Medium voltage products Installation and service instructions 12-40.5 kV – 630-3600 A – 16-50 kA Index 1. Packing and transport 2. Checking on receipt 3. Storage 4. Handling 5. Description 6. Instructions for circuit-breaker operation 7. Installation 8. Putting into service 9.
• Check that the personnel operating the apparatus have this instruction manual to hand as well as the necessary information for correct intervention. Responsible behaviour safeguards your own and others’ safety! For any requests, place contact the ABB Assistance Service.
Page 4
The environmental impact of the product life cycle is assessed Like all the apparatus manufactured by us, the HD4 circuit- by the LCA - Life Cycle Assessment procedure, which is also breakers are designed for different installation configurations.
Packing and transport The circuit-breaker is shipped in special packing in the open position with the springs discharged and with absolute pole pressure corresponding with the service value. Each piece of apparatus is protected by a plastic film to prevent any infiltration of water during the loading and unloading stages and to keep the dust off during storage.
If any damage or irregularity is discovered on unpacking, notify ABB (directly or through the agent or supplier) as soon as possible and in any case within five days of receipt. The apparatus is only supplied with the accessories specified at the time of order and confirmed in the order acknowledgement sent by ABB.
Storage In case a storage period is foreseen, on request our Insert hygroscopic substances in the packaging in the workshops will provide a suitable packing to the specified quantity of at least one standard pack per apparatus. storage conditions. Therefore, store in a sheltered, well-ventilated area with a On receipt, the apparatus must be carefully unpacked and dry, non-dusty, non-corrosive atmosphere away from highly checked as described in chapter 2: Checkink on receipt.
Handling Before carrying out any operation, always check that the 36 kV circuit-breakers operating mechanism springs are discharged and that the – Attach the tools (1) to lift and handle the circuit-breaker apparatus is in the open position. (fig. 2c); –...
Description 5.1. General features 5.3. Fixed circuit-breaker The HD4 series are sulphur hexafluoride circuit-breakers for The fixed circuit-breaker (see fig. 4) corresponds to the basic indoor installation. For the electrical performance, please refer version complete with a front protection shield and frame.
Page 11
The strikers for activating the contacts (connected/isolated), The activating lever (connection/isolation) must be fully located in the enclosure or in the switchgear, are fixed in the inserted. A lock prevents the truck from advancing into the top part of the circuit-breaker. The slides for activating the enclosure or fixed part (for example when the earthing switch segregation shutters of the medium voltage contacts of the is closed).
Instructions for circuit-breaker operation 6.1. Safety indications 6.3. Circuit-breaker closing and opening operations (fig. 6) HD4 circuit-breakers ensure a minimum degree of protection IP2X if installed under the following Circuit-breaker operation can be manual or electrical. conditions: – fixed version, with protection netting a) Manual operation for spring charging –...
Installation 7.1. General 7.4. Installation of fixed circuit-breaker The circuit-breaker can be mounted directly on the supporting Correct installation is of prime importance. The frames provided by the customer. instructions given by the manufacturer must be carefully studied and followed. It is good The circuit-breaker, complete with supporting truck, must be practice to use gloves to handle the pieces during fixed to the floor of its compartment with special brackets.
Page 14
7.6. Fixed circuit-breaker power circuit Mounting procedures connections – Place the connections in contact with the circuit-breaker terminals. 7.6.1. General directions – Interpose a spring washer and a flat washer between the head of the bolt and the connection. – The connections must be made using only the squares- –...
Page 15
Standards in force. automatism provided for operation of the pressure switch (if provided) referring to the latest technical documentation supplied by ABB. 7.8.1. Fixed circuit-breaker The connection of the circuit-breaker auxiliary circuits must be made via the terminal box mounted on the circuit-breaker structure.
Page 20
7.9. Overall dimensions Fixed circuit-breakers with truck (on request) 7268 1250 1600 31.5 with truck (on request) 7268 2000 31.5 Insulating partitions to be provided by the customer (a special kit is available on request). * Distance with truck (if provided). Fixed circuit-breakers with truck (on request) 7315...
Page 21
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 1VCD000227 17.5 1250 31.5 Also suitable for Power- Cube PB1 ±2...
Page 22
7.9. Overall dimensions HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 7350 ±1 ±1 111.5 17.5 1250 HD4/P 67.5 7350 17.5 1600 53.5 31.5 kA (*) kA (*) (*) Also suitable for PowerCube PB2. ±2 ±1.5 HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears...
Page 23
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 7352 kV (*) 111.5 ±1 ±1 17.5 2500 31.5 67.5 (*) Also suitable for PowerCube PB3. 43.5 ±2 ±1.5 HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 7371 96.5 ±1 ±1...
Page 24
7.9. Overall dimensions HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P ±1 ±1 1VCD00236 1250 kA (*) (*) 630 A only. ±1 ±2 ±1,5 HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 1VCD000099 ±1 ±1 67.5 1250 A 31.5...
Page 25
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 7355 (*) ±1 ±1 1600 A 31.5 67.5 (*) Also suitable for PowerCube PB5. 43.5 ±2 ±1.5 HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchgears HD4/P 7356 (**) ±1 ±1 2000 A 31.5...
Page 29
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module HD4/W 7402 67.5 1250 A Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module HD4/W 7316 1250 A 31.5...
Page 30
7.9. Overall dimensions Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module HD4/W 119 23 7317 67.5 1600 A 2000 A 2500 A (*) 31.5 (*) With forced ventilation. HD4/Z withdrawable circuit-breakers for UniGear type ZS3.2 - 40.5 kV switchgears HD4/Z/40.5 kV...
All the operations regarding putting into service – check the tightness of the power connections on the circuit- must be carried out by ABB personnel or customer breaker terminals; personnel who are suitably qualified and have – establish the setting of the direct solid-state overcurrent an in-depth knowledge of the apparatus and release (if provided);...
Page 33
Subject of the inspection Procedure Positive check Locking electromagnet on With the circuit-breaker open in the isolated for test position Connection is not possible. the circuit-breaker truck and the locking electromagnet not supplied, attempt to (YL2) (if provided). connect the circuit-breaker. Supply the locking electromagnet and carry out the Connection takes place correctly.
Periodical checking 10. Maintenance operations Before carrying out any operation, make sure that Maintenance must only be carried out by ABB the operating mechanism springs are discharged personnel or in any case by suitably qualified and that the apparatus is in the open position.
Potential (GWP) which is 22.800 higher than CO2, according document (1VCP000264). to the Fourth Assessment Report. To dispose of the SF6 gas, please contact the ABB The GWP is calculated over a time period of 100-years Assistance Service (see contact persons at http://www.abb.
12.1. List of spare parts All assembly operations of spare parts/accessories regarding installation, putting into service, service – Shunt opening release and maintenance must be carried out by ABB – Additional shunt opening release personnel or suitably qualified customer personnel – Undervoltage release with in-depth knowledge of the apparatus (IEC –...