Page 3
AC Drive Foreword Fundamental safety ___________________ instructions ___________________ System overview SINAMICS Mains connection and line- ___________________ side power components S120 ___________________ AC Drive Power Modules ___________________ DC link components Manual Motor-side power ___________________ components Control Units, Control Unit Adapters and operating...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Siemens content, and adapt it for your own machine documentation: http://www.siemens.com/mdm Training At the following link, you will find information on SITRAIN - training from Siemens for products, systems, and drive and automation engineering solutions: http://www.siemens.com/sitrain FAQs You can find Frequently Asked Questions in the Service&Support pages under Product...
Page 6
Equipment for Machine Tools (Catalog NC 61) SINUMERIK 840D sl Type 1B • Equipment for Machine Tools (Catalog NC 62) Configuring/installation SINAMICS S120 Equipment Manual for Control Units and • Additional System Components SINAMICS S120 Equipment Manual for Booksize Power •...
Page 7
SINAMICS drive system. Benefits This Manual provides all the information, procedures and operational instructions required for commissioning and servicing SINAMICS S120. Standard scope The scope of the functionality described in this document can differ from the scope of the functionality of the drive system that is actually supplied.
Page 8
Foreword The EC Declaration of Conformity for the Low Voltage Directive can be found on the Internet http://support.automation.siemens.com There – as a search term – enter the number 22383669 . Note When operated in dry areas, SINAMICS S units conform to the Low-Voltage Directive 2006/95/EC.
Page 9
Foreword Explanation of symbols Table 2 Symbols Symbol Meaning Protective earth (PE) Ground (e.g. M 24 V) Functional ground Equipotential bonding AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 10
Foreword AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
System overview ........................... 29 Field of application ........................29 Platform Concept and Totally Integrated Automation ..............31 Overview, SINAMICS S120 AC Drive ..................32 SINAMICS S120 components ...................... 33 System data ..........................35 Derating as a function of the ambient temperature, pulse frequency, and installation altitude ............................
Page 12
Table of contents 3.8.3 Dimension drawings ........................58 3.8.4 Mounting............................64 3.8.5 Electrical Connection ........................71 3.8.6 Technical data ..........................72 3.8.6.1 Blocksize line reactors ........................ 72 3.8.6.2 Chassis line reactors ........................75 Line connection variants ......................76 3.9.1 Operation on different line system configurations ............... 76 3.9.2 Methods of line connection ......................
Page 13
Table of contents Power Modules Chassis ......................159 4.4.1 Description ..........................159 4.4.2 Safety instructions for Power Modules chassis format .............. 159 4.4.3 Interface description ........................160 4.4.3.1 Overview ............................ 160 4.4.3.2 Connection example ........................162 4.4.3.3 Terminal Block X9 ........................163 4.4.3.4 DCPS, DCNS connection for a dv/dt filter .................
Page 14
Table of contents 6.1.1.3 Dimension drawings ........................213 6.1.1.4 Mounting............................ 221 6.1.1.5 Electrical connection ......................... 227 6.1.1.6 Technical data ........................... 228 Chassis ............................231 6.2.1 Motor reactors ........................... 231 6.2.1.1 Description ..........................231 6.2.1.2 Safety instructions for motor reactors ..................231 6.2.1.3 Dimension drawing ........................
Page 15
Table of contents 7.3.2.13 S5 DIP switch ..........................279 7.3.2.14 DIAG button ..........................279 7.3.2.15 RESET button ..........................279 7.3.2.16 Memory card ..........................280 7.3.3 Connection examples ........................ 281 7.3.4 Meaning of the LEDs ......................... 283 7.3.4.1 Function of the LEDs ......................... 283 7.3.4.2 Behavior of the LEDs during booting ..................
Page 16
Table of contents 7.6.2 Interface description ........................324 7.6.2.1 Overview ........................... 324 7.6.2.2 X200-X202 DRIVE-CLiQ interfaces ..................325 7.6.2.3 X210 EP terminal / temperature sensor ..................326 7.6.2.4 X220 HTL/TTL/SSI encoder interface ..................327 7.6.2.5 X224 electronics power supply ....................329 7.6.3 Connection example .........................
Page 17
Table of contents 8.2.6 Mounting ............................ 382 8.2.7 Technical data ..........................383 Safe Brake Adapter optional module ..................384 8.3.1 Description ..........................384 8.3.2 Safety instructions for Safe Brake Adapters ................385 8.3.3 Interface description ........................386 8.3.3.1 Overview ............................ 386 8.3.3.2 X11 interface to the Control Interface Module ................
Page 18
Table of contents 10.3 Notes on electromagnetic compatibility (EMC) ................. 419 10.4 Cable shielding and routing....................... 420 10.5 24 V DC Supply Voltage ......................422 10.5.1 General ............................422 10.5.2 Overcurrent protection ......................423 10.5.3 Overvoltage protection ......................424 10.5.4 Typical 24 V current consumption of the components ..............
Page 19
Table of contents 11.3.3.2 Replacing the Powerblock, Power Module, frame size GX ............469 11.3.3.3 Replacing the Control Interface Module, Power Module, frame size FX ........472 11.3.3.4 Replacing the Control Interface Module, Power Module, frame size GX ........474 11.3.3.5 Replacing the fan, Power Module, frame size FX ..............
Page 20
Table of contents AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Fundamental safety instructions General safety instructions DANGER Danger to life due to live parts and other energy sources Death or serious injury can result when live parts are touched. • Only work on electrical devices when you are qualified for this job. •...
Page 22
Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life when live parts are touched on damaged devices Improper handling of devices can cause damage. For damaged devices, hazardous voltages can be present at the enclosure or at exposed components;...
Page 23
Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life through unexpected movement of machines when using mobile wireless devices or mobile phones Using mobile wireless devices or mobile phones with a transmit power > 1 W closer than approx.
Fundamental safety instructions 1.2 Safety instructions for electromagnetic fields (EMF) NOTICE Device damage caused by incorrect voltage/insulation tests Incorrect voltage/insulation tests can damage the device. • Before carrying out a voltage/insulation check of the system/machine, disconnect the devices as all converters and motors have been subject to a high voltage test by the manufacturer, and therefore it is not necessary to perform an additional test within the system/machine.
Note Industrial security Siemens provides automation and drive products with industrial security functions that support the secure operation of plants or machines. They are an important component in a holistic industrial security concept. With this in mind, our products undergo continuous development.
• Keep the software up to date. Information and newsletters can be found at: http://support.automation.siemens.com • Incorporate the automation and drive components into a state-of-the-art, integrated industrial security concept for the installation or machine. For more detailed information, go to: http://www.siemens.com/industrialsecurity...
Page 27
Fundamental safety instructions 1.5 Residual risks of power drive systems 2. In the event of a fault, exceptionally high temperatures, including an open fire, as well as emissions of light, noise, particles, gases, etc. can occur inside and outside the inverter, e.g.: –...
System overview Field of application SINAMICS is the family of drives from Siemens designed for machine and plant engineering applications. SINAMICS offers solutions for all drive tasks: ● Simple pump and fan applications in the process industry. ● Complex single drives in centrifuges, presses, extruders, elevators, as well as conveyor and transport systems ●...
Page 30
System overview 2.1 Field of application Depending on the application, the SINAMICS range offers the ideal version for any drive task. ● SINAMICS G is designed for standard applications with induction motors. These applications have less stringent requirements regarding the dynamic performance of the motor speed.
SINAMICS S120 variants. It provides a high-performance, system-wide communication network which links all automation components: HMI, controls, drives and I/O devices. SINAMICS S120 is also available with a PROFINET interface. This Ethernet-based bus allows the rapid exchange of control data via PROFINET IO.
System overview 2.3 Overview, SINAMICS S120 AC Drive Overview, SINAMICS S120 AC Drive SINAMICS S120 AC Drive is a modular drive system for individual axes and addresses sophisticated drive tasks for an extremely wide range of industrial applications. Applications include: ●...
Page 34
● Power Modules (either with or without integrated line filter) and an integrated braking chopper to provide power to the connected motor To address the required functions, SINAMICS S120 AC Drive is equipped with: ● Control Units that provide the drive and technological functions ●...
• ≥ 1194 kW: 200 kA • For Blocksize and Chassis components, UL certification applies only in conjunction with the fuses prescribed by Siemens and not with other types or just with circuit-breakers. Electromagnetic compatibility Category C3 (option) according to EN 61800-3...
Page 36
System overview 2.5 System data Table 2- 2 Environmental conditions Degree of protection IPXXB according to EN 60529, open type according to UL 508 Protection class, line supply circuits I (with protective conductor connection) Electronic circuits safety extra-low voltage PELV / SELV Type of cooling Internal air cooling, power units with forced air cooling using an integrated fan...
