hit counter script
GE T60 Instruction Manual

GE T60 Instruction Manual

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

GE
Grid Solutions
T60
Transformer Protection System
Instruction Manual
Product version: 7.6x
GE publication code: 1601-0090-AF2 (GEK-131008A)
E83849
LISTED
IND.CONT. EQ.
52TL
1601-0090-AF2

Advertisement

Table of Contents
loading

Summary of Contents for GE T60

  • Page 1 Grid Solutions Transformer Protection System Instruction Manual Product version: 7.6x GE publication code: 1601-0090-AF2 (GEK-131008A) E83849 LISTED IND.CONT. EQ. 52TL 1601-0090-AF2...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    Type tests ..........................2-45 2.5.14 Production tests ........................2-45 2.5.15 Approvals ..........................2-46 2.5.16 Maintenance.........................2-46 3 INSTALLATION Unpack and inspect ....................3-1 Panel cutouts ......................3-2 3.2.1 Horizontal units ........................3-2 3.2.2 Vertical units ........................... 3-6 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 4 Configure modem connection..................3-65 3.7.5 Automatic discovery of UR devices................3-65 Connect to the T60 ....................3-66 3.8.1 Connect to the T60 in EnerVista.................. 3-66 3.8.2 Use Quick Connect via front RS232 port..............3-67 3.8.3 Use Quick Connect via front USB port ..............3-68 3.8.4...
  • Page 5 Direct inputs and outputs....................5-135 5.3.19 Teleprotection ........................5-141 5.3.20 Installation ..........................5-142 Remote resources ....................5-142 5.4.1 Remote resources configuration ................5-142 System setup.......................5-144 5.5.1 AC inputs ..........................5-144 5.5.2 Power system........................5-145 5.5.3 Signal sources........................5-146 5.5.4 Transformer ........................5-149 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 6 RTD inputs .......................... 5-376 5.10.3 RRTD inputs........................5-377 5.10.4 DCmA outputs ........................5-381 5.11 Testing ......................... 5-384 5.11.1 Test mode function ......................5-384 5.11.2 Test mode forcing......................5-385 5.11.3 Phasor Measurement Unit test values..............5-385 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 7 6.5.1 User-programmable fault reports................6-29 6.5.2 Event records ........................6-30 6.5.3 Oscillography........................6-32 6.5.4 Data logger ...........................6-32 6.5.5 Phasor Measurement Unit records................6-32 6.5.6 Breaker maintenance.......................6-33 Product information .................... 6-34 6.6.1 Model information......................6-34 6.6.2 Firmware revisions ......................6-34 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 8 10.6 Compare settings ....................10-7 10.6.1 Compare against defaults ..................... 10-7 10.6.2 Compare two devices ...................... 10-8 10.7 Back up and restore settings ................10-8 10.7.1 Back up settings .........................10-8 10.7.2 Restore settings ....................... 10-11 viii T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 9 A FLEXANALOG FlexAnalog items ....................A-1 OPERANDS B RADIUS SERVER RADIUS server configuration ................B-1 CONFIGURATION C COMMAND LINE Command line interface ..................C-1 INTERFACE D MISCELLANEOUS Warranty .........................D-1 Revision history ......................D-1 ABBREVIATIONS INDEX T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 10 TABLE OF CONTENTS T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 11: Introduction

    Ensure that the control power applied to the device, the alternating current (AC), and voltage input match the ratings specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 12: For Further Assistance

    When contacting GE by e-mail, optionally include a device information file, which is generated in the EnerVista software by clicking the Service Report button. The service report also can be generated in the field, for example with a USB cable connected between the graphical front panel and a computer, and the Device Setup configured for the USB connection.
  • Page 13 CHAPTER 1: INTRODUCTION FOR FURTHER ASSISTANCE Figure 1-1: Generate service report in EnerVista software T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 14 FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 15: Product Description

    2.1 Product description The T60 Transformer Protection System is part of the Universal Relay (UR) series of products. It is a microprocessor-based relay for protection of small, medium, and large three-phase power transformers. The relay can be configured for a maximum of six three-phase current inputs and six ground current inputs, and can satisfy applications with transformer windings connected between two breakers, such as in a ring bus or in breaker-and-a-half configurations.
  • Page 16: Description

    Secure Routable GOOSE (R-GOOSE) is supported with software options. Settings and actual values can be accessed from the front panel or EnerVista software. The T60 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are upgradable.
  • Page 17 CHAPTER 2: PRODUCT DESCRIPTION PRODUCT DESCRIPTION Figure 2-1: Single-line diagram T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 18: Security

    Remote access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet and RS485 connections. These two settings are on by default and apply to all users. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 19 When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the T60, the remote password is used. If the connection is to a front panel port, the local password applies. (These two local and remote password settings are not shown the figure.)
  • Page 20 |--------------- Demand |--------------- User-Programmable LEDs |--------------- User-Programmable Self Tests |--------------- Control Pushbuttons RW |--------------- User-Programmable Pushbuttons |--------------- Flex state Parameters |--------------- User-Definable Displays |--------------- Direct I/O |--------------- Teleprotection |--------------- Installation |---------- System Setup T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 21 Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled) NA = the permission is not enforced by CyberSentry security CyberSentry user authentication The following types of authentication are supported by CyberSentry to access the UR device: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 22: Order Codes

    The order code is on the product label and indicates the product options applicable. The T60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit. It consists of the following modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 23 CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES Table 2-4: T60 order codes for horizontal units - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount...
  • Page 24 IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5 IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + PMU + IEC 61850 + Synchrocheck + 61850-90-5 2-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 25 Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED 7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-11...
  • Page 26 Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels Table 2-5: T60 order codes for reduced-size vertical units - * ** - * * * - F ** - H **...
  • Page 27 English display French display Russian display Chinese display Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-13...
  • Page 28: Order Codes With Process Bus Modules

    G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels 2.3.2 Order codes with process bus modules Table 2-6: T60 order codes for horizontal units with process bus - * ** - * * * - F ** - H **...
  • Page 29 PRP, CyberSentry Lvl 1, PMU, IEC 61850, and Synchrocheck IEEE 1588, PRP, and CyberSentry Lvl 1 IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-15...
  • Page 30 IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + IEC 61850 + PMU + 61850-90-5 IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry UR Lvl 1 + PMU + IEC 61850 + Synchrocheck + 61850-90-5 2-16 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 31 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-17...
  • Page 32 ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION Table 2-7: T60 order codes for reduced-size vertical units with process bus - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 33 Enhanced front panel with German display Enhanced front panel with German display and user-programmable pushbuttons POWER SUPPLY 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-19...
  • Page 34: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or front panel, provide the serial number of your existing unit. Not all replacement modules apply to the T60 relay. The modules specified in the order codes for the T60 are available as replacement modules for the T60.
  • Page 35 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed) 8 RTD inputs 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-21...
  • Page 36 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed) 8 RTD inputs 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs 2-22 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 37: Signal Processing

    The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems. The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking system. The analog/digital converter has the following ranges of AC signals: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-23...
  • Page 38 Measured analog values and binary signals can be captured in COMTRADE format with sampling rates from 8 to 64 samples per power cycle. Analog values can be captured with the Data Logger, allowing much slower rates extended over a long period of time. 2-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 39: Specifications

    Zones 2 to 5: ±5% for steady fault conditions Distance: Characteristic angle: 30 to 90° in steps of 1 Comparator limit angle: 30 to 90° in steps of 1 Directional supervision: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-25...
  • Page 40 0.000 to 65.535 s in steps of 0.001 Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater) Current supervision: Level: neutral current (3I_0) Pickup: 0.050 to 30.000 pu in steps of 0.001 Dropout: 97 to 98% 2-26 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 41 > 2.0 × CT: ±1.5% of reading > 2.0 × CT rating Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse, Short/Very/ Extremely Inverse; I t; FlexCurves™ (programmable); Definite Time (0.01 s base curve) Curve multiplier: Time Dial = 0.00 to 600.00 in steps of 0.01...
  • Page 42 0.000 to 0.500 in steps of 0.001 Characteristic angle: 0 to 90° in steps of 1 Limit angle: 40 to 90° in steps of 1, independent for forward and reverse Angle accuracy: ±2° 2-28 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 43 Curve timing accuracy at >1.1 pickup: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate Operate time: <30 ms at 1.10 pickup at 60 Hz AUXILIARY OVERVOLTAGE Pickup level: 0.004 to 3.000 pu in steps of 0.001 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-29...
  • Page 44 Typical times are average operate times including variables, such as frequency change instance, and test method, and can vary by ±0.5 cycles. OVERFREQUENCY Pickup level: 20.00 to 65.00 Hz in steps of 0.01 Dropout level: pickup – 0.03 Hz 2-30 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 45 ±3% of operate time or ±42 ms, whichever is greater Operate time: <42 ms at 1.10 × pickup at 60 Hz BREAKER RESTRIKE Principle: detection of high-frequency overcurrent condition ¼ cycle after breaker opens Availability: one per digital signal processor (DSP) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-31...
  • Page 46 ±500 ms or 2%, whichever is greater for I < 0.9 × k × I and I / (k × I ) > 1.1 RTD PROTECTION Pickup: 1 to 249°C in steps of 1 Dropout level: 2°C of pickup 2-32 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 47: User-Programmable Elements

    Number: 16 (individually programmed) Output: stored in non-volatile memory Execution sequence: as input prior to protection, control, and FlexLogic USER-PROGRAMMABLE LEDs (Enhanced and standard front panels) Number: 48 plus trip and alarm T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-33...
  • Page 48: Monitoring

    FlexLogic equation Data: AC input channels; element state; contact input state; contact output state Data storage: in non-volatile memory 2-34 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 49: Metering

    REAL POWER (WATTS) Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating: ±1.0% of reading at –1.0 ≤ PF < –0.8 and 0.8 < PF ≤ 10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-35...
  • Page 50: Inputs

    Relay burden: < 0.2 VA at rated secondary Conversion range: Standard CT: 0.02 to 46 × CT rating RMS symmetrical Sensitive Ground CT module: 0.002 to 4.6 × CT rating RMS symmetrical 2-36 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 51 Range: –50 to +250°C Accuracy: ±2°C Isolation: 36 V pk-pk REMOTE RTD INPUTS Wire type: three-wire Sensor type: 100 Ω platinum (DIN 43760), 100 Ω nickel, 120 Ω nickel, 10 Ω copper T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-37...
  • Page 52: Power Supply

    100 to 240 V at 50/60 Hz Minimum AC voltage: 88 V at 25 to 100 Hz Maximum AC voltage: 265 V at 25 to 100 Hz Voltage loss hold-up: 200 ms duration at maximum load 2-38 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 53: Outputs

    1 to 2.5 mA FORM-A CURRENT MONITOR Threshold current: approx. 80 to 100 mA FORM-C AND CRITICAL FAILURE RELAY Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-39...
  • Page 54 1.6 A at L/R = 20 ms 0.8 A L/R = 40 ms CONTROL POWER EXTERNAL OUTPUT (For dry contact input) Capacity: 100 mA DC at 48 V DC Isolation: ±300 Vpk DIRECT OUTPUTS Output points: 2-40 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 55: Communication Protocols

    SIMPLE NETWORK TIME PROTOCOL (SNTP) Clock synchronization error: <10 ms (typical) PRECISION TIME PROTOCOL (PTP) PTP IEEE Std 1588 2008 (version 2) Power Profile (PP) per IEEE Standard PC37.238TM2011 Slave-only ordinary clock Peer delay measurement mechanism T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-41...
  • Page 56: Inter-Relay Communications

    At extreme temperatures these values deviate based on component tolerance. On average, the output power decreases as the temperature is increased by a factor of 1 dB / 5 °C. 2-42 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 57: Cybersentry Security

    1 phasor metering page for each AC Source 5 tabular metering pages with dynamic metering and status event records page with dynamic update product information page settings, actual values, error messages (targets) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-43...
  • Page 58: Environmental

    IP20 front, IP10 back (standard front panel and old enhanced front panel) IP40 front, IP10 back (new enhanced front panel) IP54 front with IP54 mounting collar accessory (new enhanced front panel) Ingress protection with IP20 cover accessory: IP20 back Noise: 0 dB 2-44 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 59: Type Tests

    Insulation: class 1, Pollution degree: 2, Over voltage cat II 1 Not tested by third party. 2.5.14 Production tests THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2-45...
  • Page 60: Approvals

    Normally, cleaning is not required. When dust has accumulated on the front panel display, wipe with a dry cloth. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 2-46 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 61: Installation

    For any issues, contact GE as outlined in the For Further Assistance section in chapter 1. Check that you have the latest copy of the T60 Instruction Manual and the UR Family Communications Guide, for the applicable firmware version, at http://www.gegridsolutions.com/multilin/manuals/index.htm...
  • Page 62: Panel Cutouts

    3.2.1 Horizontal units The T60 is available as a 19-inch rack horizontal mount unit with a removable front panel. The front panel is specified as enhanced, standard, or graphical at the time of ordering. The enhanced and graphical front panels contain additional user-programmable pushbuttons and LED indicators.
  • Page 63 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-1: Horizontal dimensions (old enhanced front panel) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 64 PANEL CUTOUTS CHAPTER 3: INSTALLATION Figure 3-2: Horizontal dimensions (enhanced front panel) Figure 3-3: Horizontal mounting (enhanced and graphical front panels) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 65 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-4: Horizontal dimensions and mounting (standard front panel) Figure 3-5: Horizontal dimensions (graphical front panel) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 66: Vertical Units

    3.2.2 Vertical units The T60 is available as a reduced size (¾) vertical mount unit, with a removable front panel. The front panel is specified as enhanced or standard at the time of ordering. The enhanced front panel contains additional user-programmable pushbuttons and LED indicators.
  • Page 67 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-7: Vertical dimensions and mounting (enhanced front panel) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 68 PANEL CUTOUTS CHAPTER 3: INSTALLATION Figure 3-8: Vertical dimensions and mounting (standard front panel) For side-mounting T60 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Grid Solutions website: • GEK-113180 —...
  • Page 69 CHAPTER 3: INSTALLATION PANEL CUTOUTS For side-mounting T60 devices with the standard front panel, use the following figures. Figure 3-9: Vertical side-mounting installation (standard front panel) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 70 PANEL CUTOUTS CHAPTER 3: INSTALLATION Figure 3-10: Vertical side-mounting rear dimensions (standard front panel) 3-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 71: Rear Terminal Layout

    Two-slot wide modules take their slot designation from the first slot position (nearest to CPU module), indicated by an arrow on the terminal block. The figure shows an example of rear terminal assignments. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-11...
  • Page 72 Wire connections to these two modules at 13 inch-pounds. Figure 3-12: CPU modules and power supply The following figure shows the optical connectors for CPU modules. 3-12 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 73 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-13: LC fiber connector (left) and ST fiber connector (right) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-13...
  • Page 74: Wiring

    WIRING CHAPTER 3: INSTALLATION 3.3 Wiring 3.3.1 Typical wiring Figure 3-14: Typical wiring diagram (T module shown for CPU) 3-14 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 75: Dielectric Strength

    The power supply module can be ordered for two possible voltage ranges, and the T60 can be ordered with or without a redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges are as follows (see the Specifications section of chapter 2 for details): •...
  • Page 76: Ct/Vt Modules

    CHAPTER 3: INSTALLATION For high-reliability systems, the T60 has a redundant option in which two T60 power supplies are placed in parallel on the bus. If one of the power supplies becomes faulted, the second power supply assumes the full load of the relay without any interruptions.
  • Page 77 The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as input for the synchrocheck and volts-per-hertz features, which are optional features for some UR models. Substitute the tilde “~” symbol with the slot position of the module in the following figure. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-17...
  • Page 78: Process Bus Modules

    Figure 3-17: CT/VT module wiring 3.3.5 Process bus modules The T60 can be ordered with a process bus interface module. The module interfaces with the HardFiber Process Bus System, or HardFiber Brick, allowing bidirectional IEC 61850 fiber-optic communications with up to eight HardFiber Bricks.
  • Page 79 See the Digital Elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied for breaker trip circuit integrity monitoring. Consider relay contacts unsafe to touch when the unit is energized. Death or serious injury can result from touching live relay contacts. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-19...
  • Page 80 Output or Terminal Output or assignment input assignment assignment input assignment input Form-C Fast Form-C Form-A Form-A Form-C Fast Form-C Form-A Form-A Form-C Fast Form-C Form-A Form-A Form-C Fast Form-C Form-A Form-A 3-20 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 81 ~15a - ~16a Output ~9a, ~9b 2 Inputs ~17a - ~18a Output ~10a, ~10b 2 Inputs ~1b - ~2b Output ~11a, ~11b 2 Inputs ~3b - ~4b Output ~13a, ~13b 2 Inputs T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-21...
  • Page 82 2 Outputs ~4a, ~4c 2 Inputs 2 Outputs ~5a, ~5c 2 Inputs 2 Outputs ~6a, ~6c 2 Inputs 2 Outputs ~7a, ~7c 2 Inputs 2 Outputs ~8a, ~8c 2 Inputs Not Used 3-22 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 83 CHAPTER 3: INSTALLATION WIRING Figure 3-19: Contact input and output module wiring (Sheet 1 of 3) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-23...
  • Page 84 WIRING CHAPTER 3: INSTALLATION Figure 3-20: Contact input and output module wiring (Sheet 2 of 3) 3-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 85 17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources. Figure 3-22: Dry and wet contact input connections Where a tilde “~” symbol appears, substitute the slot position of the module. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-25...
  • Page 86 T60 input even when the output is open, if there is a substantial distributed capacitance (represented by C1) present in the wiring between the output and the T60 input, and the debounce time setting in the T60 relay is low enough.
  • Page 87 To prevent this operation, the debounce time must be increased to 4 ms (set debounce time as per the following table) or insert a resistor less than or equal to "R" as calculated later. Table 3-5: Typical debounce time setting Stray capacitance (μF) Battery voltage (V) Debounce time (ms) 0.05 0.05 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-27...
  • Page 88 Eq. 3-2 The 2 mA current is used in case the contact input is connected across the GE Form A contact output with voltage monitoring. Otherwise use the amperage of the active circuit connected to the contact input when its contact output is open and the voltage across the contact input is third trigger threshold to calculate the resistor value.
  • Page 89 Contact inputs can be susceptible to parasitic capacitance, caused by long cable runs affected by switching surges from external circuits. This can result in inadvertent activation of contact inputs with the external contact open. In this case, GE recommends using the contact I/O module with active impedance circuit.
  • Page 90: Transducer Inputs And Outputs

    The following figure illustrates the transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. 3-30 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 91 CHAPTER 3: INSTALLATION WIRING Where a tilde “~” symbol appears, substitute the slot position of the module. Figure 3-28: Transducer input/output module wiring The following figure show how to connect RTDs. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-31...
  • Page 92: Rs232 Port

    RS232 port is shown in the following figure for the nine-pin connector on the UR and nine or 25-pin connector on a computer. The baud rate for this port can be set, with a default of 115200 bps. Figure 3-30: RS232 front panel port connection 3-32 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 93: Cpu Communication Ports

    3.3.9 CPU communication ports 3.3.9.1 Overview There is a rear RS485 communication port on the CPU module. The CPU module does not require a surge ground connection. Figure 3-31: CPU module communications wiring T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-33...
  • Page 94 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the T60 COM terminal (#3); others function correctly only if the common wire is connected to the T60 COM terminal, but insulated from the shield.
  • Page 95: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. The GE MultiSync 100 1588 GPS Clock as well as third-party equipment are available for generating the IRIG-B signal.
  • Page 96: Direct Input And Output Communications

    UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring. 3-36 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 97 Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the Order Code tables in Chapter 2. All of the fiber modules use ST type connectors. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-37...
  • Page 98: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser modules. Figure 3-39: 7x Laser fiber modules The following figure shows configuration for the 2I and 2J fiber-laser modules. 3-38 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 99: Interface

    X1a or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is protected by surge suppression devices. Figure 3-41: G.703 interface configuration T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-39...
  • Page 100 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is inserted fully. 3-40 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 101 (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). The switch settings for the internal and loop timing modes are shown. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-41...
  • Page 102 One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface. Figure 3-46: G.703 dual loopback mode 3-42 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 103: Rs422 Interface

    (data module 1) connects to the clock inputs of the UR RS422 interface in the usual way. In T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-43...
  • Page 104 Figure 3-49: Timing configuration for RS422 two-channel, three-terminal application Data module 1 provides timing to the T60 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure because they vary by manufacturer.
  • Page 105: Rs422 And Fiber Interface

    For the direct fiber channel, address power budget issues properly. When using a laser interface, attenuators can be necessary to ensure that you do not exceed maximum optical input power to the receiver. Figure 3-51: RS422 and fiber interface connection T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-45...
  • Page 106: And Fiber Interface

    Connection — as per all fiber-optic connections, a Tx-to-Rx connection is required The UR-series C37.94 module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94 standard. The figure shows the concept. 3-46 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 107 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of T60 communication for two and three terminal applications.
  • Page 108 When the clips have locked into position, the module is inserted fully. Figure 3-56: IEEE C37.94 timing selection switch setting Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. 3-48 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 109: C37.94Sm Interface

    Fiber-optic cable length — Up to 11.4 km • Fiber-optic connector — Type ST • Wavelength — 1300 ±40 nm • Connection — As per all fiber-optic connections, a Tx-to-Rx connection is required T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-49...
  • Page 110 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of T60 communication for two and three terminal applications.
  • Page 111 When the clips have locked into position, the module is inserted fully. Figure 3-59: C37.94SM timing selection switch setting Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-51...
  • Page 112: Activate Relay

    Press the right arrow until the message displays. MESSAGE SECURITY Press the down arrow until the message displays. MESSAGE INSTALLATION Press the right arrow until the Not Programmed message displays. MESSAGE RELAY SETTINGS: 3-52 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 113: Install Software

    To communicate via the RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to the relay and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports section earlier in this chapter. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-53...
  • Page 114: System Requirements

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair wire (20, 22, or 24 AWG) connects the F485 converter to the T60 rear communications port. The converter terminals (+, –, GND) are connected to the T60 communication module (+, –, COM) terminals. See the CPU Communication Ports section in chapter 3 for details.
  • Page 115: Install Software

    Add Now button to list software items for the product. EnerVista Launchpad obtains the software from the Internet or DVD and automatically starts the installation program after prompting about updates. From the web, the software is downloaded. A wizard opens. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3-55...
  • Page 116: Add Device To Software

    You connect remotely to the T60 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup software. The T60 also can be accessed locally with a computer through the front panel RS232 or USB port or the rear Ethernet port using the Quick Connect feature.
  • Page 117: Set Ip Address In Ur

    Online Window area, cannot be moved from it to another grouping, and needs to be renamed in the Device Setup window. GE instead recommends using the Device Setup window to add devices, as outlined here. 3.7.1 Set IP address in UR The IP and subnet addresses need to be added to the UR for Ethernet communication.
  • Page 118 ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION connections window. Or in Windows 7, access the Network and Sharing Center in the Control Panel. Right-click the Local Area Connection icon and select Properties. 3-58 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 119 Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the T60 relay and the last number different (in this example, 1.1.1.2).
  • Page 120 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: verify the physical connection between the T60 and the computer, and double-check the programmed IP address in setting, then repeat step 2. PRODUCT SETUP  COMMUNICATIONS  NETWORK  IP ADDRESS...
  • Page 121 Click the Quick Connect button to open the window. Select the Ethernet interface and enter the IP address assigned to the T60, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...
  • Page 122: Configure Serial Connection

    For the RS232 connection, a computer with an RS232 port and a serial cable are required. To use the RS485 terminals at the back of the relay, a GE Grid Solutions F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 123 Processor, such as an SEL-2030 or SEL-2032. This option enables display of a terminal window to allow interaction with the other device. Click the Read Order Code button to connect to the T60 and upload the order code to the software. If a communications error occurs, ensure that the EnerVista software serial communications values entered in the previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to multiple T60 ports.
  • Page 124: Configure Ethernet Connection

    10. If using a gateway to connect to the device, select Yes from the drop-down list. 11. Click the Read Order Code button to connect to the T60 device and upload the order code. If the device was entered already, a message displays "Device ’x’ is also using IP address.." If a communications error occurs, ensure that the...
  • Page 125: Configure Modem Connection

    12. Click the OK button when the relay order code has been received. The new site and device are added to the Online Window. The device has been configured for Ethernet communications. Proceed to the Connect to the T60 section to begin communications.
  • Page 126: Connect To The T60

    When unable to connect because of an "ACCESS VIOLATION," access Device Setup and refresh the order code for the device. When unable to connect, ensure that the same IP address is not assigned to multiple T60 ports, for example under Settings > Product Setup > Communications > Network.
  • Page 127: Use Quick Connect Via Front Rs232 Port

    View the T60 protection summary • View all of the T60 metering values • View the status of all T60 inputs and outputs • Generate a service report 3.8.2 Use Quick Connect via front RS232 port This feature applies to the enhanced and standard front panels.
  • Page 128: Use Quick Connect Via Front Usb Port

    Click the Quick Connect button to open the window. Select the USB Interface and the "GE Virtual Serial Port" driver from the drop-down list, then click Connect. If the GE driver does not display, it means that the USB cable was connected on Windows 10 when upgrading the UR software.
  • Page 129: Set Up Cybersentry And Change Default Password

    Connect" and displays them in the Online Window. Expand the sections to view data directly from the T60 device. Use the Device Setup button to change the site name. Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to the T60.
  • Page 130: Import Settings

    URS — When not IEC 61850 and version is lower than 7.30, the file is added and time stamp is unchanged. When clicking in the software on the tree element, a device folder is created, the original file moves into it, and time stamp is on the URS file is retained. 3-70 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 131: Connect To D400 Gateway

    3.11 Connect to D400 gateway A GE Multilin D400 Substation Gateway can be used to collect data from UR devices in a local area network (LAN). It collects metering, status, event, and fault report data from serial or LAN-based intelligent substation devices, and it pre-processes the data.
  • Page 132: Setting Files

    These are the configuration/settings files in the IEC 61850 SCL/IID format. The ur.iid file is saved with a "_YYMMDDhhmmss" retrieval time stamp, for example ur_170525183124.iid. It is stored in the D400 folder system using the UR site and device name. 3-72 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 133: Interfaces

    The EnerVista UR Setup software is provided with every T60. This chapter outlines the EnerVista software interface. The EnerVista UR Setup help file in the software also provides details for getting started and using the software interface.
  • Page 134: Event Viewing

    IP Address IP Subnet Mask IP Routing When a settings file is loaded to a T60 that is in-service, the following sequence occurs: The T60 takes itself out of service. The T60 issues a UNIT NOT PROGRAMMED major self-test error.
  • Page 135: File Support

    Site list / online window area Settings list / offline window area Software windows, with common toolbar Settings file data view windows, with common toolbar Workspace area with data view tabs Status bar 10. Quick action hot links T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 136: Protection Summary Window

    4.1.6 Protection summary window The Protection Summary is a graphical user interface to manage elements, such as enabling and disabling them. Access it under Settings > Protection Summary. See the Settings chapter for information on use. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 137: Settings Templates

    The settings file template is now enabled and the file menus display in light blue. The settings file is now in template editing mode. To undo the action, select Template Mode > Remove Template. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 138 Figure 4-4: Settings template with all settings specified as locked Specify the settings to make viewable by clicking them. A setting available to view displays with a yellow background. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 139 4.1.7.3 Add password protection to a template GE recommends that templates be saved with password protection to maximize security. When templates are created for online settings, the password is added during the initial template creation step. It does not need to be added after the template is created.
  • Page 140 Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are shown. The effect of applying the template to the phase time overcurrent settings is shown as follows. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 141: Secure And Lock Flexlogic Equations

    EnerVista UR Setup is in EDIT mode. Specify the entries to lock by clicking them. The locked entries display a grey background as shown in the example. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 142 The effect of applying the template to the FlexLogic entries is shown here. Figure 4-10: Locking FlexLogic entries through settings templates The FlexLogic entries are also shown as locked in the graphical view and on the front panel display. 4-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 143 Actual Values > Product Info > Model Information, the inside front panel, and the rear of the device. Right-click the setting file in the Offline Window area and select the Edit Device Properties item. The window opens. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-11...
  • Page 144: Settings File Traceability

    When a settings file is transferred to a T60 device, the date, time, and serial number of the T60 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This information can be compared with the T60 actual values at any later date to determine if security has been compromised.
  • Page 145 • The transfer date of a settings file written to a T60 is logged in the relay and can be viewed in the EnerVista software or the front panel display. Likewise, the transfer date of a settings file saved to a local computer is logged in the EnerVista software.
  • Page 146 4.1.9.2 Online device traceability information The T60 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista online window as shown in the example.
  • Page 147: Front Panel Interface

    The enhanced front panel consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-programmable pushbuttons. The front panel is hinged to allow access to removable modules inside the chassis. The T60 enhanced front panel can be horizontal or vertical. The following figure shows the horizontal front panel.
  • Page 148 IEC 61850. The USB port connects to a computer with the EnerVista software and can be used to upgrade the relay and to transfer files and settings. The USB port is the square type B. 4-16 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 149: Front Panel Display

    The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the front panel or the LEDs. To view the front panel in EnerVista software: Click Actual Values > Front Panel, then any option. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-17...
  • Page 150 IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow. On pages other than the home page, the header displays the name of the page. The footer dynamically labels the Tab, or control, pushbuttons immediately below. Page content displays between the header and footer. 4-18 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 151 RESET button clears those messages that can be. Configure the home page in the software under Settings > Product Setup > Graphical Panel > Home Page. The menu does not display when there is no graphical front panel. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-19...
  • Page 152 Factory default names are SLD 1 to SLD 5. Pages that have no configured content have a blank Tab pushbutton label, and the Tab pushbutton does nothing. The label for the current page has a blue background. Figure 4-24: Toolbar options for single-line diagram 4-20 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 153 Figure 4-25: Single-line diagram of open circuit breakers Under Settings > System Setup > Switches and Breakers, enable and name the six switches and two breakers. Switch 6, M568G, has the A/3 Pole Opened setting on. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-21...
  • Page 154 Line Diagram Editor. Add the four switches for the top line by clicking the GE switch symbol in the toolbar, then clicking in the window. (If the UR device is not online, the software attempts to connect.) Right-click to edit properties. Rotate switches SW569 and SW5682 to 270 degrees.
  • Page 155 Figure 4-27: Single-line diagram on graphical front panel Press the Enable Control pushbutton. The side pushbutton labels display. Figure 4-28: Side pushbutton display on graphical front panel Press the CB523 breaker pushbutton. Its menu displays. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-23...
  • Page 156 To add a line component, click it in the toolbox, then click in the window. Double-click a line to open its properties window to set orientation. Figure 4-30: Line and bus crossover symbols 4-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 157 Each breaker and disconnect component can be configured to use UR-style symbols, IEC symbols, or simple square/slash symbols as shown in the following figure. The symbols assume horizontal symbol orientation, red - closed color, and green - open scheme. With vertical orientation, they are rotated 90 degrees. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-25...
  • Page 158 (horizontal or vertical), color scheme (red - closed, or red - open), and assigned side button (if any). If the selected breaker or disconnect element does 4-26 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 159 A question mark displays in a symbol on the graphical front panel when status is bad. The question mark does not rotate with orientation. Figure 4-34: Symbols when status is bad The following figures show the orientation available for the static components. The default position is 0 degrees. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-27...
  • Page 160 FRONT PANEL INTERFACE CHAPTER 4: INTERFACES Figure 4-35: Single-line diagram static symbol orientation (sheet 1 of 2) 4-28 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 161 User-programmable pushbuttons 9 to 16 can be programmed among the 10 pushbuttons on the left and right sides of the screen display. They show dynamically and provide a means to perform the same control as the other pushbuttons. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-29...
  • Page 162 To add a metering component, click the M symbol in the toolbox, then click in the window. Drag it to its final location. Double-click it to open the properties window. The figure shows the properties that can be edited. 4-30 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 163 Self Reset, so the alarm displays in a solid color. The blue alarm type is Acknowledgeable, so the alarm flashes until it is acknowledged, for example by navigating with the arrow keys and pressing the ENTER button. The alarm then remains blue until the trigger condition is eliminated. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-31...
  • Page 164 FlexLogic operand. The self-reset mode alarm sequence conforms to ISA-18.1-1979 (R2004) standard type A 4 5 6. Figure 4-40: Annunciator alarm sequence in Self Reset mode 4-32 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 165 An alarm remains in an alarm state (for example, displays red) when the condition remains. That is, if you acknowledged a flashing alarm but the alarm condition remains, the background color remains red. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-33...
  • Page 166 The three page layouts (3 × 4, 4 × 6, and 6 × 8) select the number of rows x columns of windows that appear in a page. Annunciator window size and text size shrink as the number of annunciator windows in a page increases. 4-34 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 167 Content to display is configured with the cell lines. The content can be actual values, a status indicator, or text. • Actual value — Select from the FlexAnalogs applicable to the T60, where a FlexAnalog is an analog parameter T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 168 Save — Updates the connected device if online or the open setting file if offline with changes made • Restore — Undoes changes that have not been saved • Default — Changes all settings in the window to factory default values 4-36 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 169: Front Panel Navigation Keys

    ESCAPE — If a setting is open for edit, this pushbutton closes the setting without saving. If a popup menu is open, this pushbutton closes it. If an item is selected, this pushbutton deselects it. Otherwise this pushbutton activates the previous page in the page hierarchy. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-37...
  • Page 170: Led Indicators

    IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, and the relay is in (online) Programmed mode (under Settings > Product Setup > Installation) 4-38 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 171 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label package of every T60, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 172 PHASE A — Indicates phase A was involved • PHASE B — Indicates phase B was involved • PHASE C — Indicates phase C was involved • NEUTRAL/GROUND — Indicates that neutral or ground was involved 4-40 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 173 Figure 4-50: LED panel 2 (default labels) 4.2.4.3 Graphical front panel The graphical front panel has 14 LEDs. LEDs 1 to 5 are fixed status LEDs, and LEDs 6 to 14 are programmable. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-41...
  • Page 174 OTHER — LED 10 — Indicates a composite function was involved • PHASE A — LED 11 — Indicates phase A was involved • PHASE B — LED 12 — Indicates phase B was involved 4-42 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 175: Front Panel Labelling

    NEUTRAL/GROUND — LED 14 — Indicates that neutral or ground was involved 4.2.5 Front panel labelling 4.2.5.1 Enhanced front panel The following procedure requires these pre-requisites: • The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded from http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed • Small-bladed knife To create custom LED and pushbuttons labels for the enhanced front panel: Start the EnerVista UR Setup software.
  • Page 176 CHAPTER 4: INTERFACES Use the tool with the printed side containing the GE part number facing the user. The label package shipped with every T60 contains the three default labels, the custom label template sheet, and the label removal tool.
  • Page 177 Slide the label tool under the LED label until the tabs snap out as shown. This attaches the label tool to the LED label. Remove the tool and attached LED label as shown. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-45...
  • Page 178 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown. To remove the user-programmable pushbutton labels from the T60 front panel and insert the custom labels: Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent tab points away from the relay.
  • Page 179 To create LED and pushbutton labels for a standard front panel: In the EnerVista software, if the T60 is not already listed in the Offline Window area, add it by right-clicking it and selecting the Add Device to Offline Window option.
  • Page 180 4.2.5.3 Graphical front panel The T60 includes software for labelling the LEDs and pushbuttons on the graphical front panel and a sticker sheet with pre- printed and blank labels. The pre-printed labels are on the top-left of the template sheet, and the blank labels are on the bottom-right.
  • Page 181: Menu Navigation

    Use the down, right, left, and up arrows to navigate the menu. The up and down arrow keys move within a group of headers, sub-headers, setting values, or actual MESSAGE T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-49...
  • Page 182 The Page Up and Page Down Tab pushbuttons also navigate through the list. When there is only a single page of options, they jump to the first and last entries. The options displayed depend on order code. 4-50 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 183: Change Settings

    This flash message momentarily appears as confirmation of the storing process. Numerical values that contain decimal places are rounded-off if more decimal place digits are entered than specified by the step value. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-51...
  • Page 184 An example is a confirmation message upon saving settings. This setting specifies how long to display the message. Press the Menu pushbutton to display the main menu. 4-52 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 185 Figure 4-56: Main menu Use the Up or Down pushbutton to select SETTINGS, then press the Right or ENTER pushbutton. Figure 4-57: Settings menu With PRODUCT SETUP selected, press the Right or ENTER pushbutton. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-53...
  • Page 186 Pressing the ENTER pushbutton with the - key selected inverts the sign. Pressing the ENTER pushbutton with the decimal point selected enters that character at the insertion point. Push ENTER now to accept the 4. 4-54 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 187 To add accents, highlight a key and hold the ENTER pushbutton on the graphical front panel. Any special characters associated with the key display. Figure 4-61: Settings page with keyboard and accents T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-55...
  • Page 188: View Actual Values

    Phasor pages that have no configured CTs or VTs do not have a Tab pushbutton, and phasor pages that have no configured cells cannot be displayed. Figure 4-62: Phasor display The configurable name displays in the header and Tab pushbutton label. Factory default names are Page 1, Page 2, and so 4-56 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 189: Breaker Control

    4.2.9 Breaker control The T60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on front panel LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from the front panel keypad or automatically initiated from a FlexLogic operand.
  • Page 190: Change Passwords

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the T60, the remote password must be used. If the connection is to the RS232 port of the front panel, the local password must be used.
  • Page 191: Invalid Password Entry

    By default, when an incorrect Command or Setting password has been entered via the front panel three times within five minutes, the FlexLogic operand is set to “On” and the T60 does not allow settings or command level LOCAL ACCESS DENIED access via the front panel for five minutes.
  • Page 192: Logic Diagrams

    Not. Negates/reverses the output, for example 0 becomes 1.  Connection  S, R Set, Reset Timer pickup. Triggered by the settings latch in the diagram. Timer reset. Triggered by the reset latch in the diagram. 4-60 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 193: Flexlogic Design Using Engineer

    Works with all UR firmware versions The figure shows an example where several inputs are used to trigger an output. With the OR function, any one of the inputs can trigger the output. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-61...
  • Page 194 This section explains how to use Engineer. It outlines the following topics: • Design logic • Send file to and from device • Monitor logic • View front panel • Generate connectivity report • Preferences 4-62 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 195: Design Logic

    Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual outputs 3 and 4 are named DLTrigger Top logic — Seven-minute timer trigger Bottom logic — Turn on LED 9 for 10 seconds when the trigger starts T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-63...
  • Page 196 This procedure uses input / output logic as an example. To create a logic diagram: In the Offline Window area, access Engineer for the device, then Logic Designer. If the device is not listed, right-click 4-64 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 197 Optionally delete the default logic diagram by right-clicking its tab at the bottom of the window and selecting Delete. To add a blank sheet, click Edit > Add Sheet. A new tab displays. Or use the last tab displayed, which is a blank sheet. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-65...
  • Page 198 Line option. The cursor needs to be at the connection point to end the line, not elsewhere on the block. Note that the outline color is no longer red on the blocks. 4-66 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 199 The warning "input using disabled feature" means that input needs to be enabled. Double-click the block, click the View Associated Screen button, enable the setting, save, and recompile. The output and messages are explained in the next section. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-67...
  • Page 200 IEC 61850 panel and thereby become synchronized. The CID file and the IID file (depending on the preference 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated. 4-68 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 201 FLEXLOGIC DESIGN USING ENGINEER The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders. Any FlexLogic equations entered in the Offline Window area are erased. The logic drawn in the Logic Designer window in Engineer in the Offline Window area remain.
  • Page 202 Click the Ok button to save and exit from the window. In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, and so on. 4-70 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 203 Optimization Summary. Changes also display when the FlexLogic Equation Editor is accessed. The logic diagram does not change. In the example shown, no lines were saved to free up space. Figure 4-81: Code optimization results T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-71...
  • Page 204 Type in the second text string box, or select any of the 32 previous searches from the drop-down list. Click the Search button. Any results display. The search applies to all tabs, not just the active tab. Double-click a search result to view the item. 4-72 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 205: Send File To And From Device

    When a window opens, select the device to which you want to send the file, then click the Send button and confirm. The order codes must match. The file is sent to the live device. Any errors can be viewed in the log file at the prompt. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-73...
  • Page 206: Monitor Logic

    (green box outline). In this case, the battery is weak and needs to be replaced. This can be viewed as the Replace Battery message on the front panel of the device and in the EnerVista software under Actual Values > Front Panel > Front Panel or Display/Keypad. 4-74 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 207: View Front Panel And Print Labels

    To save the report and labels, click File > Save As, enter a file name, and select the FPR, JPG, or PDF format. Use the instructions in the second tab of the window to add the labels to the physical device. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-75...
  • Page 208: Generate Connectivity Report

    View > Toolbar > Advanced Actions — Active when in Logic Designer. Toggles a toolbar to nudge, rotate, flip, or change the order of an element. View > Show Unused Pins — Enable to display unconnected pins. Disable to eliminate unconnected pins from the view, for example when printing. 4-76 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 209 File Information The text entered here displays at the bottom right of a diagram when printing, provided that the Show Title Block option is enabled. Note the option to change the logo from the GE logo to your company logo. Display The panel sets how the element boxes display.
  • Page 210 The software displays the color specified when an element is on. There is no color when the element is off. The software displays another color when the status cannot be determined and is unknown. 4-78 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 211 Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status. 4.4.6.4 COMTRADE waveforms Waveform files are viewable in the EnerVista software. The preferences are unrelated to Engineer and are outlined in the UR Family Communications Guide. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-79...
  • Page 212: Toolbars

    When you re-launch the EnerVista software, communication is on by default. 4.4.7.2 Token Toolbox Drawing Tools Draw a line. Click and drag to draw. Draw multiple joined lines. Click and drag for each line. Double-click to finish. 4-80 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 213 Remote inputs from other devices Input from another UR device. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-81...
  • Page 214 Tag-In can is used to reference an existing Tag-Out. It joins another diagram to a previous diagram. Boolean Tokens These symbols are used to create FlexLogic Equations. Use them as intermediate logic for the Virtual Output equations. The display can vary from that shown here. 4-82 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 215 Place a positive one shot and a negative one shot symbol in the Logic Designer diagram Place a timer in the Logic Designer diagram Elements These blocks configure properties of the element or use element operands as input to FlexLogic equations. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-83...
  • Page 216 Set the width of the selected components to the same width as the reference component Same Height Set the height of the selected components to the same height as the reference component 4-84 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 217 Front, Back Moves current components to the absolute front or back of all viewable layers Forward, Backward Moves current components on layer higher or lower than its original layer hierarchy T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-85...
  • Page 218 FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES 4-86 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 219: Settings

     MODBUS USER MAP See page 5-109    REAL TIME See page 5-110   CLOCK  USER-PROGRAMMABLE See page 5-114   FAULT REPORT  OSCILLOGRAPHY See page 5-115   T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 220 See page 5-218   FLEXLOGIC  EQUATION EDITOR  FLEXLOGIC See page 5-218    TIMERS  FLEXELEMENTS See page 5-218    NON-VOLATILE See page 5-222    LATCHES T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 221    RESETTING See page 5-368    DIRECT INPUTS See page 5-369    DIRECT OUTPUTS See page 5-370    TELEPROTECTION See page 5-373    T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 222: Overview

    For example, if CT1 = 300 / 5 A and CT2 = 100 / 1 A, then in order to sum these, CT2 is scaled to the CT1 ratio. In this case, the base quantity is 300 A primary, 5 A secondary for CT1, and 300/(100/1) = 3 A secondary for CT2. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 223 Not every operand of a given element in a UR relay generates events, only the major output operands. Elements, asserting output per phase, log operating phase output only, without asserting the common three-phase operand event. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 224: Introduction To Ac Sources

    For example, in the scheme shown in the preceding figure, the user configures one source to be the sum of CT1 and CT2 and can name this source as “Wdg1 I.” T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 225: Product Setup

    (as described earlier) as follows for a maximum configuration: F1, F5, M1, M5, U1, and U5. 5.3 Product setup 5.3.1 Security 5.3.1.1 Security overview The following security features are available: • Password security — Basic security present by default T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 226 To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.
  • Page 227 When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the T60, the remote password must be used. If the connection is to the RS232 port of the front panel, the local password must be used.
  • Page 228 When an original password has already been used, enter it in the Enter Password field and click the Send Password to Device button. Re-enter the password in the Confirm Password field. 5-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 229 INVALID ATTEMPTS BEFORE LOCKOUT The T60 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 230 ACCESS AUTH TIMEOUT immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer updates every five seconds. 5-12 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 231 It is disabled by default to allow access to the device immediately after installation. When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before placing the device in service. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 232 If you force password entry by using this feature, ensure that you know the Administrator password. If you do not know the password and are locked out of the software, contact GE Grid Solutions for the default password of a UR device.
  • Page 233 The EnerVista security management system must be enabled (the Enable Security check box enabled) To modify user privileges: Select the Security > User Management item from the top menu to open the user management window. Locate the username in the User field. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-15...
  • Page 234 This feature requires a CyberSentry software option. See the Order Codes section in chapter 2 for details. The EnerVista software provides the means to configure and authenticate the T60 access using either a server or the device. Access to functions depends on user role.
  • Page 235 When the "Device" button is selected, the T60 uses its local authentication database and not the RADIUS server to authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer, or Administrator and Supervisor when Device Authentication is disabled), as login accounts and the associated passwords are stored on the T60 device.
  • Page 236 Figure 5-3: Security panel when CyberSentry installed For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following. Figure 5-4: Supervisory panel For the Security panel, the following settings are available. 5-18 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 237 Administrator is to re-enable Device authentication when Device authentication is disabled. To re-enable Device authentication, the Supervisor unlocks the device for setting changes, and then the Administrator can re- enable Device authentication. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-19...
  • Page 238 LOGIN: Range: Administrator, Engineer, Supervisor,   None Operator, Factory (for factory use only), None  CHANGE LOCAL See page 5-21   PASSWORDS  SESSION See page 5-22   SETTINGS 5-20 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 239 • Observer — This role has read-only access to all T60 settings. This role allows unlimited concurrent access but it has no download access to any files on the device. Observer is the default role if no authentication has been done to the device.
  • Page 240 In Device authentication mode, the Observer role does not have a password associated with it. In Server authentication mode the Observer role requires a password. If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry, the default password is "ChangeMe1#".
  • Page 241 RS232 and RS485 connections. The default value is 1 minute. GE recommends setting this value to at least 3 minutes for the following scenario: while connected to a CyberSentry device, with serial or USB cable connected to the front panel, and performing "Add Device to Offline Window" or an online/ offline comparison.
  • Page 242 Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the authentication from the device. In the EnerVista software, choose Server authentication and log in using the user name and password configured on the RADIUS server for Server authentication login. 5-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 243 Clear Demand Records command (not applicable to all UR products) Clear Energy command (not applicable to all UR products) Clear Unauthorized Access command Clear Teleprotection Counters command (not applicable to all UR products) Clear All Relay Records command Role Log in T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-25...
  • Page 244: Display Properties

    Enumeration Description Role Log off In addition to supporting syslog, a T60 with CyberSentry also saves the security events in two local security files, these being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in the EnerVista software under Maintenance >...
  • Page 245 Some customers prefer very low currents to display as zero, while others prefer the current to display even when the value reflects noise rather than the actual signal. The T60 applies a cut-off value to the magnitudes and angles of the measured currents.
  • Page 246: Graphical Front Panel

    Use the EnerVista software to configure the graphical front panel. The settings are not accessible from the graphical front panel. The following screens are available: • Home page • Rolling mode • Metering editor • Single-line diagram editor • Annunciator editor • Configurable navigation 5-28 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 247 The "Annunciator" option without a page number specifies the first annunciator page in the following sequence: – The first annunciator page that contains an annunciator window that is in alarm (fast flash) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-29...
  • Page 248 Similarly, the display backlight intensity is lowered to a specified level; lower intensity extends the life of the display. Each rolling page displays for a few seconds; duration cannot be set. The path is Settings > Product Setup > Graphical Panel > Rolling Mode. 5-30 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 249 Range: 1 to 10 in steps of 1 Default: 1 This setting specifies the number of rolling pages. During rolling mode, the graphical front panel displays pages from 1 to the selected number. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-31...
  • Page 250 For a phasor diagram, configure the source under Settings > System Setup > Signal Sources. The diagram is then viewable by pushing the Metering Tab pushbutton on the graphical front panel. The Metering Editor is not used for these phasor diagrams. The figures show setup and table preview. 5-32 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 251 A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages. Select the metering input from the drop-down list. The options reflect the FlexLogic operands applicable to the T60. They are inputs for all five metering pages, not just the current page.
  • Page 252 Range: 16, 18, 20 Default: 16 Set the font size to display on the graphical front panel. TEXT COLOR Range: 24-bit color selector Default: Black Set the text color to display in the specified cell. 5-34 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 253 This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-35...
  • Page 254 Settings > Product Setup > User-Programmable Self Tests (not shown). When the alarms are triggered, they display with a red background. An alarm is acknowledged by using the arrow keys on the graphical front panel then pressing the ENTER button. 5-36 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 255 Up to 20 characters can be input as the name of each annunciator page. The number of pages depends on the Layout. The name displays for the Tab pushbutton on the graphical front panel. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-37...
  • Page 256 The background color to display for any triggered cell, for example when an alarm is triggered. ACTUAL (Configure) Range: Configure Default: Configure The Configure button becomes active when the CONTENT field is set to "Actual" or "Mixed." The window specifies the metering data to display. 5-38 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 257 Avoid selecting condition operands that are likely to operate simultaneously but activate different pages, as only one page can be opened at a time. For example, do not select a single-line diagram page for breaker status open and select an annunciator page for a trip alarm. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-39...
  • Page 258: Clear Relay Records

    The Targets option displays error messages, such as wrong transceiver, similar to event record entries. 5.3.4 Clear relay records SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS  CLEAR RELAY CLEAR USER REPORTS: Range: FlexLogic operand   RECORDS 5-40 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 259: Communications

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user- programmable pushbuttons to clear specific records is a typical application for these commands. Since the T60 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 260 5.3.5.2 Serial ports The T60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is for local use and is fixed at 19200 baud and no parity. The rear COM2 port is used for either RS485 or RRTD communications.
  • Page 261 5.3.5.3 Ethernet network topology The T60 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND operation performed between their respective IP address and mask produces a different result.
  • Page 262 SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 is the redundant channel. In this configuration, P3 uses the IP and MAC addresses of P2. Figure 5-14: Multiple LANs, with redundancy 5-44 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 263 IP addresses and mask. Configure the network IP and subnet settings before configuring the routing settings. To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating information, such as the serial number and order code of your device.
  • Page 264 2 is performed. The delay in switching back ensures that rebooted switching devices connected to the T60, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.
  • Page 265 UR 7 redundancy Failover is selected for redundancy. 5.3.5.6 Parallel Redundancy Protocol (PRP) The T60 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 266 The default route is used as the last choice when no other route towards a given destination is found.  DEFAULT IPv4 ROUTE GATEWAY ADDRESS: Range: standard IPV4 unicast address format   127.0.0.1  IPv4 NETWORK RT1 DESTINATION: Range: standard IPV4 address format   ROUTE 1 127.0.0.1 5-48 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 267 (RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) == (Prt3IP & Prt3Mask) where & is the bitwise-AND operator == is the equality operator || is the logical OR operator T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-49...
  • Page 268 PRT2 IP ADDRESS = 10.1.2.2 PRT2 SUBNET IP MASK = 255.255.255.0 IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1 STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATEWAY = 10.1.2.1 5-50 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 269 0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change takes effect when the T60 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
  • Page 270 The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the RS232, RS485, and Ethernet ports. It shows all possible combinations of the settings. PROTOCOL DNP CHANNEL 1(2) PORT 5-52 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 271 DNP UNSOL RESPONSE Range: 0 to 65519 in steps of 1  DEST ADDRESS: 1 DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,  FACTOR: 1 100000, 1000000, 10000000, 100000000 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-53...
  • Page 272 Range: 0 to 32 in steps of 1  CONTROL POINTS: 0 DNP TCP CONNECTION Range: 10 to 7200 s in steps of 1  TIMEOUT: 120 s DNP EVENT TIME BASE: Range: UTC, LOCAL  LOCAL 5-54 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 273 DNP ADDRESS unique address to each DNP slave. The T60 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which the T60 can connect. The settings follow. SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP NETWORK CLIENT ADDRESSES ...
  • Page 274 DNP TCP connection for greater than the time specified by this setting, the connection is aborted by the T60. This frees up the connection to be re-used by a client. For any change to take effect, restart the relay.
  • Page 275 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. 5.3.5.12 IEC 61850 protocol The T60 is provided with optional IEC 61850 communications. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 276 The maximum number of simultaneous clients supported by the UR family is five. EnerVista setup for IEC 61850 The EnerVista UR Setup software provides the interface to configure T60 settings for the IEC 61850 protocol. This section describes this interface. The software also supports import/export and merging of IEC 61850 Substation Configuration Language (SCL) files as documented in the UR Family Communications Guide.
  • Page 277 Figure 5-19: IEC 61850 panel Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the T60. This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those that are mapped into the IEC 61850 information model (that is, the "public"...
  • Page 278 When the Save button is clicked in the online IEC 61850 window, UR Setup software prepares a configured IED description (CID) file containing all the settings of the UR and sends the CID file to the T60. Upon receipt, the T60 checks the CID file for correctness, going out of service, then back into service when the CID file is accepted.
  • Page 279 Range: status-only, direct-with-normal-security, sbo-with-normal-security Default: sbo-with-normal-security This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the T60. An "on" control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to Forcible, and a "test/blocked"...
  • Page 280 The LLN0 in the Master logical device, which includes setting group, GOOSE and report control blocks, and datasets • LPHD1 — Models common issues for physical devices • GGIO1 — For unmapped FlexLogic operands 5-62 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 281 Figure 5-23: Menu for logical node If the insert option is selected, or the edit option is selected for other than the Master logical device, a logical device parameters edit dialog opens. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-63...
  • Page 282 Each logical device inst name is required to be unique within the device, and it cannot be blank. Also, if the corresponding functional ldName setting is blank, the concatenation of the IED name and the logical device 5-64 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 283 The UR increments the value of paramRev by one whenever one or multiple setting changes occurs in one Modbus write request by any means (front panel, Modbus, or MMS) other than by SCL file T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-65...
  • Page 284 A v7.4 device can send an R-GOOSE message to another v7.4 device when both have R-GOOSE active as the protocol • A v7.4 device can send a GOOSE message to another v7.4 device when both have GOOSE active as the protocol 5-66 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 285 Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > TxGOOSE1 to access the settings for the first TxGOOSE. The settings and functionality for the others are similar. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-67...
  • Page 286 Range: 0 to 129 VisibleString characters Default: TxGOOSE1 The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate the TxGOOSE1 messages from other GOOSE messages. 5-68 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 287 VID values of 0 and 1 are assigned by IEEE 802.1Q to other functions and are not to be used for GOOSE. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-69...
  • Page 288 Also, Port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP elements has no meaning, as ports 2 and 3 use the port 2 MAC address, IP address, and mask. 5-70 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 289 (test field in edition 1.0 messages) are accepted only when the UR Test Mode Function setting is set to Forcible or Isolated. RxGOOSE messages can be received through any UR Ethernet port. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-71...
  • Page 290 RxGOOSE1 messages. An entered address of zero disables RxGOOSE1. If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE DST MAC setting. 5-72 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 291 <GoCBName> is the name of the publishing control block. The T60 translates the ACSI format required for this setting to the MMS format used in GOOSE messages: <LDName>/LLN0$GO$<GoCBName> If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master".
  • Page 292 7.40 UR Setup RxGOOSE Inputs pages. In this case the Member setting displays as the product-related name used by the publishing IED of the data object or data attribute, in standard SCSM format (e.g. Publisher1LD1/LLN0$ST$Off$stVal). 5-74 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 293 (supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The figure shows a selection being made by importing a CID file using the Add IED function. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-75...
  • Page 294 This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the publisher. The following choices are available: 5-76 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 295 Range: None, RxGOOSE1, RxGOOSE2, and so on Default: None This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to None, the RxGOOSE DPS1 FlexLogic operand assumes its default state. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-77...
  • Page 296 (supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. Figure 5-31: RxGOOSE Analog Inputs panel There are 32 RxGOOSE analog inputs. 5-78 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 297 Range: 0.000 to 1000000000.000 in steps of 0.001 Default: 1.000 This setting specifies the per-unit base value for other T60 features to use with the RxGOOSE Analog1 operand. A FlexElement for instance subtracts two quantities after converting their values to integers rescaled to a common base, the common base being the largest of the base values of the two quantities.
  • Page 298 RptEna attribute is false. Buffered and unbuffered reports Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports or Unbuffered Reports. 5-80 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 299 Also, the control block can be configured to send integrity reports containing the present value of all members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not read and acknowledged by the client to be retransmitted. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-81...
  • Page 300 Control blocks and data sets can be pre-configured by sending the T60 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to select the data set members and to pre-configure the control blocks.
  • Page 301 This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as described later. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-83...
  • Page 302 DataSets Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets. 5-84 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 303 The DataSet name is not copied or pasted. In short, use this feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-85...
  • Page 304 Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert. Product setup Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup. 5-86 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 305 Deadband parameters of measured values related to the Energy metering are configured here. Real Time Clock Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Real Time Clock. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-87...
  • Page 306 The analog value that each deadband setting applies is usually obvious from the name of the setting. However, a tabulation of the analog values and their associated deadband setting can be found in the UR Family Communications Guide. 5-88 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 307 Auxiliary voltage — 275 x auxiliary VT ration setting • Power (real, reactive, apparent, 3-phase, and 1-phase) — 4 × phase CT primary setting × 1.5 × VT Secondary setting × VT ratio setting T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-89...
  • Page 308 While the selected operand is asserted, Bkr0XCBR1.Loc.stVal is true and IEC 61850 commands to BkrCSWI1.Pos and Bkr0XCBR1.Pos are not accepted, and a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by- switching-hierarchy. 5-90 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 309 Bkr0XCBR1.BlkOpn.ctlVal signal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings > System Setup section later. This signal when true blocks breaker 1 trip control while the operand selected by setting XCBR1 ST.LOC OPERAND is not active. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-91...
  • Page 310 Navigate to Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1 to access the settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoring element. The settings and functionality for the others are similar. 5-92 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 311 > System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by setting XSWI1 ST.LOC OPERAND is not active. "sbo" here is select-before-operate. Enhanced security means that the T60 reports to the client the disconnect switch 1 position the end of the command sequence.
  • Page 312 SelectEditSG. The setting related to these IEC 61850 commands are described here. Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access the setting that configures the IEC 61850 setting group commands. 5-94 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 313 Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings that configure the IEC 61850 protocol interface for record clear commands. Figure 5-43: Commands panel T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-95...
  • Page 314 This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo" here is select-before-operate. Enhanced security means that the T60 reports to the client the breaker 1 position at the end of the command sequence.
  • Page 315 Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that configure the IEC 61850 protocol interface for Virtual Input commands. Figure 5-45: GGIO2 panel T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-97...
  • Page 316 <LDName>/GGIO4.AnIn01.instMag.f. The value of the FlexAnalog operand is converted automatically to the format and scaling required by the standard, that is to say primary amperes, primary volts, and so on. See Appendix A for a list of FlexAnalog operands. 5-98 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 317 File transfer by IEC 61850 The T60 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 318 NUMBER(80): 80 The T60 contains an embedded web server and can display pages in a web browser. The web pages are organized as a series of menus that can be accessed starting at the T60 “Main Menu.” Web pages are read-only and are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on.
  • Page 319 NUMBER: 0 The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the T60 over a network. The T60 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the T60 contains a list and description of all available files, for example event records and oscillography.
  • Page 320 COMMUNICATIONS  PROTOCOL connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the T60 maintains two sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the T60 at one time.
  • Page 321 PRODUCT SETUP The T60 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the T60 can connect. A maximum of two simultaneous connections are supported at any given time.
  • Page 322 EXCH 1 DATA ITEM 1 to 20/50 from the T60 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format. See the Modbus memory map in the UR Series Communications Guide for details.
  • Page 323 PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and none of IRIG-B, PTP, or SNTP is active, the T60 sets the invalid bit in the time stamp of a time-tagged message.
  • Page 324 Spontaneous transmission occurs as a response to cyclic Class 2 requests. If the T60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the control field of the response).
  • Page 325 FlexAnalog operands. The measurands sent are voltage, current, power, power factor, and frequency. If any other FlexAnalog is chosen, the T60 sends 0 instead of its value. Note that the power is transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I, respectively measurands II).
  • Page 326 Range: Virtual input  COMMAND 31 OFF: Range: Virtual input  Commands are received as General Command (Type Identification 20). The user can configure the action to perform when an ASDU command comes. 5-108 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 327: Modbus User Map

