may shift when the PDC is unloaded. Step 7 Raise the four leveling feet using an adjustable wrench.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide 5.4 Installing the PDC Prerequisites The installation environment has been checked with expected results. The site has been closed off, and notices have been posted. The PDC has been unpacked and inspected, and no problems were found.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-3 Adjusting the leveling feet ----End 5.4.2 Secured Installing the PDC on a Concrete Floor 5.4.2.1 Marking Mounting Holes Step 1 Mark installation positions of the bolts for securing the PDC using a marker based on the mounting hole positions at the cabinet bottom.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-5 Mounting hole positions at the 1200 mm deep cabinet bottom ----End 5.4.2.2 Installing Expansion Sleeves Procedure Step 1 Drill a hole at the position for installing the expansion bolt using a hammer drill with the hole depth of 52 mm to 60 mm.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-6 Expansion bolt (1) M12 bolt (2) Spring washer (3) Flat washer (4) Expansion sleeve Figure 5-7 Drilling a hole and installing an expansion sleeve (unit: mm) ----End 5.4.2.3 Securing the PDC...
Page 34
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-8 Leveling the feet Wrench an anchor bolt clockwise to elevate a cabinet leg, or wrench an anchor bolt anticlockwise to lower it. The cabinet feet can be adjusted within a range of 0–8 mm.
Page 35
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-9 Leveling the PDC (1) Level Step 3 Align the PDC mounting holes with the expansion bolt holes. Step 4 Insert four M12 expansion bolts into the expansion sleeve and use a torque wrench to tighten the bolts to a torque of 45 N m in diagonal order.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-10 Securing the PDC ----End 5.4.3 Installing the PDC on an ESD Floor A support is required when the PDC is installed on an ESD floor. The support height depends on the height between the ground and the ESD floor.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-11 Leveling and fixing bolts (1) Anchor bolt (2) Fixing bolt (3) Level ----End 5.4.4 Installing a Tail Frame Context The tail frame can extend the depth of the 1100 mm deep cabinet to 1200 mm. Its bill of materials (BOM) number is 21242025.
Page 39
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-13 Securing the tail frame accessories Step 2 Use four M5 tapping screws to secure one upper sealing plate to the tail frame. There are two upper sealing plates, and the one used in this step has a gap.
Page 40
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-15 Installing the upper sealing plates of a tail frame Step 3 Open the PDC rear door, and remove it. When removing the cabinet rear door, remove the ground cable between the cabinet and the rear door from the cabinet.
Page 41
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Put aside the hinges and connecting plates as they are needed in follow-up installation processes. Figure 5-17 Removing the PDC rear door mounting kit Step 5 Move the tail frame installed with accessories and upper sealing plates to the cabinet rear door, and adjust the anchor bolts of the tail frame so that the fail frame top is flush with the cabinet top.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Align the upper and lower holes before tightening screws. The tail frame side with anchor bolts should face the cabinet bottom. Figure 5-18 Securing the tail frame Step 7 Install the hinges and connecting plates removed in...
Page 43
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-19 Leveling the feet Step 2 Remove the cabinet connecting kits from the rack. Step 3 Secure the connecting kits in the connection positions on the front door using screws.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-20 Combining PDCs The figure is for reference only. The actual product appearance prevails. Step 6 Use a socket wrench to secure the PDC. ----End 5.4.6 Verifying the Installation...
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide 5.5 Connecting Cables 5.5.1 Cable Connection Precautions Cable Routing Standards Table 5-3 Cable routing standards Routing Rule The armoring layers of armored cables should be grounded. The PDC ground cable should be secured to the equipment room ground bar.
Page 46
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide If the wire bushings cannot be used or are missing, seal the cable inlet and outlet holes with firestop putty. Table 5-4 lists the terminal specifications for cables in the PDC. Connect cables to the corresponding terminals on the rack power distribution unit.
Page 47
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-22 Cable holes on the bottom of the PDC (1) Input power cable hole Cable inlet and outlet holes of the integrated PDC are installed with rodent-proof meshes.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-23 Positions for binding cables inside the PDC (1) Position for binding cables 5.5.2 Connecting the Ground Cable for the PDC Procedure Step 1 Lay out the ground cable based on the position of the ground grid or busbar and the onsite cabling mode.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-24 Connecting the ground cable for the PDC ----End 5.5.3 Connecting Input Power Cables for the PDC Single and dual inputs are supported for IT and air conditioner power distribution. This document describes how to connect the cable for dual inputs as an example.
Page 50
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide When cables are routed in from the top, first connect the IT power distribution input cable and the power distribution input cable of the air conditioner. When cables are routed in from the bottom, first connect the power distribution input cable of the air conditioner and the IT power distribution input cable.
Page 51
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-26 Cables routed in from the bottom ----End Follow-up Procedure After connecting cables, use diagonal pliers to cut cable inlet and outlet holes on rodent-proof meshes based on the number and specifications of cables, install the rodent-proof meshes on the top of the PDC, and seal the cable inlet and outlet holes with firestop putty.