System overview 2.6 Derating as a function of the ambient temperature, pulse frequency, and installation altitude Derating as a function of the ambient temperature, pulse frequency, and installation altitude Preliminary remark The air pressure and therefore the air density drop at altitudes above sea level. At these altitudes, the same quantity of air does not have the same cooling effect and the air gap between two electrical conductors can only insulate a lower voltage.
Page 38
System overview 2.6 Derating as a function of the ambient temperature, pulse frequency, and installation altitude AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Mains connection and line-side power components Introduction The following line-side components should be used to connect a SINAMICS drive line-up to the supply network: ● Line disconnector ● Overcurrent protection device (line fuses or circuit-breaker) ● Line contactor (this is required for electrical isolation) ●...
Mains connection and line-side power components 3.2 Information on the disconnector unit Figure 3-1 Example of a Blocksize line connection Figure 3-2 Example of a chassis line connection Information on the disconnector unit A disconnector unit is required for disconnecting the drive line-up from the supply system correctly.
Mains connection and line-side power components 3.3 Overcurrent protection by means of line fuses and circuit breakers Overcurrent protection by means of line fuses and circuit breakers Line fuses or circuit-breakers must be used for cable protection/overcurrent protection. NH, D, and DO type fuses with a gL characteristic or suitable circuit-breakers according to IEC 60947 can be used for this purpose.
Mains connection and line-side power components 3.5 Overvoltage protection ● The shielded motor cable must not be longer than 50 m. ● Use a separate residual current operated circuit-breaker for each Power Module. ● Ensure that the switching elements (disconnector unit, contactors) for connecting and disconnecting the drive line-up have max.
Mains connection and line-side power components 3.6 Line contactors Line contactors A line contactor is required if the drive line-up needs to be electrically isolated from the power supply. When selecting a line contactor, the characteristic values in the technical data apply. The cable routing, the bundling factor, and the factor for the ambient temperature according to EN 60204-1 must be taken into account when dimensioning the various cables.
In conjunction with a suitably EMC-compliant system configuration, line filters limit the conducted interference emitted by the Power Modules to limit values according to EN 61800- A line filter according to the catalog must be used for the SINAMICS S120 drive line-up. 3.7.2...
Mains connection and line-side power components 3.7 Line filter Category C3 Drive systems with a rated voltage < 1000 V, which are intended for use in the second environment and not for use in the first environment. Drive systems which correspond to category C3 may only be installed in the second environment.
Page 46
Mains connection and line-side power components 3.7 Line filter – shorter than 50 m for PM240-2 Power Modules. – shorter than 25 m for PM340 Power Modules. – shorter than 100 m for Chassis Power Modules. ● The pulse frequency is –...
Damage of further loads due to incorrect line filters Unsuitable line filters can cause line harmonics, which damage or destroy loads connected to the same line supply. • Only use line filters released by SIEMENS for SINAMICS. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Mains connection and line-side power components 3.7 Line filter 3.7.5 Dimension drawings Blocksize line filter Figure 3-3 Dimension drawing of the line filter, Power Module PM240-2 frame size FSA, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 49
Mains connection and line-side power components 3.7 Line filter Figure 3-4 Dimension drawing of the line filter, Power Module PM240-2 frame size FSB, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 50
Mains connection and line-side power components 3.7 Line filter Figure 3-5 Dimension drawing of the line filter, Power Module PM240-2 frame size FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 51
Mains connection and line-side power components 3.7 Line filter Figure 3-6 Dimension drawing of the line filter, PM340 Power Module frame size FSA, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 52
Mains connection and line-side power components 3.7 Line filter Chassis line filter Figure 3-7 Dimension drawing, line filter Table 3- 1 Dimensions of the line filter, all data in mm and (inches) 6SL3000- 0BE32-5AA0 0BE34-4AA0 0BE36-0AA0 360 (14.17) 360 (14.17) 400 (15.74) 240 (9.44) 240 (9.44)
Mains connection and line-side power components 3.7 Line filter 3.7.6 Mounting The line filters are designed as base components. The line filter is retained on the mounting surface and the Power Module is mounted on the line filter in a space-saving fashion. The cables to the Power Modules are already connected at the line filter.
Mains connection and line-side power components 3.7 Line filter Table 3- 3 Connecting Power Module PM240-2 to the line filter Frame size Fastening Tightening torque 3 x M4 bolts 2.5 Nm 4 x M4 bolts 2.5 Nm 4 x M5 bolts 3 Nm 3.7.7 Technical data...
Mains connection and line-side power components 3.7 Line filter Table 3- 5 Technical data, Blocksize line filter PM340 Line voltage 3-phase 380 ... 480 VAC Line filter 6SE6400- 2FA00-6AD0 FSA Suitable for Power 6SL3210-1SE11-3UA0, 6SL3210-1SE11-7UA0 Module 6SL3210-1SE12-2UA0, 6SL3210-1SE13-1UA0 6SL3210-1SE14-1UA0 Rated current Power loss <...
Mains connection and line-side power components 3.8 Line reactors Line reactors 3.8.1 Description The line reactors limit low-frequency line harmonics and reduce the load on the rectifiers in the Power Modules. They are used to smooth voltage spikes (line supply faults) or to bridge voltage dips/interruptions when commutating.
Page 57
Damage to the system due to impermissible line reactors An impermissible line reactor may cause damage to the system and any further loads operated on the same power network. • Only use line reactors that SIEMENS has released for SINAMICS. NOTICE Line reactor damage due to interchanged connections Interchanging the input and output connections will damage the line reactor.
Mains connection and line-side power components 3.8 Line reactors 3.8.3 Dimension drawings Blocksize line reactors for PM240-2 Figure 3-9 Dimensional drawing of line reactors, PM240-2 frame size FSA, 0.55 … 1.1 kW, all dimensions in mm and (inch) Figure 3-10 Dimensional drawing of line reactors, PM240-2 frame size FSA, 1.5 …...
Page 59
Mains connection and line-side power components 3.8 Line reactors Figure 3-11 Dimensional drawing of line reactors, PM240-2, frame size FSB, 4.0 … 7.5 kW, all dimensions in mm and (inch) Figure 3-12 Dimensional drawing of line reactors, PM240-2, frame size FSC, 11 … 15 kW, all dimensions in mm and (inch) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 60
Mains connection and line-side power components 3.8 Line reactors Blocksize line reactors for PM340 ① Frame size FSA ② Frame size FSB ③ Frame size FSC Figure 3-13 Dimension drawing of line reactors, PM340 frame sizes FSA, FSB, FSC Table 3- 7 Dimensions of line reactors, PM340 frame size FSA, all data in mm (inches) Line reactor 6SE6400- 3CC00-4AB3...
Page 61
Mains connection and line-side power components 3.8 Line reactors ① Frame size FSD ② Frame size FSE Figure 3-14 Dimension drawing of line reactors, PM340 frame sizes FSD, FSE Table 3- 9 Dimensions of line reactors, PM340 frame sizes FSD and FSE, all data in mm (inches) Line reactor 6SL3203- 0CJ24-5AA0 0CD25-3AA0...
Page 62
Mains connection and line-side power components 3.8 Line reactors Figure 3-15 Dimension drawing of line reactors, PM340 frame size FSF Table 3- 10 Dimensions of line reactors, PM340 frame size FSF, all data in mm (inches) Line reactor 6SE6400- 3CC11-2FD0 3CC11-7FD0 Frame size 240 (9.44)
Page 63
Mains connection and line-side power components 3.8 Line reactors Chassis line reactors ① Mounting hole Figure 3-16 Dimension drawing, line reactors Table 3- 11 Dimensions of the line reactors, all data in mm (inches) 6SL3000- 0CE32-3AA0 0CE32-8AA0 0CE33-3AA0 0CE35-1AA0 25 (0.98) 25 (0.98) 25 (0.98) 30 (1.18)
Mains connection and line-side power components 3.8 Line reactors 3.8.4 Mounting Blocksize line reactors for PM240-2 The line reactors for Power Modules PM240-2 of frame sizes FSA to FSC are designed for installation in a cabinet. The line reactor is installed on the mounting surface next to the Power Module.
Page 65
Mains connection and line-side power components 3.8 Line reactors Blocksize line reactors for PM340 The line reactors for PM340 Power Modules in frame sizes FSA to FSE are designed as base components. The line reactor is fastened to the mounting surface and the Power Module is mounted on the line reactor in a space-saving fashion.
Page 66
Mains connection and line-side power components 3.8 Line reactors Figure 3-18 Mounting dimensions of line reactor PM340, frame sizes FSB and FSC Table 3- 14 Mounting dimensions for line reactors PM340, frame sizes FSB and FSC, all data in mm and (inches) Line reactor 6SL3203- 0CD21-0AA0 0CD21-4AA0...
Page 67
Mains connection and line-side power components 3.8 Line reactors Figure 3-19 Mounting dimensions of line reactor PM340, frame sizes FSD and FSE Table 3- 15 Mounting dimensions for line reactors PM340, frame sizes FSD and FSE, all data in mm and (inches) Line reactor 6SL3203- 0CD25-3AA0 0CJ24-5AA0...