    CHAPTER 5: SETTINGS PRODUCT SETUP A list of available mappings is provided on the T60. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.
  • Page 328: Real-Time Clock

    Setup for IRIG-B is illustrated in the Installation chapter. For the Other protocols, whenever a time synchronization message is received through any of the active protocols, the T60 clock updates. However, given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low-accuracy time synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP, are active in the system.
  • Page 329 See the Order Codes section in chapter 2 for details. The T60 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network that implements PP.
  • Page 330 When a clock on start-up discovers that it is “better” than the present grandmaster, it assumes the grandmaster role and the previous grandmaster reverts to slave. The T60 qualification mechanism accepts a potential master clock as a new grandmaster, when in a four-second interval it has received three announce messages from it, all better than the present grandmaster clock and better than any other announce in this interval.
  • Page 331 T60 clock is closely synchronized with the SNTP/ NTP server. It takes up to two minutes for the T60 to signal an SNTP self-test error if the server is offline.
  • Page 332: User-Programmable Fault Report

     2:00 The T60 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B signals. UTC time is provided by SNTP servers. The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if the Local Time settings are not configured properly.
  • Page 333: Oscillography

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (x.xx, for example) and relay model (T60), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 334 — This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of DIGITAL 1(63) CHANNEL each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. 5-116 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 335: Data Logger

    Analog channel 23 ↔ 25th harmonic 5.3.10 Data logger SETTINGS  PRODUCT SETUP  DATA LOGGER  DATA LOGGER DATA LOGGER MODE: Range: Continuous, Trigger   Continuous DATA LOGGER TRIGGER: Range: FlexLogic operand  T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-117...
  • Page 336 This setting only applies when the mode is set to “Trigger.” — This setting selects the time interval at which the actual value data is recorded. DATA LOGGER RATE 5-118 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 337: Demand

    The figure shows the 90% thermal response time characteristic of 15 minutes. A setpoint establishes the time to reach 90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the response time indicates 99% of the value. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-119...
  • Page 338: User-Programmable Leds

    See below   LEDS   TRIP & ALARM LEDS See page 5-123    USER-PROGRAMMABLE See page 5-123   LED 1   USER-PROGRAMMABLE   LED 48 5-120 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 339 Additionally, stages 2 and 3 are repeated twice for the five device status LEDs and nine event cause LEDs, one time with green color on and the other with red color on. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-121...
  • Page 340 Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS  menu: PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST : “Enabled” LED TEST FUNCTION “PUSHBUTTON 1 LED TEST CONTROL ON” 5-122 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 341 “Latched,” the LED, once lit, remains so until reset by the front panel button, from a remote device via a RESET communications channel, or from any programmed operand, even if the LED operand state de-asserts. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-123...
  • Page 342 Event Cause LED 7 LED PHASE B EVENT CAUSE LED 7 Orange Event Cause LED 8 LED PHASE C EVENT CAUSE LED 8 Orange Event Cause LED 9 LED NEUTRAL/GROUND EVENT CAUSE LED 9 Orange 5-124 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 343: User-Programmable Self-Tests

    These are user-programmable and can be used for various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-programmable displays. The location of the control pushbuttons are shown in the following figures. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-125...
  • Page 344 CHAPTER 5: SETTINGS Figure 5-52: Control pushbuttons (enhanced front panel) An additional four control pushbuttons are included on the standard front panel when the T60 is ordered with the 12 user- programmable pushbutton option. Figure 5-53: Control pushbuttons (standard front panel) Control pushbuttons are not typically used for critical operations and are not protected by the control password.
  • Page 345: User-Programmable Pushbuttons

     EVENTS: Disabled The T60 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The number depends on the front panel ordered.
  • Page 346 Figure 5-56: User-programmable pushbuttons (standard front panel) Figure 5-57: User-programmable pushbuttons (graphical front panel) Front panel pushbuttons and LEDs can be custom labelled as outlined in the Front Panel Labelling section in the previous chapter. 5-128 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 347 — This setting selects the mode of the pushbutton (Self-Reset, Latched, Disabled). If set to PUSHBUTTON 1 FUNCTION “Disabled,” the pushbutton is not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If set to "Latched," the pushbutton remains on until reset. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-129...
  • Page 348 "Latched" mode the off message displays when the user-programmable pushbutton becomes deactivated. When set to "Normal", the duration the message displays is as specified by the setting. FLASH MESSAGE TIME 5-130 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 349 — If this setting is enabled, each user-programmable pushbutton state change is logged as an PUSHBUTTON 1 EVENTS event into the event recorder. The figures show the user-programmable pushbutton logic. Figure 5-58: User-programmable pushbutton logic (Sheet 1 of 2) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-131...
  • Page 350: Flex State Parameters

    The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256 state bits. 5-132 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 351: User-Definable Displays

    When this type of entry occurs, the sub-menus are automatically configured with the proper content—this content can be edited subsequently. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-133...
  • Page 352 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. 5-134 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 353: Direct Inputs And Outputs

    DIRECT OUTPUT DEVICE ID messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of the direct input and output message. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-135...
  • Page 354 DIRECT I/O DATA RATE setting applies to a T60 with dual-channel communication cards and allows crossing DIRECT I/O CHANNEL CROSSOVER over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network regardless of the physical media of the two communication channels.
  • Page 355 DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 2: DIRECT OUTPUT DEVICE ID: “2” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 3: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-137...
  • Page 356 Figure 5-63: Three-terminal line application A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2 constitute a first ring, while IEDs 2 and 3 constitute a second ring). 5-138 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 357 In this application, apply the following settings. For UR-series IED 1: DIRECT OUTPUT DEVICE ID: “1” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 2: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-139...
  • Page 358 EVENTS: Disabled The T60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 359: Teleprotection

     EVENTS: Disabled The T60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unreturned messages.
  • Page 360: Remote Resources

    5.4 Remote resources 5.4.1 Remote resources configuration When the T60 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
  • Page 361 Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the T60 process card and specific Brick. The relay is then configured to measure specific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 362: System Setup

    The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5.5.1.2 Voltage banks SETTINGS  SYSTEM SETUP  AC INPUTS  VOLTAGE BANK F5(U5)  VOLTAGE BANK F5 PHASE VT F5 Range: Wye, Delta   CONNECTION: Wye 5-144 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 363: Power System

    PHASE ROTATION sequence, either ABC or ACB. CT and VT inputs on the relay, labelled as A, B, and C, must be connected to system phases A, B, and C for correct operation. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-145...
  • Page 364: Signal Sources

    FREQUENCY TRACKING frequency applications. The frequency tracking feature functions only when the T60 is in the “Programmed” mode. If the T60 is “Not Programmed,” then metering values are available but can exhibit significant errors. Systems with an ACB phase sequence require special consideration. See the Phase Relationships of Three-phase Transformers section of chapter 5.
  • Page 365 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting ) controls the sensitivity of the disturbance detector PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL accordingly. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-147...
  • Page 366 8 CTs 4 CTs, 4 VTs 4 CTs, 4 VTs C60, D60, G30, G60, L30, L90, M60, T60 not applicable This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half system. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data.
  • Page 367: Transformer

    See page 5-160   The T60 provides primary protection for medium to high voltage power transformers. It is able to perform this function on two to five winding transformers in a variety of system configurations. 5.5.4.2 General transformer settings SETTINGS ...
  • Page 368 46 pu. If this happens, use manual selection of reference winding to avoid this. See the T35/T60 Reference Winding Selection and CT Ratio Mismatch Application Note (GET-8548) for information.
  • Page 369 WINDING 1 RATED MVA: Range: 0.001 to 2000.000 MVA in steps of 0.001  100.000 MVA WINDING 1 NOM φ-φ Range: 0.001 to 2000.000 kV in steps of 0.001  VOLTAGE: 220.000 kV T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-151...
  • Page 370  3φ: 10.0000 ohms The T60 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. The settings specific to each winding are shown in the table.
  • Page 371 The following example shows why this happens, using a transformer described in IEC nomenclature as a type “Yd1” or in GE Multilin nomenclature as a “Y/d30.” The example shows the physical connections within the transformer that produce a phase angle in the delta winding that lag the respective wye winding by 30°.
  • Page 372 Note that the delta winding currents leads the wye winding currents by 30°, (which is a type Yd11 in IEC nomenclature and a type Y/d330 in GE Multilin nomenclature) and which is in disagreement with the transformer nameplate. This is because the physical connections and hence the equations used to calculate current for the delta winding have not changed.
  • Page 373 Interposing CTs or tapped relay windings were used to minimize this error. The T60 automatically corrects for CT mismatch errors. All currents are magnitude compensated to be in units of the CTs of one winding before the calculation of differential and restraint quantities.
  • Page 374 The T60 performs this phase angle compensation and zero sequence removal automatically, based on the settings entered for the transformer. All CTs are connected Wye (polarity markings pointing away from the transformer). All currents are phase and zero sequence compensated internally before the calculation of differential and restraint quantities.
  • Page 375 CHAPTER 5: SETTINGS SYSTEM SETUP Table 5-19: Phase and zero sequence compensation for typical values of Φ comp T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-157...
  • Page 376 [w] = magnitude, phase, and zero-sequence compensated winding w phase currents M [w] = magnitude compensation factor for winding w (see previous sections) [w], I [w], and I [w] = phase and zero sequence compensated winding w phase currents (see earlier) 5-158 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 377 SYSTEM SETUP  SIGNAL settings menu. SOURCES  SOURCE 1(4) SOURCE 1 NAME: “WDG 1X” SOURCE 1 PHASE CT: “F1” SOURCE 1 GROUND CT: “None” SOURCE 1 PHASE VT: “None” SOURCE 1 AUX VT: “None” T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-159...
  • Page 378 TOP-OIL TEMPERATURE: Range: RTD Input 1, RTD Input 2,..., RTD Input 8, dcmA  Input 1, dcmA Input 2,..., dcmA Input 8, RRTD 1, RRTD2,..., RTD Input 1 RRTD 12, Monthly Average 5-160 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 379: Breakers

     3-Pole BREAKER 1 OPEN: Range: FlexLogic operand  BREAKER 1 BLK OPEN: Range: FlexLogic operand  BREAKER 1 CLOSE: Range: FlexLogic operand  BREAKER 1 BLK CLOSE: Range: FlexLogic operand  T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-161...
  • Page 380 1 control open/close status is forced to the substituted value. — Set to "Enable" to allow the graphical front panel to bypass breaker 1 interlocking. When asserted, BREAKER1 BYPASS settings are bypassed. BREAKER 1 BLK OPEN BREAKER 1 BLK CLOSE 5-162 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 381 If this setting is set to Off, the racked status is not considered. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-163...
  • Page 382 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-73: Dual breaker control logic (Sheet 1 of 3) 5-164 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 383 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-74: Dual breaker control logic (Sheet 2 of 3) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-165...
  • Page 384: Disconnect Switch Control

    Range: Disabled, Enabled   FUNCTION: Disabled SWITCH 1 NAME: Range: up to six alphanumeric characters  SW 1 SWITCH 1 MODE: Range: 3-Pole, 1-Pole  3-Pole SWITCH 1 OPEN: Range: FlexLogic operand  5-166 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 385 — This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary SWITCH 1 MODE switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-167...
  • Page 386 — This setting specifies the delay interval during which a disagreement of status among the pole SWITCH 1 ALARM DELAY position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the poles. 5-168 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 387 SYSTEM SETUP IEC 61850 functionality is permitted when the T60 is in “Programmed” mode and not in local control mode. The switch element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagrams. This allows remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes.
  • Page 388 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-77: Disconnect switch control status logic (sheet 2 of 3) 5-170 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 389: Flexcurves

    FlexCurve, enter the reset and operate times (using the keys) for each selected pickup point (using the VALUE up/down keys) for the required protection curve (A, B, C, or D). MESSAGE T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-171...
  • Page 390 The recloser curve configuration window shown here appears when the Initialize From setting in the EnerVista software is set to “Recloser Curve” and the Initialize FlexCurve button is clicked. 5-172 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 391 MRT and from then onwards the operating time remains at 200 ms. Figure 5-80: Composite recloser curve with HCT disabled With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding eight times pickup. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-173...
  • Page 392 Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If this is attempted, the EnerVista software generates an error message and discards the proposed changes. 5.5.7.5 Standard recloser curves The following graphs display standard recloser curves available for the T60. Figure 5-82: Recloser curves GE101 to GE106 5-174...
  • Page 393 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-83: Recloser curves GE113, GE120, GE138, and GE142 Figure 5-84: Recloser curves GE134, GE137, GE140, GE151, and GE201 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-175...
  • Page 394 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-85: Recloser curves GE131, GE141, GE152, and GE200 Figure 5-86: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165 5-176 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 395 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-87: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139 Figure 5-88: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-177...
  • Page 396: Phasor Measurement Unit

      CONFIGURATION The T60 is provided with an optional Phasor Measurement Unit (PMU) feature. This feature is specified as a software option at the time of ordering. The number of PMUs available also depends on this option. Using the order code for your device, see the order codes in chapter 2 for details.
  • Page 397 The figure shows an example of an N60 using four Logical Device PMUs (Logical Device 2 through 5) and four aggregators. The control blocks for the aggregators are located in LD1. A 64 character LDName setting is provided. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-179...
  • Page 398 MxxMMXU1 ClcMth = M-Class (Note Vaux is mapped to Vneut of MMXU) • MxxMSQI1 ClcMth = M-CLASS • NxxMMXU1 ClcMth = M-Class (Note Vaux is mapped to Vneut of MMXU) • NxxMSQI1 ClcMth = M-CLASS 5-180 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 399 The mapping is implemented as STN-IDCode (text string). From each PMU, the user selects the phasor information of interest that is mapped into the selected aggregator datset(s). For version 7.0 and later, only FCDA data is supported. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-181...
  • Page 400 5.5.8.6 Configuration example: CFG-2 based configuration (using IEC 61850-90-5) The T60 is expected to send the CFG-2 file (IEEE C37.118 config. file) upon request from the upstream synchrophasor devices (for example, P30) without stopping R-SV multicasting, as shown in the following figure. The primary domain controller (PDC) does not need to use a stop/start data stream command if the UR protocol is set to IEC 61850-90-5 prior to requesting the configuration via CFG-2 (IEEE C37.118 config.
  • Page 401 FUNCTION: Disabled PMU 1 IDCODE: Range: 1 to 65534 in steps of 1  PMU 1 STN: Range: 32-character ASCII string truncated to 16  characters if mapped into C37.118 Default: GE-UR-PMU GE-UR-PMU T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-183...
  • Page 402 PMU 1 D-CH-16 Range: 16-character ASCII string  NM: Dig Channel 16 PMU 1 D-CH- 1 Range: Off, On  NORMAL STATE: Off  PMU 1 D-CH-16: Range: Off, On  NORMAL STATE: Off 5-184 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 403 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz, 60 Hz, or 120 Hz (or 10 Hz, 25 Hz, 50 Hz, or 100 Hz when the system frequency is 50 Hz) when entered via the keypad or software; and the T60 stops the transmission of reports.
  • Page 404 (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the IEEE C37.118 configuration frame. With 90-5 PMU, the FORMAT and STYLE are Floating-point and Polar respectively, as specified in the IEC 61850-90-5 technical report. 5-186 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 405 MAG: 100.0% PMU 1 IG CALIBRATION Range: –5.00 to 5.00° in steps of 0.05  ANGLE: 0.00° PMU 1 IG CALIBRATION Range: 95.0 to 105.0 in steps of 0.1%  MAG: 100.0% T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-187...
  • Page 406 When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more beneficial to allow the central locations to perform the compensation of sequence voltages. • This setting applies to PMU data only. The T60 calculates symmetrical voltages independently for protection and control purposes without applying this correction. •...
  • Page 407 PMU 1 FREQ TRIGGER Range: 20.00 to 70.00 Hz in steps of 0.01  LOW-FREQ: 49.00 Hz PMU 1 FREQ TRIGGER Range: 20.00 to 70.00 Hz in steps of 0.01  HIGH-FREQ: 61.00 Hz T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-189...
  • Page 408 T60 standards. This element requires that the frequency be above the minimum measurable value. If the frequency is below this value, such as when the circuit is de-energized, the trigger drops out.
  • Page 409 Range: 0.00 to 600.00 s in steps of 0.01  DPO TIME: 1.00 s PMU 1 CURR TRIG BLK: Range: FlexLogic operand  PMU 1 CURR TRIGGER Range: Self-reset, Latched, Disabled  TARGET: Self-reset T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-191...
  • Page 410 The trigger responds to the single-phase and three-phase power signals of the Phasor Measurement Unit (PMU) source. 5-192 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 411 Range: 0.00 to 600.00 s in steps of 0.01  DPO TIME: 1.00 s PMU 1 df/dt TRG BLK: Range: FlexLogic operand  PMU 1 df/dt TRIGGER Range: Self-reset, Latched, Disabled  TARGET: Self-reset T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-193...
  • Page 412 “Automatic Overwrite,” the last record is erased to facilitate new recording, when triggered. Under the “Protected” selection, the recorder stops creating new records when the entire memory is used up by the old uncleared records. 5-194 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 413 FlexLogic operands are updated, and the five-second timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active; when disabled, all 16 operands for each aggregator remain reset. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-195...
  • Page 414 ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values) ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values) 5-196 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 415 0 state, the remote client writes to the reserve bit, the SvEna is rejected by the UR, and a negative response with the appropriate Service Error is returned to the client. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-197...
  • Page 416: Flexlogic

    FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The figure shows major subsystems of a generic UR-series relay involved in this process. 5-198 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 417 Figure 5-103: UR architecture overview The states of all digital signals used in the T60 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 418 The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address of the relay in a web browser and accessing the Device Information Menu. 5-200 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 419 Breaker arcing current 2 max interrupting current has operated BKR ARC 2 MAX DPO Breaker arcing current 2 max interrupting current has dropped out BKR ARC 3 to 6 Same set of operands as shown for BKR ARC 1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-201...
  • Page 420 Digital counter 1 output is ‘equal to’ comparison value Counter 1 LO Digital counter 1 output is ‘less than’ comparison value Counter 2 to 8 Same set of operands as shown for Counter 1 5-202 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 421 NEG SEQ OV1 DPO Negative-sequence overvoltage element has dropped out overvoltage NEG SEQ OV1 OP Negative-sequence overvoltage element has operated NEG SEQ OV2 to 3 Same set of operands as shown for NEG SEQ OV1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-203...
  • Page 422 Phase A of phase instantaneous overcurrent 1 has dropped out PHASE IOC1 DPO B Phase B of phase instantaneous overcurrent 1 has dropped out PHASE IOC1 DPO C Phase C of phase instantaneous overcurrent 1 has dropped out 5-204 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 423 PMU ONE-SHOT OP Indicates the one-shot operation and remains asserted for 30 seconds afterwards PMU ONE-SHOT PENDING Indicates the one-shot operation is pending; that is, the present time is before the scheduled one-shot time T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-205...
  • Page 424 SRC1 VT FF VOL LOSS Source 1 has lost voltage signals (V2 below 10% and V1 below 5% of nominal) failure) SRC1 VT FF ALARM Source 1 has triggered a VT fuse failure alarm 5-206 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 425 ↓ Teleprotection inputs/outputs TELEPRO INPUT 1-16 On Flag is set, Logic =1 TELEPRO INPUT 2-1 On Flag is set, Logic =1 ↓ ↓ TELEPRO INPUT 2-16 On Flag is set, Logic =1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-207...
  • Page 426 (does not appear unless ordered) Cont Ip 2 Off (does not appear unless ordered) ↓ ↓ Cont Ip 120 On (does not appear unless ordered) Cont Ip 120 Off (does not appear unless ordered) 5-208 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 427 LED PHASE C Asserted when phase C involved and to turn PHASE C LED on LED NEUTRAL/GROUND Asserted when a neutral or ground element involved and to turn NEUTRAL/ GROUND LED on T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-209...
  • Page 428 RESET ANCTR OP(OPRD) Reset operand (assigned in INPUTS/OUTPUTS  RESETTING ANNUNCIATOR menu) source of the reset annunciator command RESET ANCTR OP(MNUL) Reset manual (pushbutton or EnerVista software) source of the reset annunciator command 5-210 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 429 2 to 16 any input is ‘1’ 2 to 16 all inputs are ‘1’ 2 to 16 all inputs are ‘0’ NAND 2 to 16 any input is ‘0’ only one input is ‘1’ T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-211...
  • Page 430: Flexlogic Rules

    A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") can be used once only. If this rule is broken, a syntax error is declared. 5.6.3 FlexLogic evaluation Each equation is evaluated in the ascending order in which the parameters have been entered. 5-212 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 431: Flexlogic Example

    4, which is programmed in the contact output section to operate relay H1 (that is, contact output H1). Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and virtual output 4, shown as follows. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-213...
  • Page 432 It is generally easier to start at the output end of the equation and work back towards the input, as shown in the following steps. It is also recommended 5-214 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 433 It is now possible to check that this selection of parameters produces the required logic by converting the set of parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for virtual output 3 diagram as a check. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-215...
  • Page 434 Now check that the selection of parameters produce the required logic by converting the set of parameters into a logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check. 5-216 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 435 Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-217...
  • Page 436: Flexlogic Equation Editor

    Range: Off, any analog actual value parameter  FLEXELEMENT 1 INPUT Range: SIGNED, ABSOLUTE  MODE: SIGNED FLEXELEMENT 1 COMP Range: LEVEL, DELTA  MODE: LEVEL FLEXELEMENT 1 Range: OVER, UNDER  DIRECTION: OVER 5-218 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 437 — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if FLEXELEMENT 1 +IN this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not assert its output operands. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-219...
  • Page 438 Figure 5-112: FlexElement direction, pickup, and hysteresis In conjunction with the setting, the element can be programmed to provide two extra FLEXELEMENT 1 INPUT MODE characteristics, as shown in the following figure. 5-220 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 439 (Brk X Arc Amp A, B, and C) DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured under the +IN and –IN inputs DELTA TIME BASE = 1 µs T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-221...
  • Page 440: Non-Volatile Latches

    SETTINGS  FLEXLOGIC  NON-VOLATILE LATCHES  LATCH 1(16)  LATCH 1 LATCH 1 Range: Disabled, Enabled   FUNCTION: Disabled LATCH 1 ID: Range: up to 20 alphanumeric characters  NV Latch 1 5-222 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 441 Figure 5-114: Non-volatile latch operation table (N = 1 to 16) and logic Latch n type Latch n Latch n Latch n Latch n reset Reset Dominant Previous Previous State State Dominant Previous Previous State State T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-223...
  • Page 442: Grouped Elements

    5.7.3.1 Menu SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  DISTANCE  DISTANCE DISTANCE Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6   SOURCE: SRC 1 5-224 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 443 If this happens, the logic FORCE SELF-POLAR FORCE MEM-POLAR gives higher priority to forcing self-polarization as indicated in the logic diagram. This is consistent with the overall philosophy of distance memory polarization. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-225...
  • Page 444 COMP LIMIT: 90° PHS DIST Z1 Range: 30 to 90° in steps of 1  DIR RCA: 85° PHS DIST Z1 Range: 30 to 90° in steps of 1  DIR COMP LIMIT: 90° 5-226 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 445 PHS DIST Z1 REACH PHS DIST Z1 RCA as illustrated in the following figures. PHS DIST Z1 REV REACH PHS DIST Z1 REV REACH RCA T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-227...
  • Page 446 The selection is available on a per-zone basis. The two characteristics and their possible variations are shown in the following figures. Figure 5-116: Directional mho phase distance characteristic Figure 5-117: Non-directional mho phase distance characteristic 5-228 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 447 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-118: Directional quadrilateral phase distance characteristic Figure 5-119: Non-directional quadrilateral phase distance characteristic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-229...
  • Page 448 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-120: Mho distance characteristic sample shapes 5-230 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 449 Therefore, the Z1 setting is set to “Dy11.” In section (b), the CTs are located at the same side as the read point. Therefore, the Z3 setting is set to “None.” See the Application of Settings chapter for information on calculating distance reach settings in applications involving power transformers. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-231...
  • Page 450 — This setting defines the angle of the reverse reach impedance of the non-directional zone PHS DIST Z1 REV REACH RCA setting). This setting does not apply when the zone direction is set to "Forward" or "Reverse." PHS DIST Z1 DIR 5-232 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 451 — This setting enables the user to select a FlexLogic operand to block a given distance element. VT fuse fail PHS DIST Z1 BLK detection is one of the applications for this setting. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-233...
  • Page 452 2 operation when the fault evolves from one type to another or migrates from the initial zone to zone 2. Assign the required zones in the trip output function to accomplish this functionality. 5-234 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 453 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-125: Phase distance zones 3 and higher OP logic Figure 5-126: Phase distance logic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-235...
  • Page 454 GND DIST Z1 VOLT Range: 0.000 to 5.000 pu in steps of 0.001  LEVEL: 0.000 pu GND DIST Z1 Range: 0.150 to 65.535 s in steps of 0.001  DELAY: 0.150 s 5-236 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 455 The figures show the directional and non-directional quadrilateral ground distance characteristics. The directional and non-directional mho ground distance characteristics are the same as those shown for the phase distance element in the previous section. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-237...
  • Page 456 If this compensation is required, the ground current from the parallel line (3I_0) measured in the direction of the zone being compensated must be connected to the ground input CT of the CT bank 5-238 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 457 In conjunction with the quadrilateral characteristic, this setting improves security for faults close to the reach point by adjusting the reactance boundary into a tent-shape. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-239...
  • Page 458 — This setting enables the user to select a FlexLogic operand to block the given ground distance element. GND DIST Z1 BLK VT fuse fail detection is one of the applications for this setting. 5-240 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 459 2 operation if the fault evolves from one type to another or migrates from zone 3 or 4 to zone 2. Assign the required zones in the trip output element to accomplish this functionality. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-241...
  • Page 460 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-131: Ground distance zones 3 and higher OP scheme 5-242 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 461 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-132: Ground distance zone 1 pickup logic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-243...
  • Page 462 The supervision is biased toward operation in order to avoid compromising the sensitivity of ground distance elements at low signal levels. Otherwise, the reverse fault condition that generates concern has high polarizing levels so that a correct reverse fault decision can be reliably made. 5-244 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 463: Power Swing Detect (Ansi 68)

    RCA: 75° POWER SWING OUTER Range: 40 to 140° in steps of 1  LIMIT ANGLE: 120° POWER SWING MIDDLE Range: 40 to 140° in steps of 1  LIMIT ANGLE: 90° T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-245...
  • Page 464 Different protection elements respond differently to power swings. If tripping is required for faults during power swing conditions, some elements can be blocked permanently (using the operand), and others can be POWER SWING BLOCK blocked and dynamically unblocked upon fault detection (using the operand). POWER SWING UN/BLOCK 5-246 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 465 The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics, as shown in the figure. When set to “Mho,” the element applies the right and left blinders as well. If the blinders are not required, set their settings high enough to effectively disable the blinders. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-247...
  • Page 466 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-135: Power swing detect mho operating characteristics Figure 5-136: Effects of blinders on the mho characteristics 5-248 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 467 — This setting selects the shapes (either “Mho” or “Quad”) of the outer, middle, and inner POWER SWING SHAPE characteristics of the power swing detect element. The operating principle is not affected. The “Mho” characteristics use the left and right blinders. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-249...
  • Page 468 — This setting defines the middle power swing detect characteristic. It is relevant only POWER SWING MIDDLE LIMIT ANGLE for the three-step mode. A typical value is close to the average of the outer and inner limit angles. This setting applies to mho shapes only. 5-250 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 469 POWER SWING TRIP — Enables and disables the logging of power swing detect events in the sequence of events POWER SWING EVENTS recorder. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-251...
  • Page 470 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-138: Power swing detect logic (Sheet 1 of 3) 5-252 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 471 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-139: Power swing detect logic (Sheet 2 of 3) Figure 5-140: Power swing detect logic (Sheet 3 of 3) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-253...
  • Page 472: Load Encroachment

    The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be used to block selected protection elements, such as distance or phase overcurrent. The following figure shows an effect of the load encroachment characteristics used to block the quadrilateral distance element. 5-254 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 473: Transformer

    When the voltage is below this threshold, a blocking signal is not asserted by the element. When selecting this setting, remember that the T60 measures the phase-to-ground sequence voltages regardless of the VT connection. The nominal VT secondary voltage as specified with the SYSTEM SETUP ...
  • Page 474 “Σ” has as its output the vector sum of inputs, and “max” has as its output the input of maximum magnitude; these calculations are performed for each phase. 5-256 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 475 2 settings. Figure 5-144: Percent differential calculations The T60 percent differential element is based on a configurable dual-breakpoint / dual-slope differential restraint characteristic. The purpose of this characteristic is to define the differential/restraint ratio for the transformer winding currents at different loading and fault conditions to securely distinguish between external and internal faults. Increased...
  • Page 476 GROUPED ELEMENTS CHAPTER 5: SETTINGS To provide higher security during CT saturation conditions and to ease CT requirements, the T60 incorporates a dedicated CT saturation detection mechanism. The T60 CT saturation detector can detect saturation happening after approximately 3 ms from fault inception. In case CT saturation is detected, the percent differential is blocked instantly and relies further on the directional element in case fault evolved from external to internal to operate without any delays.
  • Page 477 The relay produces three FlexLogic operands that can be used for testing or for special applications, such as building custom logic (1-out-of-3) or supervising some protection functions (ground time overcurrent, for example) from the 2nd harmonic inhibit. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-259...
  • Page 478 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-146: Percent differential logic 5-260 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 479 The Hottest-Spot Temperature element provides a mechanism to detect abnormal winding hottest-spot temperatures inside the transformer. It can be set to alarm or trip in cases where the computed hottest-spot temperature is above the pickup threshold for a user-specified time (considered as transformer overheating). T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-261...
  • Page 480 — Enter a value above which the aging factor element is to operate. Enter a setting greater than the AGING FACTOR PICKUP maximum permissible aging factor under emergency loading conditions and maximum ambient temperature. Figure 5-149: Transformer aging factor logic 5-262 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 481: Phase Current

    SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE CURRENT  PHASE TOC 1 See page 5-269      PHASE TOC 6    PHASE IOC 1 See page 5-271    T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-263...
  • Page 482 5.7.7.2 Inverse TOC curve characteristics The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t standard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 483 IEC Curve A, IEC Curve B, and IEC Curve C. The IEC curves are derived by the operate and reset time equations. Eq. 5-34 where T = operate time (in seconds) TDM = Multiplier setting I = input current = Pickup Current setting pickup T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-265...
  • Page 484 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 5-266 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 485 A to E = constants defined in the table = characteristic constant defined in the table = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”) RESET Table 5-36: GE type IAC inverse time curve constants IAC curve shape IAC Extreme Inverse 0.0040 0.6379...
  • Page 486 1224.5 937.50 740.74 600.00 FlexCurves FlexCurves are described in the FlexCurves section later in this chapter. The curve shapes for the FlexCurves are derived from the formulae: Eq. 5-37 Eq. 5-38 where 5-268 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 487 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET Recloser curves The T60 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section earlier in this chapter for details. 5.7.7.3 Phase time overcurrent (ANSI 51P, IEC PTOC) SETTINGS ...
  • Page 488 — Selects the signal source for the phase time overcurrent protection element. SIGNAL SOURCE — Selects how phase current input quantities are interpreted by the T60. Inputs can be selected as fundamental INPUT phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 489 PHASE IOC1 BLOCK A: Range: FlexLogic operand   PHASE IOC1 BLOCK C: Range: FlexLogic operand  PHASE IOC1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset PHASE IOC1 Range: Disabled, Enabled  EVENTS: Disabled T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-271...
  • Page 490 Range: 0.004 to 3.000 pu in steps of 0.001  THRESHOLD: 0.700 pu PHASE DIR 1 BLOCK Range: No, Yes  WHEN V MEM EXP: No PHASE DIR 1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset 5-272 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 491 (phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA). The table shows the operating and polarizing signals used for phase directional control. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-273...
  • Page 492 When set to "No," the directional element allows tripping of phase overcurrent elements under directional control. — This setting enables and disables the logging of phase directional overcurrent events in the PHASE DIR 1 EVENTS sequence of events recorder. 5-274 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 493: Neutral Current

     NEUTRAL TOC 1 See below      NEUTRAL TOC 6    NEUTRAL IOC 1 See page 5-277     NEUTRAL IOC 12   T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-275...
  • Page 494 — This setting selects the signal source for the neutral time overcurrent protection element. NEUTRAL TOC1 SIGNAL SOURCE — This setting selects how neutral current input quantities are interpreted by the T60. Inputs can be NEUTRAL TOC1 INPUT selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 495 The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions • Transformation errors of current transformers (CTs) during double-line and three-phase faults • Switch-off transients during double-line and three-phase faults T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-277...
  • Page 496 VOLT: Calculated V0 NEUTRAL DIR OC1 OP Range: Calculated 3I0, Measured IG  CURR: Calculated 3I0 NEUTRAL DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001  SEQ RESTRAINT: 0.063 5-278 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 497 The following tables define the neutral directional overcurrent element. V_0 is the zero-sequence voltage, I_0 is the zero-sequence current, ECA is the element characteristic angle, and IG is the ground current. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-279...
  • Page 498 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) Take the bias into account when using the neutral directional overcurrent element to directionalize other protection elements. 5-280 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 499 For example, if using an autotransformer neutral current as a polarizing source, ensure that a reversal of the ground current does not occur for a high-side fault. Assume that the T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-281...
  • Page 500 — This setting defines the pickup level for the overcurrent unit of the element in the reverse NEUTRAL DIR OC1 REV PICKUP direction. When selecting this setting, keep in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. 5-282 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 501: Ground Current

    SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND CURRENT  GROUND TOC1 See below      GROUND TOC6    GROUND IOC1 See page 5-285     GROUND IOC12   T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-283...
  • Page 502 — This setting selects the signal source for the ground time overcurrent protection element. GROUND TOC1 SIGNAL SOURCE — This setting selects how ground current input quantities are interpreted by the T60. Inputs can be GROUND TOC1 INPUT selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 503 The ground instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental phasor magnitude. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-285...
  • Page 504  TARGET: Self-reset As of T60 firmware revision 3.20, the definition of the restraining signal has been significantly changed compared to previous versions. The restraint during external faults is generally not lower, and often much higher, compared to the previous definition of the restraining signal (enhanced security). The restraint on internal faults has been greatly reduced compared to previous versions (enhanced sensitivity), particularly during low-current internal faults.
  • Page 505 CT installed in the grounding path, or the ground current obtained by external summation of the neutral-side stator CTs. The following figure shows the basic application and wiring rules. Figure 5-163: Typical applications of RGF protection T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-287...
  • Page 506 CT saturates heavily, the actual restraining signal (Igr(k)) does not reduce instantly but keeps decaying decreasing its value by 50% each 15.5 power system cycles. 5-288 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 507 Example 4: Internal low-current single-line-to-ground fault under full load Given the following inputs: IA = 1.10 pu ∠0°, IB = 1.0 pu ∠–120°, IC = 1.0 pu ∠120°, and IG = 0.05 pu ∠0° T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-289...
  • Page 508: Negative Sequence Current