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide 5.5.4 Connecting Output Power Cables for the PDC Procedure Step 1 Connect the IT equipment power cables to the terminals of IT output circuit breakers in the PDC. The PDC supports a maximum of 48 groups of single-phase IT outputs.
Page 53
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Figure 5-28 Connecting air conditioner output power cables for the PDC Step 3 Connect the light power cables to the terminals of light output circuit breakers in the PDC. Issue 07 (2019-04-15)
PDU8000 Modular Integrated PDC V1.0 User Manual 5 Installation Guide Connect the light power cables to XT2-1–XT2-6. When the air conditioner adopts two MCCB inputs, the L wires of the light power cable should be routed from the right side of the cabinet rear door, while the N/PE wires of XT2-4–XT2-6 should be connected to the left N/PE bars through the cable beam in the...
PDU8000 Modular Integrated PDC V1.0 User Manual 6 Power-On Commissioning Power-On Commissioning 6.1 Check Before Power-On Commissioning Table 6-1 Hardware installation checklist Check Item Result □Yes □No The cabinet is clean, without dust or sundries. □Yes □No The paint on the cabinet exterior is intact.
Page 57
PDU8000 Modular Integrated PDC V1.0 User Manual 6 Power-On Commissioning Table 6-3 Cable installation checklist Check Item Result □Yes □No All bolts are tightened, especially the bolts used for electrical connection. Flat washers and spring washers are installed properly. □Yes □No Cables are bundled neatly, and cable ties are secured evenly and properly.
PDU8000 Modular Integrated PDC V1.0 User Manual 6 Power-On Commissioning 6.2 PDC Power-On Commissioning Context Figure 6-1 Circuit breaker positions on the front panel of the PDC (1) IT power distribution (2) IT power distribution (3) IT power distribution input indicator...
Page 59
PDU8000 Modular Integrated PDC V1.0 User Manual 6 Power-On Commissioning Procedure Step 1 Switch on all SPD circuit breakers. If the surge protection module indicator is green, the SPD is running properly. If the surge protection module indicator is red, the surge protection module is faulty and must be replaced immediately.
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide MDU Commissioning Guide 7.1 Interface Description After the MDU is powered on, the main screen is displayed. The main screen consists of a status bar, an alarm bar, a menu bar, and an information area.
Page 61
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Alarm Bar Displays active alarms in a scrolling list and the number of active alarms based on severity. Tap the alarm icon area to open the active alarm page.
Page 63
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Figure 7-5 Hierarchy of the main menu The hierarchy of the menu for IT power distribution input and air conditioner power distribution input mode is used as an example.
Page 64
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Main Second-Level Third/Fourth-Level Function Preset Menu Menu Menu Value each branch. Route 2 RT Curve Route 3 RT Curve Route 4 RT Curve Main energy Inq. Queries the energy yield of each main circuit and branch circuit.
Page 65
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Main Second-Level Third/Fourth-Level Function Preset Menu Menu Menu Value System Rated Specifies the rated frequency of Param. frequency (Hz) the PDU8000. The value ranges from 45 to 65. Rated line...
Page 66
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Main Second-Level Third/Fourth-Level Function Preset Menu Menu Menu Value abnormal Main input Enable breaker tripping Mains no Enable system output Main input Enable open phase Main input Enable overvoltage...
Page 67
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Main Second-Level Third/Fourth-Level Function Preset Menu Menu Menu Value Set Rated Specifies the rated voltage of Current (A) each branch. The value ranges from 0 to 100. Threshold Sys Defect The value ranges from 0 to 60.
Page 68
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Main Second-Level Third/Fourth-Level Function Preset Menu Menu Menu Value Upper load Specifies the upper alarm 80.0 cur. thres. (%) threshold relative to the rated current. The value ranges from 80.0 to 100.0.
Page 69
Software V versions are displayed on the Version Details screen. To view software VBD versions, hardware versions, and compile time of the PDU8000, tap the blank area in the table. Tap the blank area again to return to the original screen.
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide 7.2 Common Operations 7.2.1 Information Export Configurations, logs, alarm information, and electronic labels can be exported to a USB flash drive. The following describes how to export alarm information.
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Figure 7-8 Information export 3 ----End 7.2.2 Configuration Loading The configuration loading function enables you to set system parameters for a PDC. Context Note that the configuration loading function may change the original parameter values of a PDC.
Page 72
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide Figure 7-9 Configuration loading 1 Step 2 Select the file to be loaded and tap Next. In the displayed dialog box, tap Ok. The progress bar for configuring parameters is displayed.
The Modbus protocol is expanded to support configuration upload and download. Addresses 49000 to 49999 are the extended addresses. The addresses can be customized to match the readable addresses in the protocol. For details, see PDU8000 Modbus Protocol for External Systems. 7.2.3.1 Import MD Config Procedure Step 1 Insert the USB flash drive.
PDU8000 Modular Integrated PDC V1.0 User Manual 7 MDU Commissioning Guide 7.3 DIP Switch A dual in-line package (DIP) switch is located at the rear of the MDU. Figure 7-14 DIP switch The following lists the functions of the DIP switch: ...