Page 68
Mains connection and line-side power components 3.8 Line reactors Figure 3-20 Mounting dimensions of line reactor PM340, frame size FSF Table 3- 16 Mounting dimensions of line reactor PM340, frame size FSF, all data in mm and (inches) Line reactor 6SE6400- 3CC11-2FD0 3CC11-7FD0 Frame size...
Page 69
Mains connection and line-side power components 3.8 Line reactors Mounting examples Figure 3-21 Mounting the PM340 with a line reactor, using frame size FSB as an example ① Frame size FSB ② Frame size FSC ③ Lateral mounting bracket Figure 3-22 Lateral mounting of line reactors for frame sizes FSB and FSC AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 70
Mains connection and line-side power components 3.8 Line reactors Figure 3-23 Mounting the PM340 with a line reactor, using frame size FSD as an example Chassis line reactors The line reactors for Power Modules, frame sizes FSF, FX, and GX are, as a result of their weight and their size, mounted separately.
Mains connection and line-side power components 3.8 Line reactors 3.8.5 Electrical Connection Line/load connection ① Line reactor ② Power Module Figure 3-24 Power Module with line filter ① Line reactor ② Line filter ③ Power Module Figure 3-25 Power Module with line reactor and line filter AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Mains connection and line-side power components 3.8 Line reactors 3.8.6 Technical data 3.8.6.1 Blocksize line reactors Table 3- 17 Technical data of Blocksize line reactors PM240-2 Order No. 6SL3203- 0CE13-2AA0 0CE21-0AA0 0CE21-8AA0 0CE23-8AA0 Frame size Matching Power Line voltage 1-phase 200 VAC -10% to 240 VAC +10%: Modules 6SL3210- 6SL3210-...
Page 73
Mains connection and line-side power components 3.8 Line reactors Table 3- 18 Technical data, Blocksize line reactors PM340, frame size FSA Line voltage 1-phase 200 VAC -10% to 240 VAC +10% Order No. 6SE6400- 3CC00-4AB3 3CC01-0AB3 Suitable for Power Module 1SB11-0xxx 1SB14-0xxx 6SL3210-...
Page 74
Mains connection and line-side power components 3.8 Line reactors Table 3- 20 Technical data, Blocksize line reactors PM340, frame sizes FSB and FSC Line voltage 3-phase 380 VAC -10% to 480 VAC +10% Frame size Order No. 6SL3203- 0CD21-0AA0 0CD21-4AA0 0CD22-2AA0 0CD23-5AA0 Suitable for...
Mains connection and line-side power components 3.8 Line reactors Table 3- 21 Technical data, Blocksize line reactors PM340, frame sizes FSD, FSE, and FSF Line voltage 3-phase 380 VAC -10% to 480 VAC +10% Frame size Order number 6SL3203- 6SL3203- 6SL3203- 6SE6400- 6SE6400-...
Mains connection and line-side power components 3.9 Line connection variants Line connection variants 3.9.1 Operation on different line system configurations The Power Modules are designed for the following power distribution systems according to IEC 60364-1. Note Above an installation altitude of 2000 m, you must observe the notes in Section Derating as a function of the ambient temperature, pulse frequency, and installation altitude (Page 37).
Page 77
Mains connection and line-side power components 3.9 Line connection variants TT system In a TT system, a point of the generator or the transformer is grounded, normally the neutral point. The housing of the consumer is connected with the ground using a separate cable. Figure 3-27 TT system ●...
Page 78
Mains connection and line-side power components 3.9 Line connection variants NOTICE Damage of the drive line-up when operating on an IT line system without motor reactor If the drive unit is operated without motor reactor on an IT line system, a ground fault on the motor side of the Power Modules can cause damage to the drive line-up or trigger the overcurrent protective equipment.
Mains connection and line-side power components 3.9 Line connection variants 3.9.2 Methods of line connection A distinction is made between the following line connection types: ● Line connection components to be directly connected to the line supply ● Operation of the line connection components via an autotransformer ●...
Page 80
Mains connection and line-side power components 3.9 Line connection variants Note Line connection of motors In combination with the drive system, the motors are generally approved for operation on TN and TT systems with grounded neutral point and on IT systems. In use on IT systems, the occurrence of a first fault between a live part and ground must be signaled by a monitoring device.
Mains connection and line-side power components 3.9 Line connection variants 3.9.3 Operation of the line connection components on the supply line The SINAMICS S drive system is designed to be directly connected to TN and TT systems with a grounded neutral point as well as to IT systems without line filter with rated voltages from 3-phase 380 VAC to 480 VAC and 1-phase 200 VAC to 240 VAC.
Mains connection and line-side power components 3.9 Line connection variants 3.9.4 Operation of the line connection components via an autotransformer An autotransformer can be used to adapt the voltage in the range up to 3-phase 480 VAC +10% or 240 VAC +10%. Application example: ●...
Mains connection and line-side power components 3.9 Line connection variants 3.9.5 Operation of the line connection components via an isolating transformer The isolating transformer converts the type of system grounding of the installation (e.g. IT system) to a TN system with grounded neutral point. Additional voltage adaptation to the permissible voltage tolerance range is possible.
Page 84
Mains connection and line-side power components 3.9 Line connection variants AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules Safety instructions for Power Modules WARNING Danger to life if the fundamental safety instructions and residual risks are not observed The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death. •...
Page 86
• Check the tightening torques of all power connections at regular intervals and tighten them when required. This applies in particular after transport. Note Malfunctions on non-Siemens equipment caused by high-frequency faults in residential environments In the 1st environment Category C2 according to EMC product standard IEC 61800-3 (residential, commercial and industrial sector), the device may cause high-frequency disturbance, which can result in malfunctions in other equipment.
Page 87
Power Modules 4.1 Safety instructions for Power Modules Note Connection authorization Power Modules have been designed for use in the industrial environment and generate current harmonics on the line side as a result of the rectifier circuit. When connecting a machine with integrated Power Modules to the public low-voltage line supply, authorization is required in advance from the local power supply company (utility company) if •...
Power Modules 4.2 Blocksize Power Modules (PM240-2) Blocksize Power Modules (PM240-2) 4.2.1 Description The Power Modules in Blocksize format are designed as follows: ● Line-side diode rectifier ● DC-link electrolytic capacitors with pre-charging circuit ● Output inverter ● Braking chopper for (external) braking resistor ●...
Page 89
Power Modules 4.2 Blocksize Power Modules (PM240-2) Power Module frame size FSB, with and without Push Through Power Module frame size FSB, with and without integrated line filter an integrated line filter Power Module frame size FSC, with and without Push Through Power Module frame size FSC, with and without integrated line filter an integrated line filter...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.2 Safety information for 240-2 Power Modules WARNING Danger to life if the fundamental safety instructions and residual risks are not observed The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death.
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.3.2 Connection example Figure 4-4 PM240-2 connection example AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.3.3 Line supply connection Table 4- 2 Removable line connector Terminal Signal name Technical data Line conductor L1 Line conductor L2 Line conductor L3 PE connection 4.2.3.4 Braking resistor and DC link connection Table 4- 3 Removable braking resistor and DC link connector Terminal...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.3.6 Safe brake relay connection Table 4- 5 Connector Terminal Designation Technical data Low signal safe brake relay to PM240-2 High High signal safe brake relay to PM240-2 Note For further information, see Section Option module Safe Brake Relay (Page 378). 4.2.4 Dimension drawings Power Modules frame size FSA / FSB / FSC...
Page 96
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-6 Drilling pattern of PM240-2 Push Through Power Modules, frame sizes FSA, FSB, FSC; all data in mm and (inches) Figure 4-7 Dimension drawing of PM240-2 Power Modules, frame size FSA, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 97
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-8 Dimension drawing of PM240-2 Power Modules, frame size FSB, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 98
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-9 Dimension drawing of PM240-2 Power Modules, frame size FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 99
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-10 Dimension drawing of PM240-2 Push Through Power Modules, frame size FSA, all data in mm (inches) Figure 4-11 Dimension drawing of PM240-2 Push Through Power Modules, frame size FSB, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 100
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-12 Dimension drawing of PM240-2 Push Through Power Modules, frame size FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 101
Power Modules 4.2 Blocksize Power Modules (PM240-2) Shield connection plates frame sizes FSA/FSB/FSC Figure 4-13 Dimension drawing of shield connection plates for PM240-2 Power Modules, frame size FSA to FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 102
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-14 Dimension drawing of shield connection plates for PM240-2 Push Through Power Modules, frame size FSA to FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.5 Mounting Note Mounting instructions • Please refer to the notes for installing Power Modules in Section Safety information for 240-2 Power Modules (Page 90). • You must mount the PM240-2 Push Through Power Modules on an unpainted metal surface in order to comply with EMC requirements.