     NEG SEQ DIR OC1 See page 5-292     NEG SEQ DIR OC3   For information on the negative sequence time overcurrent curves, see the Inverse TOC Curve Characteristics section earlier. 5-290 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 509 5.7.10.3 Negative sequence instantaneous overcurrent (ANSI 50Q, IEC PIOC) SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT  NEG SEQ OC1(3)  NEG SEQ IOC1 NEG SEQ IOC1 Range: Disabled, Enabled  FUNCTION: Disabled  T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-291...
  • Page 510 SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT  NEG SEQ DIR OC1(3)  NEG SEQ DIR OC1 NEG SEQ DIR OC1 Range: Disabled, Enabled   FUNCTION: Disabled 5-292 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 511 CT errors, since the current is low. The operating quantity depends on the way the test currents are injected into the T60. For single phase injection •...
  • Page 512 1.5 of a power system cycle. The element emulates an electromechanical directional device. Larger operating and polarizing signals result in faster directional discrimination, bringing more security to the element operation. 5-294 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 513 — Select the element characteristic angle (ECA) for the forward direction. The element NEG SEQ DIR OC1 FWD ECA characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-295...
  • Page 514: Breaker Failure (Ansi 50Bf)

    Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6  SRC 1 BF1 USE AMP SUPV: Range: Yes, No  BF1 USE SEAL-IN: Range: Yes, No  BF1 3-POLE INITIATE: Range: FlexLogic operand  5-296 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 515 Valid only for 1-Pole breaker failure schemes BF1 PH B INITIATE: Range: FlexLogic operand  Valid only for 1-Pole breaker failure schemes BF1 PH C INITIATE: Range: FlexLogic operand  Valid only for 1-Pole breaker failure schemes T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-297...
  • Page 516 This path is intended to detect a breaker that opens mechanically but fails to interrupt fault current; the logic therefore does not use a breaker auxiliary contact. 5-298 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 517 Figure 5-169: Breaker failure main path sequence The current supervision elements reset in less than 0.7 of a power cycle for any multiple of pickup current as shown in the following figure. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-299...
  • Page 518 In microprocessor relays this time is not significant. In T60 relays, which use a Fourier transform, the calculated current magnitude ramps-down to zero one power frequency cycle after the current is interrupted, and this lag needs to be included in the overall margin duration, as it occurs after current interruption.
  • Page 519 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command needs to be given via output operand BKR FAIL 1 TRIP T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-301...
  • Page 520 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-171: Single-pole breaker failure initiate logic 5-302 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 521 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-172: Single-pole breaker failure, timers logic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-303...
  • Page 522 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-173: Three-pole breaker failure, initiate logic 5-304 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 523 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-174: Three-pole breaker failure, timers logic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-305...
  • Page 524: Voltage Elements

    • Source transfer schemes — In the event of an undervoltage, a transfer signal can be generated to transfer a load from its normal source to a standby or emergency power source. 5-306 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 525 Range: 0.004 to 3.000 pu in steps of 0.001  PICKUP: 1.000 pu PHASE UV1 Range: Definite Time, Inverse Time  CURVE: Definite Time PHASE UV1 Range: 0.00 to 600.00 s in steps of 0.01  DELAY: 1.00 s T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-307...
  • Page 526 PHASE OV1 RESET Range: 0.00 to 600.00 s in steps of 0.01  DELAY: 1.00 s PHASE OV1 BLOCK: Range: FlexLogic Operand  PHASE OV1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset 5-308 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 527 Range: 0.00 to 600.00 s in steps of 0.01  DELAY: 1.00 s NEUTRAL OV1 BLOCK: Range: FlexLogic operand  NEUTRAL OV1 TARGET: Range: Self-reset, Latched, Disabled  Self-reset NEUTRAL OV1 EVENTS: Range: Disabled, Enabled  Disabled T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-309...
  • Page 528 Range: Disabled, Enabled  Disabled Use the negative-sequence overvoltage element to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. 5-310 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 529 Range: Disabled, Enabled  Disabled The T60 contains one auxiliary undervoltage element for each VT bank. This element monitors undervoltage conditions of the auxiliary voltage. selects the voltage level at which the time undervoltage element starts timing. The nominal secondary...
  • Page 530 Range: Disabled, Enabled  Disabled The T60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM is the per-unit (pu) base used when setting the SETUP ...
  • Page 531 If the voltage mode is set as “Phase- phase”, then the operating quantity for this element is the phase-to-phase nominal voltage. Likewise, if the voltage T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-313...
  • Page 532 “Phase-ground”, then the operating quantity for this element is the phase-to-ground nominal voltage. It is beneficial to use the phase-to-phase voltage mode for this element when the T60 device is applied on an isolated or resistance-grounded system.
  • Page 533 TDM = Time Delay Multiplier (delay in sec.) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The figure shows the volts/hertz inverse B curves. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-315...
  • Page 534 TDM = Time Delay Multiplier (delay in sec.) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The figure shows the volts/hertz inverse C curves. 5-316 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 535: Sensitive Directional Power (Ansi 32)

    Range: 0.00 to 600.00 s in steps of 0.01  DELAY: 20.00 s DIR POWER 1 BLK: Range: FlexLogic operand  DIR POWER 1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset DIR POWER 1 Range: Disabled, Enabled  EVENTS: Disabled T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-317...
  • Page 536 For example, section (a) in the figure shows settings for reverse power, while section (b) shows settings for low forward power applications. 5-318 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 537 DIR POWER 1 RCA setting to “90°,” active underpower by setting to “180°,” and reactive underpower by DIR POWER 1 RCA DIR POWER 1 RCA setting to “270°.” DIR POWER 1 RCA T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-319...
  • Page 538: Control Elements

    5.8.2 Trip bus SETTINGS  CONTROL ELEMENTS  TRIP BUS  TRIP BUS 1(6)  TRIP BUS 1 TRIP BUS 1 Range: Enabled, Disabled  FUNCTION: Disabled  5-320 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 539: Trip Bus

    — The trip bus output is blocked when the operand assigned to this setting is asserted. TRIP BUS 1 BLOCK — This setting specifies a time delay to produce an output depending on how output is used. TRIP BUS 1 PICKUP DELAY T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-321...
  • Page 540: Setting Groups

    Range: FlexLogic operand   GROUP 6 ACTIVATE ON: Range: FlexLogic operand  GROUP 1 NAME: Range: up to 16 alphanumeric characters   GROUP 6 NAME: Range: up to 16 alphanumeric characters  5-322 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 541 The most recent SelectActiveSG selection is preserved while the UR is powered down or reset. If it becomes necessary to cancel the SelectActiveSG selection without using a SelectActiveSG service request, change the setting to Disabled. This resets the SelectActiveSG selection to 1. SETTING GROUPS FUNCTION T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-323...
  • Page 542: Selector Switch

    1 to the . If the control word is outside the range, an alarm is established by setting the SELECTOR FULL RANGE FlexLogic operand for three seconds. SELECTOR ALARM 5-324 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 543 If the acknowledging signal does not appear within a pre-defined period of time, the selector rejects the change and an alarm established by invoking the FlexLogic operand SELECTOR BIT ALARM for three seconds. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-325...
  • Page 544 The selector position pre-selected via the three-bit control input has not been confirmed before the time The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting. 5-326 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 545 CHAPTER 5: SETTINGS CONTROL ELEMENTS Figure 5-192: Time-out mode T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-327...
  • Page 546 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input. 5-328 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 547 SETTINGS  PRODUCT menu: SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1 : “Self-reset” PUSHBUTTON 1 FUNCTION : “0.10 s” PUSHBUTTON 1 DROP-OUT TIME The figure shows the logic for the selector switch. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-329...
  • Page 548: Underfrequency (Ansi 81U)

     DELAY : 2.000 s UNDERFREQ 1 TARGET: Range: Self-reset, Latched, Disabled  Self-reset UNDERFREQ 1 EVENTS: Range: Disabled, Enabled  Disabled There are six identical underfrequency elements, numbered 1 through 6. 5-330 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 549: Overfrequency (Ansi 81O)

    The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage channel, current channel A, and ground current channel. The first available signal is used for frequency calculation. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-331...
  • Page 550: Frequency Rate Of Change (Ansi 81R)

    Range: 0 to 65.535 s in steps of 0.001  DELAY: 0.000 s FREQ RATE 1 RESET Range: 0 to 65.535 s in steps of 0.001  DELAY: 0.000 s FREQ RATE 1 BLOCK: Range: FlexLogic operand  5-332 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 551 If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum voltage supervision is 3 V. Figure 5-197: Frequency rate of change logic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-333...
  • Page 552: Synchrocheck (Ansi 25)

    Range: Disabled, Enabled  Disabled The T60 is provided with an optional synchrocheck element. This element is specified as a software option (select “10” or “11”) at the time of ordering. See the Order Codes section of chapter 2 for details. 5-334...
  • Page 553 Figure 5-198: Synchrocheck plot for slip > 0 (slip = F2-F1) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-335...
  • Page 554 The selected sources for synchrocheck inputs V1 and V2 (which must not be the same source) can include both a three-phase and an auxiliary voltage. The relay automatically selects the specific voltages to be used by the synchrocheck element in accordance with the following table. 5-336 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 555 The relay uses the phase channel of a three-phase set of voltages if programmed as part of that source. The relay uses the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-337...
  • Page 556 CONTROL ELEMENTS CHAPTER 5: SETTINGS Figure 5-200: Synchrocheck logic 5-338 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 557: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY — This setting enables or disabled the digital element pickup LED. When set to “Disabled,” the DIGITAL ELEMENT 1 PICKUP LED operation of the pickup LED is blocked. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-339...
  • Page 558 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact that is open when the breaker is open (see figure). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5-202: Trip circuit example 1 5-340 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 559 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off.” In this case, the settings are as follows (EnerVista example shown). T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-341...
  • Page 560: Digital Counters

    COUNTER 1 BLOCK: Range: FlexLogic operand  CNT1 SET TO PRESET: Range: FlexLogic operand  COUNTER 1 RESET: Range: FlexLogic operand  COUNT1 FREEZE/RESET: Range: FlexLogic operand  COUNT1 FREEZE/COUNT: Range: FlexLogic operand  5-342 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 561 If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power-down operation. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-343...
  • Page 562: Monitoring Elements

     BREAKER RESTRIKE 1 See page 5-353     BREAKER RESTRIKE 3    CT FAILURE See page 5-355   DETECTOR 1   CT FAILURE   DETECTOR 6 5-344 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 563 The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function. Correction is implemented to account for a non-zero reset time of the overcurrent function. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-345...
  • Page 564 -cycle) and AMP MAX (kA) values of the last event. — This setting specifies the maximum symmetrical interruption rating of the circuit breaker. BKR 1 INTERUPTION RATING Figure 5-205: Arcing current measurement 5-346 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 565 CHAPTER 5: SETTINGS CONTROL ELEMENTS Figure 5-206: Breaker arcing current logic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-347...
  • Page 566 (contact input indicating the breaker status is off), and no flashover current is flowing. A contact showing the breaker status must be provided to the relay. The voltage difference is not considered as a condition for open breaker in this part of the logic. 5-348 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 567 This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than setting. However, monitoring the breaker contact ensures scheme stability. BRK 1 FLSHOVR DIFF V PKP T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-349...
  • Page 568 (all line breakers open), to well above the maximum line (feeder) load (line/feeder connected to load). 5-350 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 569 A six-cycle time delay applies after the selected FlexLogic operand resets. — This setting specifies the time delay to operate after a pickup condition is detected. BRK FLSHOVR PKP DELAY T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-351...
  • Page 570 CONTROL ELEMENTS CHAPTER 5: SETTINGS Figure 5-207: Breaker flashover logic 5-352 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 571  EVENTS: Disabled One breaker restrike element is provided for each DSP in the T60. According to IEEE standard C37.100 entitled IEEE Standard Definitions for Power Switchgear, restrike is defined as “a resumption of current between the contacts of a switching device during an opening operation after an interval of zero current of ¼...
  • Page 572 — Specifies the reset delay for this element. When set to “0 ms,” then FlexLogic operand is BREAKER RESTRIKE 1 RESET DELAY picked up for only 1/8th of the power cycle. 5-354 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 573 CT FAIL 1 3V0 INPUT Range: 0.04 to 2.00 pu in steps of 0.01  PKP: 0.20 pu CT FAIL 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001  DELAY: 1.000 s T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-355...
  • Page 574 CT FAIL 1 3V0 INPUT — Specifies the pickup value for the 3V_0 source. CT FAIL 1 3V0 INPUT PICKUP — Specifies the pickup delay of the CT failure element. CT FAIL 1 PICKUP DELAY 5-356 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 575 Once the fuse failure condition is declared, it is sealed-in until the cause that generated it disappears. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-357...
  • Page 576  THERMAL THERMAL PROTECTION 1 Range: Disabled, Enabled   PROTECTION 1 FUNCTION: Disabled THERMAL PROTECTION 1 Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6  SOURCE: SRC1 5-358 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 577 ) is limited to 8, even when realistically it is exceeding this value. The reset time of the thermal overload protection element is also time delayed using following formula: Eq. 5-59 where T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-359...
  • Page 578 , element starts increasing the thermal energy: Eq. 5-60 When current is less than the dropout level, I > 0.97 × k × I , the element starts decreasing the thermal energy: Eq. 5-61 where 5-360 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 579: Inputs/Outputs

    The figure shows the logic for the thermal overload protection element. Figure 5-214: Thermal overload protection logic 5.9 Inputs/outputs 5.9.1 Contact inputs SETTINGS  INPUTS/OUTPUTS  CONTACT INPUTS  CONTACT INPUTS  T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-361...
  • Page 580 The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-settable debounce time in order for the T60 to validate the new contact state. In the following figure, the debounce time is set at 2.5 ms;...
  • Page 581: Virtual Inputs

    Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5.9.2 Virtual inputs SETTINGS  INPUTS/OUTPUTS  VIRTUAL INPUTS  VIRTUAL INPUT 1(64)  VIRTUAL INPUT 1 VIRTUAL INPUT 1 Range: Disabled, Enabled  FUNCTION: Disabled  T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-363...
  • Page 582: Contact Outputs

    Range: up to 20 alphanumeric characters   Cont Op 1 OUTPUT H1 OPERATE: Range: FlexLogic operand  OUTPUT H1 SEAL-IN: Range: FlexLogic operand  CONTACT OUTPUT H1 Range: Disabled, Enabled  EVENTS: Enabled 5-364 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 583 L-Cont Op 1  OUTPUT H1a OPERATE: Range: FlexLogic operand  OUTPUT H1a RESET: Range: FlexLogic operand  OUTPUT H1a TYPE: Range: Operate-dominant, Reset-dominant  Operate-dominant OUTPUT H1a EVENTS: Range: Disabled, Enabled  Disabled T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-365...
  • Page 584  USER PUSHBUTTON 1 USER PUSHBUTTON 2 : “Self-reset” PUSHBUTTON 1 FUNCTION : “0.00 s” PUSHBTN 1 DROP-OUT TIME : “Self-reset” PUSHBUTTON 2 FUNCTION : “0.00 s” PUSHBTN 2 DROP-OUT TIME 5-366 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 585 A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1 is high, and is to remain opened when VO1 is low. Program the relay as follows. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-367...
  • Page 586: Virtual Outputs

     RESETTING RESET OPERAND: Range: FlexLogic operand   5.9.5.2 Graphical front panel SETTINGS  INPUTS/OUTPUTS  RESETTING  RESETTING RESET OPERAND: Range: FlexLogic operand   RESET ANNUNCIATOR: Range: FlexLogic operand  5-368 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 587: Direct Inputs And Outputs

    — Represents the state of the direct input when the associated direct device is offline. The DIRECT INPUT 1 DEFAULT STATE following choices are available: • On — Defaults the input to Logic 1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-369...
  • Page 588 UR IED 2: “Cont Ip 1 DIRECT OUT 12 OPERAND On” operand of UR IED 2 is now available in UR IED 1 as Cont Ip 1 On DIRECT INPUT 5 ON 5-370 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 589 (if any default state is set to “On”), or to trip the bus on any overcurrent condition (all default states set to “Off”). Example 3: Pilot-aided schemes Consider a three-terminal line protection application shown in the following figure. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-371...
  • Page 590 5" (forward a message from 1 to 3) DIRECT OUT 3 OPERAND "DIRECT INPUT 6" (forward a message from 3 to 1) DIRECT OUT 4 OPERAND The figure shows the signal flow among the three IEDs. 5-372 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 591: Teleprotection

    The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/ On” and logic 0 for “Latest/Off.” T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-373...
  • Page 592 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. Figure 5-224: Teleprotection input/output processing 5-374 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 593: Transducer Inputs/Outputs

    VALUE: 0.000 The T60 is provided with optional DCmA capability. This feature is specified as an option at the time of ordering. See the Order Codes section in chapter 2 for details. Hardware and software are provided to receive signals from external transducers and to convert these signals into a digital format for use as required.
  • Page 594: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. See the following table for reference temperature values for each RTD type. 5-376 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 595: Rrtd Inputs

    SETTINGS  TRANSDUCER I/O  RRTD INPUTS  RRTD INPUTS  RRTD 1 See below      RRTD 12   Menus are available to configure each of the remote RTDs. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-377...
  • Page 596 CHAPTER 5: SETTINGS It is recommended to use the T60 to configure the RRTD parameters. If the RRTDPC software is used to change the RRTD settings directly (the application and type settings), then one of the following two operations is required for changes to be reflected in the T60: •...
  • Page 597 “None.” APPLICATION If the RRTD communication link with the T60 is broken, then the last temperature actual values are retained until the RRTD communication failure is detected. When this occurs, a RRTD COMM FAILURE self-test alarm and target message is generated, an event is logged in the event recorder, and the temperature actual values are reset to 0.
  • Page 598 A value of “None” specifies that the remote RTD operates individually and not part of any RTD group. All remote RTDs programmed to “Stator” are used for RTD biasing of the T60 thermal model. Common groups are provided for rotating machines applications, such as ambient, bearing, group 1, or group 2.
  • Page 599: Dcma Outputs

    The feature is intentionally inhibited if the settings are entered incorrectly, for example when MAX VAL MIN VAL MAX VAL – < 0.1 pu. The resulting characteristic is illustrated in the following figure. MIN VAL T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-381...
  • Page 600 20% overload compared to the nominal. The nominal three-phase power is: Eq. 5-64 The three-phase power with 20% overload margin is: Eq. 5-65 5-382 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 601 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is “Delta.” The voltage is to be monitored in the range from 70% to 110% of nominal. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-383...
  • Page 602: Testing

     FUNCTION: Disabled The T60 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions and the phasor measurement unit (where applicable), using simulated conditions. The test mode can be in any of three states: Disabled, Isolated, or Forcible.
  • Page 603: Test Mode Forcing

      When in Forcible mode, the operand selected by the setting dictates further response of the T60 to TEST MODE FORCING testing conditions, as described in the following two sections. The test mode state is indicated on the relay front panel by a combination of the Test Mode LED indicator, the In-Service LED indicator, and by the critical fail relay, as shown in the following table.
  • Page 604 In test mode, the following actions take place: • The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set • The Sim bit in all output datasets is set 5-386 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 605: Force Contact Inputs

    If set to “Freeze,” the output retains its position at the instant before the was Forcible and the TEST MODE FUNCTION operand selected by the setting was On, regardless of later changes in the status of the operand TEST MODE FORCING T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-387...
  • Page 606 While the selected operand is Off, the output behaves as it does when in service. On restart, the setting and the force contact input and force contact output settings revert to TEST MODE FORCING their default states. 5-388 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 607: Actual Values

