Honeywell apex Step-By-Step

Honeywell apex Step-By-Step

Single 4-wire smoke zone with sounders
Hide thumbs Also See for apex:

Advertisement

Quick Links

Step-by-Step
- Single 4-Wire Smoke Zone with Sounders -
Objective
To activate the sounders on
all smokes after any smoke
detector is activated

Sequence of Operation

When the panel detects an alarm from any fire zone, the panel will activate the on board relay to activate the trigger
wire (purple see wiring diagram below) which in turn with sound ALL sounders.
To Reset:
1. Press Code 1 time
2. Press Code + 6 (Smoke Power Reset)
3. Arm and Disarm the panel (to Clear the Alarm Memory)
Required Programming
Location
9940
4097
4119
0185
4055
See Below for the wiring Diagram:
Apex Destiny 6100 Control Panel, rev. 8.05 or greater
System Sensor Smokes: 4WTA-B, 4WTAR-B, 4WITAR-B
System Sensor RRS-MOD
Value
Function
01 (zone #)
Zone Type = 006
Zone Options 1 = 080
Zone Options 2 = 001
Device Type = 000 (onboard zones) or 001 (Zone Expander HWB416)
Enter the 2 digit input # (001 in this case)
001
Enable Control Channel 1
008
Assign Control Channel 1 to the on-board relay
001
Assign the "fire" Trigger
006
002 (on – on any fire alarm) + 004 (off – restore action for fire alarm is
disarming the control) = 006
Equipment List
- 1 -
Tech Support
Updated 11/2/07

Advertisement

loading

Summary of Contents for Honeywell apex

  • Page 1: Sequence Of Operation

    - Single 4-Wire Smoke Zone with Sounders - Objective Equipment List To activate the sounders on Apex Destiny 6100 Control Panel, rev. 8.05 or greater all smokes after any smoke System Sensor Smokes: 4WTA-B, 4WTAR-B, 4WITAR-B detector is activated System Sensor RRS-MOD...
  • Page 2 - Multiple 4-Wire Smoke Zones with Sounders - Objective Equipment List To activate the sounders on Apex Destiny 6100 Control Panel, rev. 8.05 or greater all smokes after any smoke System Sensor Smokes: 4WTA-B, 4WTAR-B, 4WITAR-B detector is activated System Sensor RRS-MOD...
  • Page 3 - 2-Wire Smoke Zones with Sounders - Objective Equipment List To activate the sounders on Apex Destiny 6100 Control Panel, rev. 8.05 or greater all smokes after any smoke System Sensor Smokes: 2WTA-B, 2WTR-B detector is activated System Sensor RRS-MOD...
  • Page 4 Step-by-Step If any fire alarm occurs, Press F2 to silence smokes. Then enter a valid 4 digit code to silence sounder. Then enter a valid 4 digit code and 6 to reset smokes. Note Pressing F2 with no Fire alarm condition present will cause the sounders to activate and deactivate. 2-wire Smoke loop Wiring Notes: Sounders will continue to sound until a valid 4 digit code is entered.