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.5.1 Mounting dimensions and tightening torques The mounting dimensions and the tightening torques for fixing the Power Modules are specified in the following table. Table 4- 6 PM240-2, dimensions and tightening torques for mounting Frame size Height, width, depth (without Control Unit) Fastening...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.5.2 Mounting the shielding plate The shield connection plate is used to connect the shields of the 2 power cables. Figure 4-15 Mounting the shield connection plate on the PM240-2 Figure 4-16 Mounting the shield connection plate on the PM240-2 Push Through AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.6 Technical data Note Degree of protection of PM240-2 Power Modules The degree of protection of the PM240-2 Power Modules is IP20. When Push Through Power Modules are installed in a cabinet with degree of protection IP54 using a suitable mounting frame and seals, the Power Modules also comply with this degree of protection.
Page 107
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 1-phase/3-phase 200 … 240 VAC ± 10% Internal Push-through Order number 6SL3210– 6SL3210– 6SL3211– without integrated line filter 1PB13-0UL0 1PB13-8UL0 1PB13-8UL0 with integrated line filter 1PB13-0AL0 1PB13-8AL0 1PB13-8AL0 Max. cable length to braking resistor Line supply connection L1, L2, PE Screw-type terminals...
Page 108
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 1-phase/3-phase 200 … 240 VAC ± 10% Internal Push-through Order number 6SL3210– 6SL3210– 6SL3210– 6SL3211– without integrated line filter 1PB15-5UL0 1PB17-4UL0 1PB21-0UL0 1PB21-0UL0 with integrated line filter 1PB15-5AL0 1PB17-4AL0 1PB21-0AL0 1PB21-0AL0 Rated input current 13,5 18,1...
Page 109
Power Modules 4.2 Blocksize Power Modules (PM240-2) Table 4- 10 Technical data of the PM240-2, FSC (200 V) Line voltage 1-phase/3-phase 200 … 240 VAC ± 10% 3-phase 200 … 240 VAC ±10% Internal Push-through Internal Order number 6SL3210– 6SL3210– 6SL3211–...
Page 110
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 1-phase/3-phase 200 … 240 VAC ± 10% 3-phase 200 … 240 VAC ±10% Internal Push-through Internal Order number 6SL3210– 6SL3210– 6SL3211– 6SL3210– 6SL3210– without integrated line filter 1PB21-4UL0 1PB21-8UL0 1PB21-8UL0 1PC22-2UL0 1PC22-8UL0 with integrated line filter 1PB21-4AL0...
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.6.2 400 V Power Modules Table 4- 11 Technical data of the PM240-2, FSA (400 V) (1/2) Line voltage 3-phase 380 … 480 VAC ± 10% Internal Order number 6SL3210– 6SL3210– 6SL3210– 6SL3210– without integrated line filter 1PE11-8UL1 1PE12-3UL1...
Page 112
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 3-phase 380 … 480 VAC ± 10% Internal Order number 6SL3210– 6SL3210– 6SL3210– 6SL3210– without integrated line filter 1PE11-8UL1 1PE12-3UL1 1PE13-2UL1 1PE14-3UL1 with integrated line filter 1PE11-8AL1 1PE12-3AL1 1PE13-2AL1 1PE14-3AL1 PE connection On line connector Max.
Page 113
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 3-phase 380 … 480 VAC ± 10% Internal Push-through Order number 6SL3210– 6SL3210– 6SL3211– without integrated line filter 1PE16-1UL1 1PE18-0UL1 1PE18-0UL1 with integrated line filter 1PE16-1AL1 1PE18-0AL1 1PE18-0UL1 Resistance value of the external Ω...
Page 114
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 3-phase 380 … 480 VAC ± 10% Internal Push-through Order number 6SL3210– 6SL3210– 6SL3210– 6SL3211– without integrated line filter 1PE21-1UL0 1PE21-4UL0 1PE21-8UL0 1PE21-8UL0 with integrated line filter 1PE21-1AL0 1PE21-4AL0 1PE21-8AL0 1PE21-8AL0 Cooling air requirement /s 0,0092 0,0092...
Page 115
Power Modules 4.2 Blocksize Power Modules (PM240-2) Table 4- 14 Technical data of the PM240-2, FSC (400 V) Line voltage 3-phase 380 … 480 VAC ± 10% Internal Push-through Order number 6SL3210– 6SL3210– 6SL3211– without integrated line filter 1PE22-7UL0 1PE23-3UL0 1PE23-3UL0 with internal line filter 1PE22-7AL0...
Page 116
Power Modules 4.2 Blocksize Power Modules (PM240-2) Line voltage 3-phase 380 … 480 VAC ± 10% Internal Push-through Order number 6SL3210– 6SL3210– 6SL3211– without integrated line filter 1PE22-7UL0 1PE23-3UL0 1PE23-3UL0 with internal line filter 1PE22-7AL0 1PE23-3AL0 1PE23-3AL0 PE connection On line connector Max.
Power Modules 4.2 Blocksize Power Modules (PM240-2) 4.2.6.3 Characteristics Overload capability Figure 4-17 Duty cycle with initial load (for servo drives) Figure 4-18 Duty cycle without initial load (for servo drives) Figure 4-19 S6 duty cycle with initial load (for servo drives) Figure 4-20 Duty cycle with initial load (for servo drives) AC Drive...
Page 118
Power Modules 4.2 Blocksize Power Modules (PM240-2) Figure 4-21 Duty cycle with 60 s overload with a duty cycle duration of 300 s Figure 4-22 Duty cycle with 30 s overload with a duty cycle duration of 300 s Note The short leading edges of the duty cycles shown can only be achieved using speed or torque control.
Page 119
Power Modules 4.2 Blocksize Power Modules (PM240-2) Derating characteristics for PM240-2 Power Modules in Blocksize format For further information, see Section Derating as a function of the ambient temperature, pulse frequency, and installation altitude (Page 37). Figure 4-23 Output current as a function of the pulse frequency Figure 4-24 Output current as a function of the ambient temperature Figure 4-25...
Page 120
Power Modules 4.2 Blocksize Power Modules (PM240-2) It is not permissible that the Power Module is operated with its maximum rated current at output frequencies below 10 Hz. Otherwise, its service life could be reduced. Figure 4-26 Output current as a function of the output frequency Figure 4-27 Current derating as a function of the DC-link voltage AC Drive...
Power Modules 4.3 Power Modules Blocksize (PM340) Power Modules Blocksize (PM340) 4.3.1 Description The Power Modules in blocksize format are designed as follows: ● Line-side diode rectifier ● DC link electrolytic capacitors with pre-charging circuit ● Output inverter ● Braking chopper for (external) braking resistor ●...
Page 122
Power Modules 4.3 Power Modules Blocksize (PM340) Power Module frame size FSC, with and without Power Module frame size FSD, with and without integrated line integrated line filter filter Power Module frame size FSE, with and without Power Module frame size FSF, with and without integrated line integrated line filter filter AC Drive...
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.2 Safety instructions for Power Modules blocksize format WARNING Danger to life if the fundamental safety instructions and residual risks are not observed The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death.
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.3.2 Connection example Figure 4-34 PM340 connection example AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 131
Power Modules 4.3 Power Modules Blocksize (PM340) Arrangement of the line and motor terminals The following diagram shows the arrangement of the line and motor terminals for frame sizes FSA to FSF of the PM340 Power Module. ① Frame size FSA ②...
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.3.3 Line supply connection Table 4- 16 Terminal block, line supply connection 200 V to 240 V 1 AC Terminal Signal name Technical data Line phase L Line phase N Max. conductor cross-section: 2.5 mm² Table 4- 17 Terminal block, line supply connection 380 V to 480 V 3 AC Terminal...
Power Modules 4.3 Power Modules Blocksize (PM340) Note To connect the cable lugs of the brake resistor cable to a PM340 Power Module frame size FSA it is necessary to nip the lug on connection R2 off using a diagonal cutter tool. Take great care to ensure that no pieces of plastic fall into the housing.