      RxGOOSE STATUS See page 6-7    RxGOOSE See page 6-7   STATISTICS  DIGITAL COUNTERS See page 6-7    SELECTOR SWITCHES See page 6-8   T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 608  FREQUENCY RATE See page 6-25   OF CHANGE  FLEXELEMENTS See page 6-25    RxGOOSE Analogs See page 6-26    PHASOR MEASUREMENT See page 6-26   UNIT T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 609: Front Panel

    The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the front panel. To view the front panel in EnerVista software: Click Actual Values > Front Panel. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 610: Graphical Front Panel

    Access Actual Values > Graphical Panel > Annunciator Panel. Alarms are listed, allowing remote acknowledgement/ reset. Click the Acknowledge or Reset button for an alarm. Figure 6-2: Annunciator alarms displayed in the software) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 611: Status

    Range: On, Off  STATUS: Off The T60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. 6.3.4 RxGOOSE DPS inputs ACTUAL VALUES ...
  • Page 612: Teleprotection Inputs

    STATUS CHAPTER 6: ACTUAL VALUES The T60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. 6.3.5 Teleprotection inputs ACTUAL VALUES ...
  • Page 613: Rxgoose Status

     Offline The T60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE All RxGOOSE Online Input.
  • Page 614: Selector Switches

    6.3.14 Real time clock synchronizing ACTUAL VALUES  STATUS  REAL TIME CLOCK SYNCHRONIZING  REAL TIME CLOCK RTC SYNC SOURCE: Range: see below   SYNCHRONIZING None GRANDMASTER ID: Range: any 8 octet value  0X0000000000000000 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 615: Direct Inputs

    COUNT CH1: 0 CRC FAIL COUNT  CH1: 0 AVERAGE MSG RETURN  TIME CH2: 0 ms UNRETURNED MSG  COUNT CH2: 0 CRC FAIL COUNT  CH2: 0 DIRECT INPUT 1:   T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 616: Direct Devices Status

      SIGNATURE: 0 SLOW EXCHANGE 1  DATA LENGTH: 0 These values provide information for debugging an EGD network. The EGD signature and packet size for the slow EGD exchanges display. 6-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 617: Teleprotection Channel Tests

    UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP status shows 4. For the graphical front panel, the remaining connections refer to TCP connections only. — The number of IEC 61850 connections remaining. MMS TCP T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-11...
  • Page 618: Parallel Redundancy Protocol (Prp)

    Range: 0 to 4G, blank if PRP disabled  The T60 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 619: Metering

    GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast. 6.4 Metering 6.4.1 Metering conventions 6.4.1.1 UR convention for measuring power and energy The figure illustrates the conventions established for use in UR devices. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-13...
  • Page 620 6.4.1.2 UR convention for measuring phase angles All phasors calculated by URs and used for protection, control and metering functions are rotating phasors that maintain the correct phase angle relationships with each other at all times. 6-14 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 621 For display and oscillography purposes the phase angles of symmetrical components are referenced to a common reference as described in the previous sub-section. WYE-connected instrument transformers • ABC phase rotation: • ACB phase rotation: The above equations apply to currents as well. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-15...
  • Page 622 * The power system voltages are phase-referenced – for simplicity – to V and V , respectively. This, however, is a relative matter. It is important to remember that the T60 displays are always referenced as specified under SETTINGS  SYSTEM SETUP  POWER SYSTEM  FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure.
  • Page 623: Transformer

    ACTUAL VALUES  METERING  TRANSFORMER  THERMAL ELEMENTS  THERMAL TOP OIL °C:   ELEMENTS 70°C HOTTEST-SPOT °C:  130° AGING FACTOR:  DAILY RATE LOL:  15 hrs XFMR LIFE LOST:  100000 hrs T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-17...
  • Page 624: Sources

     0.000 A SRC 1 RMS Ib:  0.000 A SRC 1 RMS Ic:  0.000 A SRC 1 RMS In:  0.000 A SRC 1 PHASOR Ia:  0.000 A 0.0° 6-18 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 625 0.000 V 0.0° SRC 1 PHASOR Vcg:  0.000 V 0.0° SRC 1 RMS Vab:  0.00 V SRC 1 RMS Vbc:  0.00 V SRC 1 RMS Vca:  0.00 V T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-19...
  • Page 626 SRC 1 REACTIVE PWR  φb: 0.000 var SRC 1 REACTIVE PWR  φc: 0.000 var SRC 1 APPARENT PWR  3φ: 0.000 VA SRC 1 APPARENT PWR  φa: 0.000 VA 6-20 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 627 S = V x Î x Î x Î Eq. 6-1 When VTs are configured in delta, the T60 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î Eq. 6-2...
  • Page 628 The metered frequency values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by the user for the associated source (see SETTINGS  SYSTEM SETUP  SIGNAL SOURCES 6-22 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 629 = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT) m is the last sample number for the sliding window h = 1, 2,..., 25 is the harmonic number The short-time Fourier transform is applied to the unfiltered signal: Eq. 6-3 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-23...
  • Page 630: Sensitive Directional Power

    V2 ANG: 0.0° SYNCHROCHECK 1 PROJ  DELTA_PHASE: 0.0° SYNCHROCHECK 1 PROJ  SYNSCP D_PH: 0.0° If synchrocheck or a setting is "Disabled," the corresponding actual values menu item does not display. 6-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 631: Tracking Frequency

    = maximum primary RMS value of the +IN and -IN inputs BASE (Xfmr Iad, Ibd, and Icd Mag) (CT primary for source currents, and transformer reference primary current for transformer differential currents) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-25...
  • Page 632: Rxgoose Analogs

     0.000 The T60 is provided with optional GOOSE communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE messages sent from other devices.
  • Page 633: Pmu Aggregator

    RGF 1 DIFF Igd:   GROUND FAULT 1 0.000 A RGF 1 RESTR Igr:  0.000 A This menu displays the differential and restraint current values for the restricted ground fault element. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-27...
  • Page 634: Transducer Inputs And Outputs

     ANGLE: 0.00 DEG AG LOOP RESISTANCE  RAG: 0.00 Ohms AG LOOP REACTANCE  XAG: 0.00 Ohms AG LOOP IMPEDANCE  ZAG: 0.00 Ohms AG LOOP IMPEDANCE  ANGLE: 0.00 DEG 6-28 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 635: Records

    Wye if the ground distance element is enabled. 6.5 Records 6.5.1 User-programmable fault reports ACTUAL VALUES  RECORDS  USER-PROGRAMMABLE FAULT REPORTS  USER-PROGRAMMABLE NEWEST RECORD   FAULT REPORTS NUMBER: 0 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-29...
  • Page 636: Event Records

    The event records are also viewable in the software and in a web browser. The figure shows the event records in the software. To view them in a web browser, enter the IP address of the device. When an oscillography icon displays, click it to open it. 6-30 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 637 (highlight in yellow), then press the green or cyan Mark Event Tab pushbutton. The mark color hides the selector until the selector is moved. A field at the top of the page shows the interval between the two marks. Figure 6-7: Event record T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-31...
  • Page 638: Oscillography

    The status of the phasor measurement unit recorder is indicated as follows. ACTUAL VALUES  RECORDS  PMU RECORDS  PMU 1 RECORDING  PMU 1 PMU 1 FORCE TRIGGER: Range: No, Yes   RECORDINg 6-32 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 639: Breaker Maintenance

    BREAKER OPERATING TIME All of the values are stored in non-volatile memory and retained with power cycling. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-33...
  • Page 640: Product Information

    BOOT PROGRAM Range: 0.00 to 655.35  REVISION: 7.01 Revision number of the boot program firmware. FRONT PANEL PROGRAM Range: 0.00 to 655.35  REVISION: 2.01 Revision number of front panel program firmware. 6-34 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 641 The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. The date format reflects the format specified for the clock and can vary from that shown here. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-35...
  • Page 642 PRODUCT INFORMATION CHAPTER 6: ACTUAL VALUES 6-36 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 643: Commands And Targets

    The commands menu contains relay directives intended for operations personnel. All commands can be protected from unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash message appears after successfully command entry. COMMAND EXECUTED T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 644: Virtual Inputs

    CLEAR LOSS OF LIFE Range: No, Yes  RECORDS? No CLEAR TELEPROTECT Range: No, Yes  COUNTERS? No  CLEAR IEC61850 See below   XWSI OPCNT  CLEAR IEC61850 See below   XCBR OPCNT T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 645: Set Date And Time

    COMMANDS  RELAY MAINTENANCE  COMMANDS PERFORM LAMP TEST? Range: No, Yes   RELAY MAINTENANCE PERFORM LCD TEST? Range: Off, Red, Green, Blue, White & Text Pattern,  Black & Text Pattern, TV Test Pattern T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 646 Although the diagnostic information is cleared before the T60 is shipped from the factory, the user can want to clear the diagnostic information for themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart from scratch.
  • Page 647: Phasor Measurement Unit One-Shot

    30 seconds afterwards PMU ONE-SHOT OP When the function is disabled, all three operands are de-asserted. The one-shot function applies to all logical PMUs of a given T60 relay. Figure 7-1: PMU one-shot FlexLogic operands T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 648: Security

    With the CyberSentry option, this setting is available to enable or disable the following commands. — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session. ADMINISTRATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session. ENGINEER LOGOFF T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 649: Targets Menu

    A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target messages of all the devices inserted into that site. Each T60 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu.
  • Page 650: Relay Self-Tests

    Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the T60 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed module (for example, F8L).
  • Page 651 MAINTENANCE ALERT: Direct I/O Ring Break • Latched target message: No. • Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 652 Latched target message: No. • Description of problem: A data item in a configurable GOOSE data set is oscillating. • How often the test is performed: Upon scanning of each configurable GOOSE data set. 7-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 653 This time can be from milliseconds to minutes. • What to do: Check GOOSE setup. AGGREGATOR ERROR: • Latched target message: No. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-11...
  • Page 654 V-type CPU = All ports support RJ45 SFPs only The consequence of an incorrect SFP can range from damage to the T60 to no power information for the T60 on its web page (enter IP address in a web browser, then click the SFP Transceiver Information — only the type of SFP displays and not power data).
  • Page 655 How often the test is performed: On relay power-up and afterwards once every 24 hours. • What to do: Contact the factory. PROTOTYPE FIRMWARE: Self Test Error • Description of problem: Seen until the builds is tagged as being 'release candidate' or 'gold' builds. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-13...
  • Page 656 Brick. Where multiple UR-series devices have self-test errors, look for common causes. 7-14 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 657 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the front panel reset key if the command has ended, however the output can still be non-functional. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 7-15...
  • Page 658 TARGETS MENU CHAPTER 7: COMMANDS AND TARGETS 7-16 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 659: Commissioning

    SYSTEM SETUP  TRANSFORMER  WINDING 1(4)  WINDING 1(4) CONNECTION : “Not Within Zone” SYSTEM SETUP  TRANSFORMER  WINDING 1(4)  WINDING 1(4) GROUNDING : “0°” SYSTEM SETUP  TRANSFORMER  WINDING 2(4)  WINDING 2(4) ANGLE WRT WINDING 1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 660 To test any point from the Slope 2 portion of the characteristic, inject a per-unit restraint current greater than the Breakpoint 2 current as restraint and repeat the steps above by substituting the Breakpoint 2 value in the equations with the new per-unit restraint current value. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 661: Differential Characteristic Test Examples

    This allows the tester to define and confirm various points on the operating characteristic. The spreadsheet can be found at GE Grid Solutions website (look for the T35/T60 Percent Differential Element Simulator in the support documents for the product).
  • Page 662: Test Example 1

    I is the largest compensated current. Compensation refers to vector and magnitude corrections applied to the currents from the HV and LV transformer sides. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 663 From the Current Distribution diagram earlier, there is a 0.866 pu x 100.4 A/200 = 0.434 A secondary current for HV phases B and C, and a 0.866 pu x 925.98 A/1000 = 0.8 A secondary current for LV phases b and c. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 664 0 A ∠0° 0 A ∠0° 0.15 A ∠0° 0.23 A ∠–180° 0.15 A ∠–180° 0.23 A ∠0° Read the following differential and restraint current values from the T60 actual values menu. Phase Differential current (I Phase Restraint current (I 0 ∠0°...
  • Page 665 CHAPTER 8: COMMISSIONING DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES Read the following differential and restraint current values from the T60 actual values menu. Phase Differential current (I Phase Restraint current (I 0 ∠0° 0 ∠0° 0.113 pu ∠0° 1 pu ∠–180° 0.113 pu ∠0°...
  • Page 666 Due to the mathematical complexity involved in shaping the curve between Breakpoint 1 and Breakpoint 2, an Excel-based simulation tool is available from the GE Grid Solutions website (look for the T35/T60 Percent Differential Element Simulator in the support documents for the product). With this tool, you can see the preset I...
  • Page 667: Test Example 2

    CHAPTER 8: COMMISSIONING DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES Read the following differential and restraint current values in the T60 actual values menu. Phase Differential current (I Phase Restraint current (I 0 ∠0° 0 ∠0° 8.631 pu ∠–180° 9 pu ∠–180° 8.631 pu ∠0°...
  • Page 668: Test Example 3

    180°, can be simulated with one current source passed through these relay terminals in series. The second current source simulates the Phase B primary current. The third source simulates the delta “b” and “c” phase currents, also equal in magnitude but displaced by 180°. 8-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 669: Test Example 4

    12.73 ∠–180° 8.2.5 Test example 4 8.2.5.1 D/D0° transformer with phase b to c fault on the secondary delta winding Transformer data — D/D0°, 20 MVA, 115/12.47 kv, CT1 (200:1), CT2 (1000:1) T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 8-11...
  • Page 670 0 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° Operate = 96% 0.18 ∠–90° 8.33 ∠–270° 8 ∠–270° 8.33 ∠–270° > Slope 2 = 95% 0.18 ∠–270° 8.33 ∠–90° 8 ∠–90° 8.33 ∠–90° 8-12 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 671: Inrush Inhibit Test

    Apply a second harmonic to Phase A with a level greater than the set threshold and monitor the operation of the Percent Differential element. The element should drop out when the injected second harmonic level becomes three times larger than the set threshold. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 8-13...
  • Page 672: Overexcitation Inhibit Test

    Injection to a particular T60 frequency element must be to its configured source and to the channels that the source uses for frequency measurement. For frequency measurement, a source uses the first quantity configured in the following...
  • Page 673 0.20 Hz before the threshold and subtract 1 second from the test set time reading of ramp start to relay operation. Note that the T60 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time taken by the frequency responding component to pickup.
  • Page 674: Blank Test Tables

    BLANK TEST TABLES CHAPTER 8: COMMISSIONING sets its frequency high or low to allow the T60 sample clock to catch-up or wait as necessary to reach synchronism with the power system. 8.6 Blank test tables 8.6.1 Differential restraint tests Table 8-5: Differential characteristic test table...
  • Page 675: Inrush Inhibit Tests

    Harmonic Harmonic 8.6.3 Overexcitation inhibit tests Table 8-7: Overexcitation inhibit test results Phase Injected Displayed Status W1 Current W1 5th W2 Current W2 5th (PU) (pu) (Block/Operate) Harmonic Harmonic Harmonic Table 8-8: T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 8-17...
  • Page 676 BLANK TEST TABLES CHAPTER 8: COMMISSIONING 8-18 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 677: Theory Of Operation

    I and I phasors is to be checked. Ideally, during external faults, the said angle is close to 180° (as shown); and close to 0 degrees during internal faults. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 678: Saturation Detector

    9.2.1 CT saturation detection The saturation detector of the T60 takes advantage of the fact that any CT operates correctly for a short period of time, even under very large primary currents that would subsequently cause a very deep saturation. As a result, in the case of an external fault, the differential current stays very low during the initial period of linear operation of the CTs while the T60 TRANSFORMER PROTECTION SYSTEM –...
  • Page 679 This must be kept in mind when setting the characteristic as its parameters must retain their original meaning. The operation of the saturation detector is available as the FlexLogic operand XFMR PCNT DIFF SAT A/B/C. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 680 SATURATION DETECTOR CHAPTER 9: THEORY OF OPERATION Figure 9-4: Saturation detector state machine T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 681: Maintenance

    UR Family Communications Guide for the entries. The upper part of the window displays values. The lower part of the window is for factory service use. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-1...
  • Page 682 Float — A numbering system with no fixed number of digits before or after the decimal point. An example is 0.000000. Binary — A numbering system using 0 and 1. An example is 0000-0000-0000-0000. Entries are not saved when closing the window. 10-2 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 683: General Maintenance

    GENERAL MAINTENANCE 10.2 General maintenance The T60 requires minimal maintenance. As a microprocessor-based relay, its characteristics do not change over time. Expected service life is 20 years for UR devices manufactured June 2014 or later when applied in a controlled indoor environment and electrical conditions within specification.
  • Page 684 Using the Up or Down pushbuttons on the front panel, select the file. Press the COPY pushbutton. The files are copied from the T60 to the USB drive. Do not unplug the USB drive while copying is in progress, else the USB drive can be compromised.
  • Page 685: Convert Device Settings

    Convert the settings by right-clicking one of the files in the Offline Window and selecting the Convert Device Settings option. GE recommends converting settings in firmware steps, for example when converting from 6.0 to 7.4x, convert first to 7.0 then 7.4 in order to follow embedded conversion rules and keep settings.
  • Page 686 Change settings in the new file, for example by looking at the original file. Write the converted file to the device, for example by dragging and dropping from the Offline Window to the Online Window. Check settings and operation. 10-6 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 687: Copy Settings To Other Device

    10.5 Copy settings to other device Settings from one T60 device can be copied to another T60 device for rapid deployment. The order codes must match. See the Settings File section at the beginning of the Interfaces chapter for a list of settings not deployed, such as IP address.
  • Page 688: Back Up And Restore Settings

    UR device settings can be saved in a backup URS file using the EnerVista UR Setup software. The URS file is the standard UR settings file. For an introduction to settings files in the URS format, see the beginning of the Interfaces chapter. 10-8 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 689 Have this option enabled when you want to keep the IID file from the UR device instead of from another tool. The location of the file is C:\ProgramData\GE Power Management\urpc\Offline, for example.
  • Page 690 The file is copied from the computer to the location specified. To save list of sites and devices with an Environment backup: In EnerVista, click File > Environment > Backup. A window opens. Name and save the .ENV file. 10-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 691: Restore Settings

    These messages display because the roles of the protection engineer and network engineer can be separate. The former can require a URS file, while the latter can require stored Modbus settings and protection schemes. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-11...
  • Page 692 EnerVista UR Setup software. To restore the list of sites and devices from an Environment backup: In EnerVista, click File > Environment > Restore. A window opens. Select the .ENV file to restore. 10-12 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 693: Upgrade Software

    For Windows 10, to finish installing the UR USB driver, open Device Manager > Ports, then plug in the USB cable (to connect the relay and computer). A new port starting with "GE Virtual Serial Port" is available. If available, click the OK button to complete the installation.
  • Page 694: Upgrade Firmware

    You access the Convert Device Settings option by right-clicking the file in the Offline Window area at the lower left. GE recommends converting settings in firmware steps, for example when converting from 6.0 to 7.4x, convert first to 7.0 then 7.4 in order to follow embedded conversion rules and keep settings. Note that the values of all settings that have been defaulted during conversion are not listed in the conversion report;...
  • Page 695: Replace Front Panel

