en | On-board points
Callout - Description
3 - 1.0 kΩ resistor at device
4 - 1.0 kΩ resistor at EOL (end-of-line)
12.2
Point response time
The control panel scans on-board and off-board point sensor loops every 250 milliseconds. In
RPS or in the Installer Services Portal programming tool (available in Europe, Middle East,
Africa, and China), the Debounce parameter in the Point Assignment section sets the point
response time. Set the length of time the control panel scans a point before the control panel
sends an alarm.
The debounce time can range from 250 milliseconds to 6.15 seconds. The default for
Debounce is 820 ms.
Notice!
Before you increase the Debounce time
Increasing Debounce time might cause missed alarms. If you increase the Debounce time,
detection devices can enter alarm and reset without exceeding the point response time.
Debounce does not apply to points with the Point Source configured as Wireless, Output, or
IP Camera.