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.4 Dimension drawings Frame sizes FSA/FSB/FSC Figure 4-36 Drilling pattern, PM340 Power Modules, frame sizes FSA, FSB, FSC; all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 135
Power Modules 4.3 Power Modules Blocksize (PM340) ① Frame size FSC ② Frame size FSB ③ Frame size FSA Figure 4-37 Dimension drawing, PM340 Power Modules, frame sizes FSA, FSB, FSC; all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 136
Power Modules 4.3 Power Modules Blocksize (PM340) Frame size FSD ① Connections M6 Figure 4-38 Dimension drawing, PM340 Power Module, frame size FSD (without integrated line filter); all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 137
Power Modules 4.3 Power Modules Blocksize (PM340) Figure 4-39 Dimension drawing, PM340 Power Module, frame size FSD (with integrated line filter); all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 138
Power Modules 4.3 Power Modules Blocksize (PM340) Frame size FSE (without/with integrated line filter) ① Connections M6 Figure 4-40 Dimension drawing, PM340 Power Module, frame size FSE (without integrated line filter); all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 139
Power Modules 4.3 Power Modules Blocksize (PM340) Figure 4-41 Dimension drawing, PM340 Power Module, frame size FSE (with integrated line filter); all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 140
Power Modules 4.3 Power Modules Blocksize (PM340) Frame size FSF (without/with integrated line filter) ① Connections M6 Figure 4-42 Dimension drawing, PM340 Power Module, frame size FSF (without integrated line filter); all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 141
Power Modules 4.3 Power Modules Blocksize (PM340) Figure 4-43 Dimension drawing, PM340 Power Module, frame size FSF (with integrated line filter); all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.5 Mounting 4.3.5.1 Mounting dimensions and tightening torques The mounting dimensions and the tightening torques for fixing the Power Modules are specified in the following table. Table 4- 21 PM340, dimensions and tightening torques for mounting Frame size Height, width, depth Dimensions...
Page 143
Power Modules 4.3 Power Modules Blocksize (PM340) Table 4- 22 PM340, load terminals - Tightening torques Frame size Tightening torques (Nm) 2.25 AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.5.2 Access to the power supply terminals and motor terminals Access to the power supply terminals and motor terminals The line and motor terminals are accessed by releasing the tab on the side of the terminal covers using a suitable screwdriver.
Power Modules 4.3 Power Modules Blocksize (PM340) DANGER Danger to life due to electric shock due to exposed terminals Touching live components results in death or severe injury. • Only operate the Power Module with the terminal cover closed 4.3.6 Technical data 4.3.6.1 Power Modules Blocksize, 1-ph.
Page 146
Power Modules 4.3 Power Modules Blocksize (PM340) Line voltage 1-phase 200 … 240 VAC ± 10% PM340 6SL3210– 1SB11-0UA0 1SB12-3UA0 1SB14-0UA0 PM340 with integrated line filter 6SL3210– 1SB11-0AA0 1SB12-3AA0 1SB14-0AA0 Max. cable length to braking resistor Line supply connectionL, N Screw terminals for cable cross-sections 1.0 to 2.5 mm Motor connection U2, V2, W2 DC-link connection, connection for...
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.6.2 Power Modules Blocksize, 3-ph. AC Table 4- 24 Technical data of the PM340, FSA (380 V … 480 V 3 AC ±10 %) PM340 (without integrated 6SL3210- 1SE11-3UA0 1SE11-7UA0 1SE12-2UA0 1SE13-1UA0 1SE14-1UA0 line filter) Output current Rated current I...
Page 148
Power Modules 4.3 Power Modules Blocksize (PM340) PM340 (without integrated 6SL3210- 1SE11-3UA0 1SE11-7UA0 1SE12-2UA0 1SE13-1UA0 1SE14-1UA0 line filter) PE connection At the housing with M4 screw Max. motor cable length shielded/unshielded 50 / 75 Degree of protection IP20 or IPXXB Weight Rated power of a typical standard induction motor at 400 V 3 AC The input current depends on the motor load and line impedance.
Page 149
Power Modules 4.3 Power Modules Blocksize (PM340) PM340 6SL3210- 1SE16-0UA0 1SE17-7UA0 1SE21-0UA0 PM340 with integrated line filter 6SL3210- 1SE16-0AA0 1SE17-7AA0 1SE21-0AA0 Max. cable length to braking resistor Line supply connection Screw terminals for L1, L2, L3 cable cross-sections 1.0 … 6 mm Motor connection U2, V2, W2 DC link connection, connection for...
Page 150
Power Modules 4.3 Power Modules Blocksize (PM340) PM340 6SL3210- 1SE21-8UA0 1SE22-5UA0 1SE23-2UA0 PM340 with integrated line filter 6SL3210- 1SE21-8AA0 1SE22-5AA0 1SE23-2AA0 NH fuses 3NA3810 3NA3814 3NA3817 IEC 60947 Rated current Circuit breaker type designation 3RV1031-4EA10 3RV1031-4FA10 3RV1031-4HA10 IEC 60947 Rated current 22 …...
Page 151
Power Modules 4.3 Power Modules Blocksize (PM340) PM340 6SL3210- 1SE23-8UA0 1SE24-5UA0 1SE26-0UA0 PM340 with integrated line filter 6SL3210- 1SE23-8AA0 1SE24-5AA0 1SE26-0AA0 24 V DC supply for the Control Unit Rated input current with/without integrated line reactor 40 / 46 47 / 53 63 / 72 Class J UL fuses 3NE1817-0...
Page 152
Power Modules 4.3 Power Modules Blocksize (PM340) Table 4- 28 Technical data PM340, FSE and FSF (3 AC 380 V to 480 V ±10 %) PM340 6SL3210- 1SE27-5UA0 1SE31-0UA0 1SE31-1UA0 1SE31-5UA0 1SE31-8UA0 PM340 with integrated line 6SL3210- 1SE27-5AA0 1SE31-0AA0 1SE31-1AA0 1SE31-5AA0 1SE31-8AA0 filter...
Page 153
Power Modules 4.3 Power Modules Blocksize (PM340) PM340 6SL3210- 1SE27-5UA0 1SE31-0UA0 1SE31-1UA0 1SE31-5UA0 1SE31-8UA0 PM340 with integrated line 6SL3210- 1SE27-5AA0 1SE31-0AA0 1SE31-1AA0 1SE31-5AA0 1SE31-8AA0 filter PE connection At the housing with M6 screw At the housing with M8 screw Max. motor cable length shielded/unshielded 70 / 100 Degree of protection...
Power Modules 4.3 Power Modules Blocksize (PM340) 4.3.6.3 Characteristics Overload capability Figure 4-45 Duty cycle with initial load (for servo drives) Figure 4-46 Duty cycle without initial load (for servo drives) Figure 4-47 S6 duty cycle with initial load (for servo drives) Figure 4-48 Duty cycle with initial load (for servo drives) AC Drive...
Page 155
Power Modules 4.3 Power Modules Blocksize (PM340) Figure 4-49 Duty cycle with 60 s overload with a duty cycle duration of 300 s Figure 4-50 Duty cycle with 30 s overload with a duty cycle duration of 300 s Note The short leading edges of the duty cycles shown can only be achieved using speed or torque control.
Page 156
Power Modules 4.3 Power Modules Blocksize (PM340) Derating characteristics for PM340 Power Modules in Blocksize format For further information, see Section Derating as a function of the ambient temperature, pulse frequency, and installation altitude (Page 37). Figure 4-51 Frame sizes FSA to FSE: Output current as a function of the pulse frequency Figure 4-52 Frame size FSF: Output current as a function of the pulse frequency Figure 4-53...
Page 157
Power Modules 4.3 Power Modules Blocksize (PM340) Figure 4-54 Output current as a function of the installation altitude It is not permissible that the Power Module is operated with its maximum rated current at output frequencies below 10 Hz. Otherwise, its service life could be reduced. Figure 4-55 Output current as a function of the output frequency AC Drive...
Page 158
Power Modules 4.3 Power Modules Blocksize (PM340) Figure 4-56 Current derating as a function of the DC-link voltage AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.4 Power Modules Chassis Power Modules Chassis 4.4.1 Description A Power Module is a power unit (frequency inverter) that provides the power supply for the connected motor. A Power Module must be connected to a Control Unit via DRIVE-CLiQ. The open-loop and closed-loop control functions are stored in the Control Unit.
Power Modules 4.4 Power Modules Chassis 4.4.3 Interface description 4.4.3.1 Overview Figure 4-57 Power Module, frame size FX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 161
Power Modules 4.4 Power Modules Chassis Figure 4-58 Power Module, frame size GX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.4 Power Modules Chassis 4.4.3.2 Connection example Figure 4-59 Connection example: Power Module chassis AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.4 Power Modules Chassis 4.4.3.3 Terminal Block X9 Table 4- 29 Terminal block X9 Terminal Signal name Technical data P24V Voltage: 24 V DC (20.4 ... 28.8 V) Current consumption: max 1.4 A Reserved, do not use Reserved, do not use Main contactor 240 V AC/ max.
Power Modules 4.4 Power Modules Chassis 4.4.3.5 X41 EP terminal / temperature sensor connection Table 4- 31 Terminal block -X41 Terminal Function Technical data EP M1 Supply voltage: 24 V DC (20.4 ... 28.8 V) (Enable Pulses) Current consumption: 10 mA EP +24 V Signal propagation delays: (Enable Pulses)
Power Modules 4.4 Power Modules Chassis Note The temperature sensor connection can be used for motors that are equipped with a KTY84- 1C130-, PTC- or PT100 probe in the stator windings. Note A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and - X9:7.