    For an enhanced front panel, loosen the thumb screw and open slightly the front panel. For a standard front panel, lift up the black plastic latch on the right side of the front panel and open slightly the front panel. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-15...
  • Page 696 With a Phillips screwdriver, unscrew and remove the mounting bracket on the right side of the unit. The bracket for the enhanced front panel looks similar to that for the graphical front panel, but they are not the same. 10-16 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 697 Figure 10-15: Remove standard front panel mounting bracket on right side Open the front panel. Unplug or unscrew the grey ground cable from the front panel. Unplug the RJ45 connector from the CPU module in the second slot on the left. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-17...
  • Page 698 Unscrew and remove the mounting bracket with the front panel from the left side. Figure 10-17: Unscrew enhanced front panel mounting bracket on left side Figure 10-18: Unscrew standard front panel mounting bracket on left side 10-18 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 699 Figure 10-19: Attach mounting bracket to relay on left side (no power supply module in first slot) Screw the right mounting bracket to the right side of the relay. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-19...
  • Page 700 Close the front panel without tightening the screw to the mounting bracket. Optionally remove the protective plastic film on the graphical front panel. It is normally peeled off, but also can be left The graphical front panel has been installed but not connected. 10-20 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 701 Ensure that the RS485 connector and the black cover plate are not on the back of the CPU module before sliding the module into the front of the relay. Figure 10-23: Rear of a CPU module before insertion without RS485 connector or cover plate T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-21...
  • Page 702 Insert the silver SFP connector(s) at the back of the CPU module, then connect any Ethernet connection(s). Power up the relay. If the graphical front panel does not power up immediately, disconnect power, open the front 10-22 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 703: Replace Module

    Open the enhanced front panel to the left once the thumb screw has been removed. This allows for easy access of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the T60. Figure 10-26: Modules inside relay with front cover open (enhanced front panel) T60 TRANSFORMER PROTECTION SYSTEM –...
  • Page 704: Battery

    When required, the battery can be replaced. The power supply module contains the battery. The battery type is 3 V cylindrical. 10.12.1 Replace battery for SH/SL power supply When required, the battery can be replaced. The power supply module contains the battery. 10-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 705 10. Reinstall the battery holder and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-25...
  • Page 706: Dispose Of Battery

    (Cd), el plomo (Pb), o el mercurio (Hg ). Para el reciclaje apropiado, devuelva este producto a su distribuidor ó deshágase de él en los puntos de reciclaje designados. Para mas información : wwwrecyclethis.info. 10-26 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 707 (Cd), lood (Pb) of kwik (Hg). Voor correcte vorm van kringloop, geef je de producten terug aan jou locale leverancier of geef het af aan een gespecialiseerde verzamelpunt. Meer informatie vindt u op de volgende website: www.recyclethis.info. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 10-27...
  • Page 708 Bu sembolle işaretlenmiş piller Kadmiyum(Cd), Kurşun(Pb) ya da Civa(Hg) içerebilir. Doğru geri dönüşüm için ürünü yerel tedarikçinize geri veriniz ya da özel işaretlenmiş toplama noktlarına atınız. Daha fazla bilgi için: www.recyclethis.info. 10-28 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 709: Clear Files And Data After Uninstall

    For issues not solved by troubleshooting, the process to return the device to the factory for repair is as follows: • Contact a GE Grid Solutions Technical Support Center. Contact information is found in the first chapter. • Obtain a Return Materials Authorization (RMA) number from the Technical Support Center.
  • Page 710: Storage

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gegridsolutions.com/multilin/support/ret_proc.htm...
  • Page 711: Flexanalog Items

    Field RTD 4 Value Field RTD 4 value 5828 Field RTD 5 Value Field RTD 5 value 5829 Field RTD 6 Value Field RTD 6 value 5830 Field RTD 7 Value Field RTD 7 value T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 712 SRC 2 Ic Mag Amps Source 2 phase C current magnitude 6224 SRC 2 Ic Angle Degrees Source 2 phase C current angle 6225 SRC 2 In Mag Amps Source 2 neutral current magnitude T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 713 SRC 4 Ic Angle Degrees Source 4 phase C current angle 6353 SRC 4 In Mag Amps Source 4 neutral current magnitude 6355 SRC 4 In Angle Degrees Source 4 neutral current angle T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 714 6481 SRC 6 In Mag Amps Source 6 neutral current magnitude 6483 SRC 6 In Angle Degrees Source 6 neutral current angle 6484 SRC 6 Ig RMS Amps Source 6 ground current RMS T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 715 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude 6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle 6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 716 SRC 4 Vag RMS Volts Source 4 phase AG voltage RMS 6850 SRC 4 Vbg RMS Volts Source 4 phase BG voltage RMS 6852 SRC 4 Vcg RMS Volts Source 4 phase CG voltage RMS T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 717 6946 SRC 5 Vx Angle Degrees Source 5 auxiliary voltage angle 6947 SRC 5 V_0 Mag Volts Source 5 zero-sequence voltage magnitude 6949 SRC 5 V_0 Angle Degrees Source 5 zero-sequence voltage angle T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 718 SRC 1 Phase A PF Source 1 phase A power factor 7194 SRC 1 Phase B PF Source 1 phase B power factor 7195 SRC 1 Phase C PF Source 1 phase C power factor T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 719 7288 SRC 4 PF Source 4 three-phase power factor 7289 SRC 4 Phase A PF Source 4 phase A power factor 7290 SRC 4 Phase B PF Source 4 phase B power factor T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 720 Source 3 positive varhour 7462 SRC 3 Neg varh varh Source 3 negative varhour 7472 SRC 4 Pos Watthour Source 4 positive Watthour 7474 SRC 4 Neg Watthour Source 4 negative Watthour A-10 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 721 SRC 5 Demand var Vars Source 5 reactive power demand 7754 SRC 5 Demand VA Source 5 apparent power demand 7760 SRC 6 Demand Ia Amps Source 6 phase A current demand T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-11...
  • Page 722 Transformer differential phase C fifth harmonic current angle 9008 Xfmr top-oil t° C °C Transformer top oil temperature 9009 Xfmr hst-spot t° C °C Transformer hottest spot temperature 9010 Xfmr agng fctr Transformer aging factor A-12 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 723 SRC 1 Ia Harm[13] Source 1 phase A current thirteenth harmonic 10253 SRC 1 Ia Harm[14] Source 1 phase A current fourteenth harmonic 10254 SRC 1 Ia Harm[15] Source 1 phase A current fifteenth harmonic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-13...
  • Page 724 SRC 1 Ic Harm[10] Source 1 phase C current tenth harmonic 10316 SRC 1 Ic Harm[11] Source 1 phase C current eleventh harmonic 10317 SRC 1 Ic Harm[12] Source 1 phase C current twelfth harmonic A-14 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 725 SRC 2 Ib Harm[7] Source 2 phase B current seventh harmonic 10379 SRC 2 Ib Harm[8] Source 2 phase B current eighth harmonic 10380 SRC 2 Ib Harm[9] Source 2 phase B current ninth harmonic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-15...
  • Page 726 SRC 3 Ia Harm[4] Source 3 phase A current fourth harmonic 10442 SRC 3 Ia Harm[5] Source 3 phase A current fifth harmonic 10443 SRC 3 Ia Harm[6] Source 3 phase A current sixth harmonic A-16 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 727 Source 3 phase C current total harmonic distortion 10505 SRC 3 Ic Harm[2] Source 3 phase C current second harmonic 10506 SRC 3 Ic Harm[3] Source 3 phase C current third harmonic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-17...
  • Page 728 SRC 4 Ia Harm[23] Source 4 phase A current twenty-third harmonic 10560 SRC 4 Ia Harm[24] Source 4 phase A current twenty-fourth harmonic 10561 SRC 4 Ia Harm[25] Source 4 phase A current twenty-fifth harmonic A-18 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 729 SRC 4 Ic Harm[20] Source 4 phase C current twentieth harmonic 10623 SRC 4 Ic Harm[21] Source 4 phase C current twenty-first harmonic 10624 SRC 4 Ic Harm[22] Source 4 phase C current twenty-second harmonic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-19...
  • Page 730 SRC 5 Ib Harm[17] Source 5 phase B current seventeenth harmonic 10686 SRC 5 Ib Harm[18] Source 5 phase B current eighteenth harmonic 10687 SRC 5 Ib Harm[19] Source 5 phase B current nineteenth harmonic A-20 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 731 SRC 6 Ia Harm[14] Source 6 phase A current fourteenth harmonic 10749 SRC 6 Ia Harm[15] Source 6 phase A current fifteenth harmonic 10750 SRC 6 Ia Harm[16] Source 6 phase A current sixteenth harmonic T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-21...
  • Page 732 SRC 6 Ic Harm[11] Source 6 phase C current eleventh harmonic 10812 SRC 6 Ic Harm[12] Source 6 phase C current twelfth harmonic 10813 SRC 6 Ic Harm[13] Source 6 phase C current thirteenth harmonic A-22 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 733 Degrees Synchrocheck 3 V2 angle 10891 Synchchk 3 V2’ Mag Volts Synchrocheck 3 V2_mag 10893 Synchchk 3 V2’ Ang Degrees Synchrocheck 3 V2_angle 10894 Synchchk 3 Delta’ Phs Degrees Synchrocheck 3 delta_phase T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-23...
  • Page 734 Breaker 1 arcing amp phase A 12044 Brk 1 Arc Amp B kA2-cyc Breaker 1 arcing amp phase B 12046 Brk 1 Arc Amp C kA2-cyc Breaker 1 arcing amp phase C A-24 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 735 RTD input 3 actual value 13555 RTD Ip 4 RTD input 4 actual value 13556 RTD Ip 5 RTD input 5 actual value 13557 RTD Ip 6 RTD input 6 actual value T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-25...
  • Page 736 Ohm inputs 1 value 13601 Ohm Inputs 2 Value Ohms Ohm inputs 2 value 14189 PTP–IRIG-B Delta PTP time minus IRIG-B time 24432 Communications Group Groups communications group 24447 Active Setting Group Current setting group A-26 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 737 V0 3rd Harmonic 4 Volts VTFF 4 V0 3rd Harmonic 42400 Volts Per Hertz 1 Volts per hertz 1 actual value 42401 Volts Per Hertz 2 Volts per hertz 2 actual value T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL A-27...
  • Page 738 RxGOOSE Analog 30 RxGOOSE analog input 30 45644 RxGOOSE Analog 31 RxGOOSE analog input 31 45646 RxGOOSE Analog 32 RxGOOSE analog input 32 61439 PMU Num Triggers Phasor measurement unit recording number of triggers A-28 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 739: Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...
  • Page 740 Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file. Restart the relay for the IP address and port changes to take effect.
  • Page 741: Command Line Interface

    When the Supervisor account is enabled, the 'Lock Relay' setting must first be changed to No before the putsettings, inservice, or reboot command can be used. This setting cannot be changed using the command line interface. • Use quotes ("") to enclose any parameter containing a space T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 742 For non-CyberSentry devices — Set <authentication type> to "traditional". Note that <authentication type> defaults to "traditional" if not specified. Set <account> to "COMMANDS" or "SETTINGS". If not specified, the SETTINGS account is used. Example: SetupCLI URPC login -d "C30 Melbourne" -A traditional -a SETTINGS -w 1password1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 743 Read settings from device <device> and save them to the .urs file <File>. The <File> must not already exist. The default path to the output file is C:\Users\Public\Public Documents\GE Power Management\URPC\Data Example: SetupCLI URPC getsettings -d C30 -f "C30 Markham.urs"...
  • Page 744 SetupCLI URPC getsettings -d demoDevice -f devicefile.urs SetupCLI URPC compare -f existingfile.urs -r devicefile.urs -o output.txt The output is similar to the following: Comparing settings file aaa.urs : C:\Users\Public\Public Documents\GE Power Management\URPC\Data\ with bbb.urs : C:\Users\Public\Public Documents\GE Power Management\URPC\Data\ Setting Name...
  • Page 745 SetupCLI URPC getsettings -d DEV@SETUP_CLI -f "example file.urs" SetupCLI URPC logout -d DEV@SETUP_CLI SetupCLI URPC exit DEV@SETUP_CLI has to be used as the device name in the commands followed by the 'adddevice' command. T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 746 COMMAND LINE INTERFACE APPENDIX C: COMMAND LINE INTERFACE T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 747: Warranty

    This chapter provides the warranty and revision history. D.1 Warranty For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the Terms and Conditions at http://www.gegridsolutions.com/multilin/warranty.htm...
  • Page 748 1 September 2015 15-2215 1601-0090-AC1 7.40x 8 December 2016 16-3319 1601-0090-AE1 7.41x 31 January 2017 17-3427 1601-0090-AE3 7.4x 28 April 2017 17-3561 1601-0090-AF1 7.6x 30 June 2017 17-3779 1601-0090-AF2 7.6x 31 October 2017 17-3935 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 749 APPENDIX D: MISCELLANEOUS REVISION HISTORY Table D-2: Major changes for T60 manual version AF2 (English) Page Description General revision Added type W CPU module to order codes in chapter 2, installation chapter 3, Replace Front Panel section in chapter 10 Added Japanese and Polish languages and modules 6W and 6X to order codes in chapter 2.
  • Page 750 Description Added Engineer content Updated IEC 61850 content Updated FlexAnalog table for most UR products Table D-6: Major changes for T60 manual version AC1 (English) Page Description General revision. Added online help and generic online help. Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not...
  • Page 751 Finite Impulse Response Contact Output Full Load Current Communication Fiber Optic COMM Communications FPGA Field-programmable Gate Array COMP Compensated, Comparison FREQ Frequency CONN Connection Frequency-Shift Keying CONT Continuous, Contact File Transfer Protocol CO-ORD Coordination FlexElement™ T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 752 Loopback Power Line Carrier Line Pickup Positive Locked-Rotor Current POTT Permissive Over-reaching Transfer Trip Load Tap-Changer PRESS Pressure Low Voltage Primary PROT Protection Machine Parallel Redundancy Protocol Machine to Machine PSEL Presentation Selector T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 753 Time, transformer Thermal Capacity Transmission Control Protocol Thermal Capacity Used TD MULT Time Dial Multiplier TEMP Temperature TFTP Trivial File Transfer Protocol Total Harmonic Distortion Timer Time Overcurrent Time Overvoltage TRANS Transient TRANSF Transfer T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 754 ABBREVIATIONS T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 755 Authentication by device or server ........... 5-16 role for CyberSentry ................2-5 Authentication fail message ............7-13 Aggregator Automatic discovery of UR devices .......... 3-65 actual values ..................6-27 settings ....................5-195 Aggregator error message ............7-11 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 756 Comm status remaining connections ........6-11 logic diagram ..............5-302, 5-303 Command line interface to software ..........C-1 main path sequence ..............5-299 Command password ............. 4-58, 5-10 settings ................5-296, 5-300 specifications ..................2-31 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 757 ..................6-28 Convert device settings ..............10-5 actual values ..................6-28 Copy of Copy of ..................10-7 FlexAnalogs ..................A-25 Copy settings for upgrading ............10-5 settings ....................5-375 Copy settings to other device ............10-7 specifications ..................2-37 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 758 Direct devices Drag and drop files ................4-3 settings ....................5-369 Duplicate device settings ............... 10-7 status ..................... 6-10 Duplicate settings for upgrading ..........10-5 Direct I/O application example ..............5-370 configuration examples ..............5-136 settings ....................5-369 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 759 .............. 7-8 Flash memory ..................10-29 Error messages ..................7-8 Flash messages ................... 5-26 device not recognized ..............10-13 Flex State parameters in Engineer ...................4-69 actual values ..................6-8 settings ....................5-132 specifications ..................2-33 FlexAnalog parameters ..............A-1 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 760 ....................3-18 FlexAnalogs ..................A-28 replacement modules ..............2-20 routable, explained ................5-66 specifications ..................2-39 settings ....................5-66 FPGA revision ....................6-34 upgrade ....................10-15 Frequency metering actual values ..................6-22 specifications ..................2-36 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 761 Import settings from SCD or CID file ........10-12 HardFiber In service indicator ................7-8 interface module described ............3-18 In Service LED ..................3-52 order codes for compatible URs ..........2-8 Incompatible device order codes or versions ....10-14 self-test errors ..................7-14 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 762 IRIG-B connection ................3-12 Logic diagrams, create ..............4-61 ISO standards ..................2-46 Logic gates, FlexLogic ............4-82, 5-212 Logout users forcefully ...............7-3 Logs, system ..................5-25 Loop actual values ................6-28 viii T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 763 Flex State parameters ..............5-132 Neutral IOC port, close .....................5-51 FlexLogic operands ...............5-204 register entry ...................5-109 logic diagram ...................5-278 settings ....................5-51 settings ....................5-277 user map ....................5-109 specifications ..................2-27 Modbus Analyzer .................10-1 Model information, view ..............6-34 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 764 ..................5-4 latching outputs ................5-365 Phase angle metering ..............6-14 virtual outputs .................5-368 Phase compensation ..............5-156 Overcurrent curve types ...............5-264 Phase current metering ..............6-18 Overcurrent curves FlexCurves ..................5-268 IAC ......................5-267 IEC ......................5-265 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 765 ..................3-12 Programmed mode ................3-52 SNTP, close ..................5-113 Protection elements ................5-4 TFTP, close ..................5-101 Protection Summary interface ......3-67, 4-4, 5-321 USB ......................4-16 Protocol selection ................5-52 Prototype firmware error message .......... 7-13 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 766 Relay architecture ................5-198 specifications ..................2-41 Relay maintenance ................7-3 RTD FlexAnalogs ..................A-25 Relay name ...................5-142 Release Notes ..................10-14 Remote access of front panel in EnerVista ....4-17, 6-3 Remote access, explained ..............5-8 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 767 ..............7-13 description ..................... 7-8 photo ....................10-21 error messages ..................7-8 Signal loss detection for fiber ............5-47 FlexLogic operands ...............5-211 Signal sources user-programmable ..............5-125 description ....................5-6 metering ....................6-18 settings ....................5-146 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL xiii...
  • Page 768 Test voltages ..................3-15 control with IEC 61850 ..............5-92 settings ................5-166, 5-324 Synchrocheck actual values ..................6-24 FlexAnalogs ..................A-23 FlexLogic operands ...............5-207 logic diagram ...................5-338 settings ....................5-334 specifications ..................2-32 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 769 Unauthorized setting write message ........7-13 data ......................4-13 Underfrequency overview ....................4-12 FlexLogic operands ...............5-208 rules ......................4-14 logic diagram ...................5-331 view data ....................4-14 settings ....................5-330 Tracking frequency ................6-25 specifications ..................2-30 testing ....................8-14 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 770 9 to 16 ........4-29 Web server protocol ............... 5-100 logic diagrams .................5-131 Winding settings ....................5-127 application example ..............5-159 specifications ..................2-34 settings ....................5-151 testing ...................... 7-3 Windows requirement ..............3-54 User-programmable self-test settings .........5-125 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 771 RS422 interface .................3-43 Wiring diagram ..................3-14 Withdrawal from operation ............10-29 Wrong transceiver message ............7-12 XOR gate explained ................4-82 Yellow caution icon in Offline Window ........4-68 Zero-sequence compensation ..........5-156 Zero-sequence core balance ............3-17 T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL xvii...
  • Page 772 INDEX xviii T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL...

Table of Contents

Save PDF