Appliance information
3
Appliance information
3.1
General information
Standard package:
A - Floor standing oil fired condensing boiler
B - Literature pack:
• Greenstar Danesmoor external Installation, Commissioning and
Servicing instruction manual
• User Instructions
• Guarantee registration card
C - Condensate trap
D - BSP plug, one inch (Regular only)
E - ErP label
F - Flue damper
G - Balanced flue kit
H - 100mm Ø Services duct
J - Cabinet key
A
J
H
Fig. 1
Standard package
6
B
C
D
E
F
G
3.2
Technical data
Description
Central heating
Central heat output (max)
Primary water capacity (total)
Max.static head (Regular only)
Min. static head (Regular only)
Water side resistance (20°C
difference)
Maximum available pump head
(20°C difference) System only
Maximum permissible sealed
system operating pressure in
accordance with WRAS
guidelines
Flue
Exit flue gas mass flow
Pipework connections
Fuel line (compression)
Flow Kitchen
Flow Kitchen System
Kitchen flow and optional vent/
air vent
Return
Condensate (Polypropylene)
PRV outlet - System only
Electrical
Electrical power supply voltage ac ..V
Frequency
Thermostats
Boiler flow temperature range
(cut in/cut out)
Control thermostat differential
Boiler high limit thermostat set
point
Boiler manual reset overheat
thermostat set point
Flue manual reset overheat
thermostat set point
General data
Maximum hearth temperature
SEDBUK 2009
SEDBUK 2005
Appliance protection rating
Weight (excluding packaging)
External Regular
Weight (excluding packaging)
External System
Greenstar Danesmoor External
ErP+
and External System
Units
12/18 18/25 25/32
kW
18
25
32
litres
20
21
22
metres
30
30
30
metres
1
1
1
mbar
20
30
56
mH
O
5.2
4.3
4.1
2
bar
2.5
2.5
2.5
kg/hr
29
40
51
mm
10
10
10
BSP
1"
1"
1"
mm
22
22
28
BSP
1"
1"
1"
mm
22
22
28
mm
21.5
21.5
21.5
mm
15
15
15
230
230
230
Hz
50
50
50
°C
55/81 55/81 55/81
°C
5
5
5
°C
95
95
95
°C
105
105
105
°C
110
110
110
°C
<100
<100
<100
%
91.1
90.9
90.7
%
93.2
93.0
92.8
IP
45
45
45
kg
110
114
124
kg
119
121
131
ErP+
6720821725 (2018/04)