Power Modules 4.4 Power Modules Chassis 4.4.3.7 X46 Brake control and monitoring Table 4- 33 Terminal block -X46 Terminal Function Technical data BR output + This interface is intended for the connection of the safe brake adapter. BR output - FB input + FB input - Max.
(0.5 Hz) Green/Red Firmware download is complete. Wait for POWER ON. (2 Hz) Green/orange Recognition of the component via LED is activated (see SINAMICS S120/S150 List Manual) red/orange Note: Both options depend on the LED status when component recognition is activated using the parameter.
Power Modules 4.4 Power Modules Chassis 4.4.4 Dimension drawings Dimension drawing frame size FX The cooling clearances to be maintained are indicated by the dotted line. Figure 4-60 Dimension drawing Power Module, frame size FX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 169
Power Modules 4.4 Power Modules Chassis Dimension drawing frame size GX The cooling clearances to be maintained are indicated by the dotted line. Figure 4-61 Dimension drawing Power Module, frame size GX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Power Modules 4.4 Power Modules Chassis 4.4.5 Electrical connection Adjusting the fan voltage (-T10) The power supply for the device fans (1-phase 230 VAC) in the Power Module (-T10) is taken from the line supply using a transformer. The mounting position of the transformer is shown in the interface descriptions.
Page 171
Power Modules 4.4 Power Modules Chassis Remove the connection clip for the interference-suppression capacitor for operation on an ungrounded line supply / IT supply If the Power Module is operated from a non-grounded line supply (IT system), the connection bracket for the interference suppression capacitor of the Power Module must be removed. The position of the connection clip can be seen in the overviews of the Power Modules.
Power Modules 4.4 Power Modules Chassis 4.4.6 Technical data Table 4- 38 Technical data, Power Modules Chassis Line voltage 3-ph. 380 V to 480 V AC ±10% (-15% < 1 min) Order number 6SL3310– 1TE32-1AA3 1TE32-6AA3 1TE33–1AA3 1TE33-8AA3 1TE35-0AA3 Frame size Output current rated current I base load current I...
Page 173
Power Modules 4.4 Power Modules Chassis Line voltage 3-ph. 380 V to 480 V AC ±10% (-15% < 1 min) Order number 6SL3310– 1TE32-1AA3 1TE32-6AA3 1TE33–1AA3 1TE33-8AA3 1TE35-0AA3 Motor connection Flat connector for M10 cable Flat connector for M10 cable lug, U2, V2, W2 lug, max.
Power Modules 4.4 Power Modules Chassis 4.4.6.1 Characteristics Overload capability The Power Modules are equipped with an overload reserve, e.g. to handle breakaway torques. In drives with overload requirements, the appropriate base load current must, therefore, be used as a basis for the required load. The overload data is valid under the precondition that the Power Module is operated with its base load current before and after the overload occurs (a load duration of 300 s is used as a basis here).
Page 175
Power Modules 4.4 Power Modules Chassis High overload The base load current for high overload I is based on a load duty cycle of 150% for 60 s or 160% for 10 s with a load duty duration of 300 s. Figure 4-65 Characteristic: High overload AC Drive...
Page 176
Maximum output frequencies achieved by increasing the pulse frequency in VECTOR mode Pulse frequency [kHz] Maximum output frequency [Hz] The maximum output frequency is limited to 300 Hz due to the closed-loop control (see SINAMICS S120/S150 List Manual.) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 177
Power Modules 4.4 Power Modules Chassis Table 4- 42 Maximum output frequencies achieved by increasing the pulse frequency in SERVO mode Pulse frequency [kHz] Maximum output frequency [Hz] 300 / 650 The maximum output frequency of 650 Hz is can only be achieved for a current controller clock cycle of 125 µs (factory setting: 250 µs.) This is only possible for Power Modules with order numbers 6SL3310–1TExx–xAA3 and firmware version as of V4.3x.
Page 178
Power Modules 4.4 Power Modules Chassis AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
DC link components Blocksize 5.1.1 Braking resistors 5.1.1.1 Description The PM240-2 and PM340 Power Modules cannot regenerate into the line supply. For regenerative operation, e.g. the braking of a rotating mass, a braking resistor must be connected to convert the resulting energy into heat. A thermostatic switch monitors the braking resistor for overtemperature and issues a signal on an isolated contact if the limit value is exceeded.
Page 180
DC link components 5.1 Blocksize CAUTION Risk of burns or damage resulting from high surface temperature of the braking resistor The braking resistor can become very hot. You can be severely burnt when touching the surface. Neighboring components can become damaged. •...
DC link components 5.1 Blocksize 5.1.1.3 Connection examples The braking resistor is connected directly on the Power Module at the terminals DCP/R1 and The braking resistor must be protected against overheating. A thermostatic switch handles this protective function (included in the scope of supply of each breaking resistor). Evaluate the braking resistor temperature monitoring so that the motor is switched off when the resistor is in an overtemperature condition.
DC link components 5.1 Blocksize 5.1.1.4 Dimension drawings Braking resistors for PM240-2 Power Modules Figure 5-2 Dimension drawing of braking resistor for PM240-2, frame size FSA, 0.55 … 1.5 kW, all dimensions in mm and (inch) Figure 5-3 Dimension drawing of braking resistor for PM240-2, frame size FSA, 2.2 … .3.0 kW, all dimensions in mm and (inch) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 183
DC link components 5.1 Blocksize Figure 5-4 Dimension drawing braking resistor for PM240-2, frame size FSB, all data in mm (inches) Figure 5-5 Dimension drawing of PM240-2, frame size FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 184
DC link components 5.1 Blocksize Braking resistors for PM340 Power Modules Figure 5-6 Dimension drawing of braking resistor for PM340, frame sizes FSA / FSB Table 5- 1 Dimension drawing in mm (inches) Order number 6SE6400-4BC05-0AA0 6SE6400-4BD11-0AA0 6SL3201-0BE12-0AA0 Frame size 230 (9.05) 230 (9.05) 239 (9.40)
Page 185
DC link components 5.1 Blocksize Figure 5-7 Dimension drawing of braking resistor for PM340, frame sizes FSC / FSD / FSE / FSF Table 5- 2 Dimension drawing in mm (inches) Order number 6SE6400-4BD16- 6SE6400-4BD21- 6SE6400-4BD22- 6SE6400-4BD24- 5CA0 2DA0 2EA0 0FA0 Frame size 285 (11.22)
DC link components 5.1 Blocksize 5.1.1.6 Technical data Recommendation Use the following or comparable braking resistors for the PM240-2 Power Modules 200 V. The technical properties and statements made by the manufacturer apply. Table 5- 4 Technical data of PM240-2 Blocksize braking resistors, 200 V Line voltage 1-phase 200 VAC -10% to 240 VAC +10% Manufacturer Heine Resistors GmbH...
Page 188
DC link components 5.1 Blocksize Line voltage 1-phase 200 VAC -10% to 240 VAC +10% Manufacturer Heine Resistors GmbH Manufacturer's GWHS GWHS GWHS GWHS designation 167-60x30-K 217-60x30-K 337-60x30-K 337-120x30-K IP20 200. ±7% IP20 68. ±7% IP20 37. ±7% IP20 20. ±7% 37.5 W TS KA 110 W TS KA 200 W TS KA...
Page 189
DC link components 5.1 Blocksize Table 5- 5 Technical data of PM240-2 Blocksize braking resistors, 400 V Line voltage 3-phase 380 VAC -10% to 480 VAC +10% Order No. 6SL3201- 0BE14-3AA0 0BE21-0AA0 0BE21-8AA0 0BE23-8AA0 Frame size FSA (0.55 … 1.5 kW) FSA (2.2 …...
Page 190
DC link components 5.1 Blocksize Table 5- 6 Technical data of braking resistors for PM340 Power Modules, frame sizes FSA to FSC Order number 6SE6400- 6SE6400- 6SL3201- 6SE6400- 4BC05-0AA0 4BD11-0AA0 0BE12-0AA0 4BD16-5CA0 Suitable for Power Modules of frame size FSA (1-phase FSA (3-phase Resistance Ω...
Page 191
DC link components 5.1 Blocksize Duty cycles Figure 5-8 Load diagram for the braking resistor, in Blocksize format T [s] period duration of braking duty cycle [s] load duration for peak power [W] unit rating of the braking resistor [W] peak braking power of the braking resistor AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
DC link components 5.2 Chassis Chassis 5.2.1 Braking Modules 5.2.1.1 Description A Braking Module (and an external braking resistor) is required in certain cases when the drive is to be braked or brought to a standstill (e.g. EMERGENCY SWITCHING-OFF Category 1). The Braking Module contains the power electronics and the associated control. The supply voltage for the electronics is taken from the DC link.