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Operation and Maintenance 8.1 Routine Maintenance Routine maintenance is performed on a regular basis when the equipment is running properly to find out and eliminate defects or potential risks in a timely manner.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance 8.1.2 Quarterly Maintenance Table 8-2 Quarterly maintenance Maintenance Item Operation Guide Expected Result Exception Handling PDC component Visual observation PDC components are Take measures depending on the appearance intact, without noise severity.
Page 78
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Alarm Name Alarm Possible Cause Solutions Severity Failed to configure Critical The MDU version does not Use the latest upgrade package to board match the power distribution activate the board.
Page 79
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Alarm Name Alarm Possible Cause Solutions Severity Main input THD-i Warning The input power is abnormal. Check the input power. high Main input surge Major The input AC SPD is Replace the input AC SPD.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Figure 8-1 Common polarity terminal and common terminal of the transformer (1) Common polarity terminal (2) Common terminal 8.3 Troubleshooting Symptom Possible Cause Solution 1. Replace the The LCD fails to ...
8.4 Parts Replacement This document describes only the replacement method for certain components. If a faulty component to be replaced is not covered in this document, contact Huawei technical support. 8.4.1 Replacing a Circuit Breaker Prerequisites Before replacement, ensure that the input and output circuit breakers are OFF, and that the upstream and downstream circuit breakers are also OFF.
Page 82
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Figure 8-2 Removing the panel Step 3 Remove cables connected to the left and right sides of the circuit breaker. When removing cables, label the cables with corresponding terminal ports for later connection.
Page 83
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Mark the circuit breakers removed to ensure correct reinstallation. Figure 8-4 Pushing the black clip Figure 8-5 Removing the circuit breaker Step 5 Install the new circuit breaker. Step 6 Connect cables.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Figure 8-6 Mounting holes (1) mounting holes Step 7 Reinstall the panel on the PDC. ----End 8.4.2 Replacing a Hot-Swap Circuit Breaker Prerequisites Tools required: circuit breaker extracting kit, Phillips screwdriver, key to the PDC door.
Page 85
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Figure 8-7 Removing the front panel Step 3 Push open the handles on both sides of the circuit breaker. Figure 8-8 Pushing open the handles Step 4 Remove the circuit breaker using the circuit breaker extracting kit.
Page 86
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Figure 8-9 Removing the circuit breaker (1P) Figure 8-10 Removing the circuit breaker (3P) When using an circuit breaker extracting kit to install and remove the 3-pole circuit breaker, you need to perform operations on the circuit breaker in the middle.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Verify that the new circuit breaker is switched to OFF before the installation. Figure 8-11 Removing copper bars Step 6 Install the new circuit breaker using the circuit breaker extracting kit, and close the handles on both sides of the hot-swap base.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance The MDU can be replaced online without disconnecting the power supply. Back up parameters before the replacement, and set parameters after the replacement. Procedure Step 1 Disconnect the CAN, FE or DB26 communications cables from the MDU.
Page 89
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Do not replace a surge protection module during a thunderstorm. Tools required: an electrical tester pen and the PDC door key. Materials required: a spare surge protection module of the same model is available and functional.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Figure 8-15 Detecting voltages Step 4 Use a flat-head screwdriver to lever the faulty SPD out. Step 5 Install a new SPD module. Figure 8-16 Replacing an SPD Module If there is a faulty surge protection module, it is recommended that all surge protection modules be replaced.
Page 91
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance When replacing a fuse, you must wear insulation gloves, and must not touch the input copper bar. Tools required: a pair of insulation gloves and the PDC door key.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance When an electricity meter is configured Fuse Description FU1–FU3 Fuses of yellow, green, and red indicators respectively Power supply fuse of the electricity meter FU5–FU6 Fuses of the power board FU7–FU9...
Page 93
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Procedure Step 1 Open the PDC rear door, push out the fuse terminal block, and remove the fuse of the indicator to open the circuit. Step 2 Open the PDC front door, and open the indicator protection panel.
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance Step 6 Reinstall the fuse to reconnect the circuit. Step 7 Verify that the indicator lights up properly. Step 8 Reinstall the protection panel. ----End 8.4.7 Replacing a Power Distribution Monitoring Board Prerequisites ...
PDU8000 Modular Integrated PDC V1.0 User Manual 8 Operation and Maintenance 8.4.8 Replacing an Electricity Meter Prerequisites Tools required: an electrical tester pen, a pair of insulation gloves, a Phillips screwdriver, the PDC door key. Materials required: A spare electricity meter of the same model is available and functional.
PDU8000 Modular Integrated PDC V1.0 User Manual A PDC Silk Screen Description PDC Silk Screen Description The silk screen content is in the format of route number + symbol + switch sequence number. In the single-input scenario, the route number is omitted by default. For example, 1QF1 indicates the first switch of route I, 2QF1 indicates the first switch of route II, and QF1 indicates the first switch in the single-input scenario.
PDU8000 Modular Integrated PDC V1.0 User Manual C Acronyms and Abbreviations Acronyms and Abbreviations control area network China Compulsory Certification Conformité Europé enne current transformer fast Ethernet International Electrotechnical Commission Internet Protocol miniature circuit breaker MCCB molded case circuit breaker...