– Route the cables in separate cable ducts or pipes. NOTICE Damage due to impermissible braking resistor An impermissible braking resistor may become damaged. • Only use braking resistors that SIEMENS has authorized for SINAMICS. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
DC link components 5.2 Chassis 5.2.1.3 Braking Module for frame size FX Figure 5-9 Braking Module for Power Module, frame size FX Note With this Braking Module, the R1 and DCPA interfaces use the same connection. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
DC link components 5.2 Chassis 5.2.1.4 Braking Module for frame size GX Figure 5-10 Braking Module for Power Module, frame size GX Note With this Braking Module, the R1 and DCPA interfaces use the same connection. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
DC link components 5.2 Chassis 5.2.1.5 Connection example Figure 5-11 Example connection of Braking Module AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Applying a high signal to terminal X21.3 inhibits the Braking Module. On a falling edge, pending error signals are acknowledged. Note You will find setting instructions for wiring the signals in the SINAMICS S120 Function Manual. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
DC link components 5.2 Chassis 5.2.1.8 S1 Threshold switch The response threshold at which the Braking Module is activated and the DC-link voltage generated during braking are specified in the following table. WARNING Danger to life due to electric shock when operating threshold switches Operating the threshold switch when a voltage is present will cause death or serious injury.
DC link components 5.2 Chassis 5.2.1.9 Installing a Braking Module in a Power Module, frame size FX ① Loosen the two M6 screws. Remove the front cover to the top. ② Loosen the two screws from the cover plate at the top and the M6 nut on the left-hand side.
Page 200
DC link components 5.2 Chassis ④ Remove the three screws on the blanking cover. Remove the blanking cover. ⑤ Install the Braking Module instead of the blanking cover and secure it with the blanking cover screws that were previously removed. ⑥...
DC link components 5.2 Chassis 5.2.1.10 Installing a Braking Module in a Power Module, frame size GX ① Loosen the two M6 screws. Remove the front cover to the top. ② Loosen the two screws from the cover plate at the top and the M6 nut on the left-hand side.
Page 202
DC link components 5.2 Chassis ④ Remove the three screws on the blanking cover. Remove the blanking cover. ⑤ Install the Braking Module instead of the blanking cover and secure it with the blanking cover screws that were previously removed. ⑥...
DC link components 5.2 Chassis 5.2.1.11 Technical data Table 5- 11 Technical data, Braking Modules Order number 6SL3300–1AE31-3AA0 6SL3300–1AE32-5AA0 Suitable for installation in Power Modules, frame size power (unit rating) 25 kW 50 kW power (peak power) 125 kW 250 kW power 100 kW 200 kW...
DC link components 5.2 Chassis 5.2.2 Braking resistors 5.2.2.1 Description The braking resistor is used to reduce the excess DC link energy in regenerative operation. The braking resistor is connected to the Braking Module. The braking resistor is mounted outside the cabinet or switchgear room. This means that the resulting heat loss around the Power Module can be dissipated - and cooling costs/equipment reduced.
Page 205
DC link components 5.2 Chassis WARNING Risk of fire and device damage as a result of ground fault / short-circuit The cables to the braking resistor must be routed so that a ground fault or short-circuit can be ruled out. A ground fault can result in fire with associated smoke. •...
Page 206
DC link components 5.2 Chassis NOTICE Damage to braking resistor due to ingress of water The ingress of water can damage the braking resistor. • To maintain degree of protection IP20, provide a canopy to protect against rain when mounting outside. Note Interaction between braking resistor and fire detection sensor If a braking resistor is placed underneath a fire detection sensor, the heat generated could...
DC link components 5.2 Chassis 5.2.2.4 Electrical connection Recommended cable cross-sections: ● For 25 kW: 35 mm² ● For 50 kW: 50 mm² Thermostatic switch A thermostatic switch is installed to protect the braking resistor against overload. Its floating contacts must be integrated in the fault chain on the line side. Table 5- 12 Thermostatic switch connection Terminal...
Page 209
DC link components 5.2 Chassis Duty cycle Figure 5-14 Duty cycle for braking resistors AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 210
DC link components 5.2 Chassis AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Motor-side power components Blocksize 6.1.1 Motor reactors 6.1.1.1 Description Motor reactors reduce the voltage stress on the motor windings by reducing the voltage gradients at the motor terminals that occur when motors are fed from drive converters. At the same time, the capacitive re-charging currents that additionally load the output of the Power Module when longer motor cables are used are simultaneously reduced.
Page 212
There is a risk that the motor reactor will be thermally damaged. • Only use motor reactors that SIEMENS has released for SINAMICS. NOTICE Risk of damaging motor reactors by exceeding the maximum output frequency The maximum permissible output frequency when motor reactors are used is 150 Hz.
Motor-side power components 6.1 Blocksize 6.1.1.3 Dimension drawings Figure 6-1 Dimension drawing of motor reactor, PM240-2 frame size FSA, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 214
Motor-side power components 6.1 Blocksize Figure 6-2 Dimension drawing of motor reactor, PM240-2 frame size FSB, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 215
Motor-side power components 6.1 Blocksize Figure 6-3 Dimension drawing of motor reactor, PM240-2 frame size FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 216
Motor-side power components 6.1 Blocksize Figure 6-4 Dimension drawing motor reactor, PM340 frame size FSA Table 6- 1 Dimensions of motor reactor, PM340 frame size FSA Motor reactor 6SE6400- 3TC00-4AD2 Frame size A in mm (inch) 200 (7.87) B in mm (inch) 75.5 (2.97) C in mm (inch) 110 (4.33)
Page 217
Motor-side power components 6.1 Blocksize ① Frame size FSB ② Frame size FSC Figure 6-5 Dimension drawing of motor reactor, PM340 frame size FSB / FSC Table 6- 2 Dimensions of motor reactor, PM340 frame size FSB / FSC Motor reactor 6SL3202- 0AE21-0CA0 0AJ23-2CA0 Frame size...
Page 218
Motor-side power components 6.1 Blocksize ① Protective conductor connection (M6 x 12) ② Mounting hole Figure 6-6 Dimension drawing of motor reactor, PM340 frame size FSD Table 6- 3 Dimensions of motor reactor, PM340 frame size FSD in mm (inch) Motor reactor 6SE6400- 3TC05-4DD0 3TC03-8DD0...
Page 219
Motor-side power components 6.1 Blocksize ① Protective conductor connection (M 6x12) ② Mounting hole Figure 6-7 Dimension drawing motor reactor, PM340 frame size FSE Table 6- 4 Dimensions of motor reactor, PM340 frame size FSE in mm (inch) Motor reactor 6SE6400- 3TC07-5ED0 3TC08-0ED0 Frame size...
Page 220
Motor-side power components 6.1 Blocksize ① Protective conductor connection (M 8x16) ② Mounting hole Figure 6-8 Dimension drawing motor reactor, PM340 frame size FSF Table 6- 5 Dimensions of motor reactor, PM340 frame size FSF in mm (inch) Motor reactor 6SE6400- 3TC14-5FD0 3TC15-4FD0 Frame size...
Motor-side power components 6.1 Blocksize 6.1.1.4 Mounting Note The motor reactor must be mounted as close as possible to the Power Module. Installation of motor reactors for PM240-2 Power Modules The motor reactors for PM240-2 Power Modules of frame sizes FSA to FSC are designed for installation in a cabinet.
Page 222
Motor-side power components 6.1 Blocksize Mounting of motor reactors for PM340 Power Modules Figure 6-9 Mounting dimensions of motor reactor, frame size FSA Table 6- 7 Mounting dimensions, motor reactor, frame size FSA in mm (inch) Motor reactor 6SE6400- 3TC00-4AD2 Frame size 160 (6.29) 56 (2.20)
Page 223
Motor-side power components 6.1 Blocksize ① Frame size FSB ② Frame size FSC Figure 6-10 Mounting dimensions, motor reactors, frame sizes FSB / FSC Table 6- 8 Mounting dimensions, motor reactors, frame sizes FSB / FSC in mm (inch) Motor reactor 6SL3202- 0AE21-0CA0 0AJ23-2CA0...
Page 224
Motor-side power components 6.1 Blocksize Figure 6-11 Mounting dimensions, motor reactors, frame sizes FSD / FSE / FSF Table 6- 9 Mounting dimensions, motor reactors, frame sizes FSD / FSE in mm (inch) Motor reactor 6SE6400- 3TC05-4DD0 3TC03-8DD0 3TC07-5ED0 3TC08-0ED0 Frame size Motor reactor 20 (0.78)
Page 225
Motor-side power components 6.1 Blocksize Table 6- 10 Mounting dimensions, motor reactor, frame size FSF in mm (inch) Motor reactor 6SE6400- 3TC14-5FD0 3TC15-4FD0 Frame size Motor reactor 20 (0.78) 20 (0.78) 4 (0.15) 4 (0.15) 10 (0.39) 10 (0.39) ∅9 (0.35) ∅9 (0.35) 357 (14.05) 270 (10.62)
Page 226
Motor-side power components 6.1 Blocksize Mounting PM340 Power Module and motor reactors Figure 6-12 Mounting Power Modules and motor reactors, frame sizes FSB / FSC Table 6- 11 Overall dimensions, PM340 Power Module and motor reactor, frame size FSA / FSB / FSC in mm (inch) Motor reactor 6SE6400-3TC00- 6SE6400-3TC00-...
Motor-side power components 6.1 Blocksize 6.1.1.5 Electrical connection Electrical connection of PM240-2 Power Modules Note Approved cables Use only 75° C copper cables. Table 6- 12 Securing the connection cables to the motor reactor Frame size Terminal connection PE connection Max.
Motor-side power components 6.1 Blocksize 6.1.1.6 Technical data Table 6- 13 Motor reactors for PM240-2 Power Modules, frame size FSA to FSC Order No. 6SL3202- 0AE16-1CA0 0AE18-8CA0 0AE21-8CA0 0AE23-8CA0 Frame size FSA (2.2 kW) FSA (4 kW) FSB (7.5 kW) FSC (18.5 kW) Matching Power Line voltage 1-phase 200 VAC -10% to 240 VAC +10%:...
Page 229
Motor-side power components 6.1 Blocksize Table 6- 14 Motor reactors for PM340 Power Modules 3-phase 380 VAC to 480 VAC, frame size FSA Motor reactor (for a 4 kHz pulse frequency) Order number 6SE6400-3TC00-4AD2 Frame size Suitable for Power Module 6SL3210- 6SL3210- 6SL3210-...
Page 230
Motor-side power components 6.1 Blocksize Table 6- 16 Motor reactors for PM340 Power Modules 3-phase 380 VAC to 480 VAC, frame sizes FSD and FSE Motor reactor (for a 4 kHz pulse frequency) Order no. 3TC05-4DD0 3TC03-8DD0 3TC05-4DD0 3TC08-0ED0 3TC07-5ED0 6SE6400- Frame size Suitable for Power...
Motor-side power components 6.2 Chassis Chassis 6.2.1 Motor reactors 6.2.1.1 Description Motor reactors reduce the voltage stress on the motor windings by reducing the voltage gradients at the motor terminals that occur when motors are fed from drive converters. At the same time, the capacitive charge/discharge currents that also occur on the output of the Motor Module when long motor cables are used are reduced.
Page 232
There is a risk that the motor reactor will be thermally damaged. • Only use motor reactors that SIEMENS has released for SINAMICS. NOTICE Risk of damaging motor reactors by exceeding the maximum output frequency The maximum permissible output frequency when motor reactors are used is 150 Hz.
Motor-side power components 6.2 Chassis 6.2.1.3 Dimension drawing ① Mounting hole ② Motor reactor type 1 ③ Motor reactor type 2 Figure 6-14 Dimension drawing, motor reactor 6SL3000- 2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0 2BE35-0AA0 Connection type 25 (0.98) 25 (0.98) 25 (0.98) 25 (0.98) 30 (1.18) 5 (0.19)
Motor-side power components 6.2 Chassis 6.2.1.4 Technical data Table 6- 18 Technical data, motor reactors Order number 6SL3000- 2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0 2BE35-0AA0 Suitable for 6SL3310- 1TE32-1AAx 1TE32-6AAx 1TE33-1AAx 1TE33-8AAx 1TE35-0AAx Power Module Unit rating of the Power Module Rated current Power loss - at 50 Hz 0,436...
Motor-side power components 6.2 Chassis 6.2.2 Sinusoidal filter 6.2.2.1 Description The sine-wave filter at the output of the Power Module supplies voltages that are virtually sinusoidal at the motor, thereby enabling standard motors to be used without shielded cables and without the need to reduce the power. Non-shielded cables can be used and, if long motor supply cables are used, no additional motor reactors are required.
Page 236
When using components that have not been released, damage or malfunctions can occur at the devices or the system itself. • Only use sine-wave filters that SIEMENS has released for SINAMICS. NOTICE Risk of damaging sine-wave filter by exceeding the maximum output frequency The maximum permissible output frequency when sine-wave filters are used is 150 Hz.
Motor-side power components 6.2 Chassis 6.2.2.4 Technical data Table 6- 20 Technical data, sine-wave filter Order number 6SL3000- 2CE32-3AA0 2CE32-3AA0 2CE32-8AA0 2CE33-3AA0 2CE34-1AA0 Suitable for 6SL3310- 1TE32-1AAx 1TE32-6AAx 1TE33-1AAx 1TE33-8AAx 1TE35-0AAx Power Module Unit rating of the Power Module at a 4 kHz pulse frequency Rated current Power loss...
Motor-side power components 6.2 Chassis 6.2.3 dv/dt filter plus Voltage Peak Limiter 6.2.3.1 Description The dV/dt filter plus Voltage Peak Limiter consists of two components: the dV/dt reactor and the voltage limiting network (Voltage Peak Limiter), which limits voltage peaks and returns the energy to the DC link.
Page 240
Motor-side power components 6.2 Chassis WARNING Danger to life caused by high discharge currents when the external protective conductor is interrupted dV/dt filters plus Voltage Peak Limiter result in a high discharge current via the protective conductor. When the protective conductor is interrupted, touching live components can result in electric shock, which can lead to death or serious injuries.
Page 241
When using components that have not been released, damage or malfunctions can occur at the devices or the system itself. • Only use dV/dt filters that SIEMENS has approved for operation with SINAMICS. NOTICE Damage to the dV/dt filter by exceeding the maximum output frequency The maximum permissible output frequency when using dV/dt filters plus Voltage Peak Limiter is 150 Hz.
Motor-side power components 6.2 Chassis 6.2.3.4 Connecting the dv/dt filter plus Voltage Peak Limiter Figure 6-18 Connecting the dV/dt filter plus Voltage Peak Limiter Cable cross-sections Table 6- 22 Cable cross-sections for connections between a dV/dt filter and Power Module dV/dt filter plus Voltage Peak Connection to the DC link Connection between a dV/dt...
Motor-side power components 6.2 Chassis 6.2.3.6 Dimension drawing of the voltage peak limiter Figure 6-20 Dimension drawing of the Voltage Peak Limiter, type 1 Figure 6-21 Dimension drawing of the Voltage Peak Limiter, type 2 Table 6- 24 Assigning Voltage Peak Limiter to dimension drawings Voltage peak limiter Dimension drawing type 6SL3000-2DE32-6BA0...
Motor-side power components 6.2 Chassis 6.2.4 dv/dt filter compact plus Voltage Peak Limiter 6.2.4.1 Description The dV/dt filter compact plus Voltage Peak Limiter has two components: The dV/dt reactor and the voltage limiting network (Voltage Peak Limiter). The voltage limiting network cuts-off the voltage peaks and feeds the energy back into the DC link.
Page 248
Motor-side power components 6.2 Chassis WARNING Danger to life caused by high discharge currents when the external protective conductor is interrupted dV/dt filters plus Voltage Peak Limiter result in a high discharge current via the protective conductor. When the protective conductor is interrupted, touching live components can result in electric shock, which can lead to death or serious injuries.
Page 249
When using components that have not been released, damage or malfunctions can occur at the devices or the system itself. • Only use a dV/dt filter compact that SIEMENS has released for SINAMICS. NOTICE Risk of damaging the dV/dt filter compact by exceeding the maximum output frequency The maximum permissible output frequency when using dV/dt filters compact plus Voltage Peak Limiter is 150 Hz.
Page 250
Motor-side power components 6.2 Chassis NOTICE Damage to the dV/dt filter if motor is not connected If the drive is operated without the motor being connected, the dV/dt filter plus the Voltage Peak Limiter may be damaged or destroyed. • Never operate drives with dV/dt filters plus Voltage Peak Limiter without a motor being connected.
Motor-side power components 6.2 Chassis 6.2.4.3 Interface description Figure 6-22 Interface overview, dV/dt filter compact plus Voltage Peak Limiter, type 1 Figure 6-23 Interface overview, dV/dt filter compact plus Voltage Peak Limiter, type 2 AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Motor-side power components 6.2 Chassis 6.2.4.4 Connecting the dv/dt filter compact plus Voltage Peak Limiter Figure 6-24 Connecting the dV/dt filter compact plus Voltage Peak Limiter Cable cross-sections Table 6- 26 Cable cross-sections for connections between a dV/dt filter and Power Module dV/dt filter compact plus Voltage Cross-section Connection on dV/dt filter...
Motor-side power components 6.2 Chassis 6.2.4.5 Dimension drawing of dv/dt filter compact plus Voltage Peak Limiter dV/dt filter compact plus Voltage Peak Limiter, type 1 Figure 6-25 Dimension drawing of dV/dt filter compact plus Voltage Peak Limiter, type 1 AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 254
Motor-side power components 6.2 Chassis dV/dt filter compact plus Voltage Peak Limiter, type 2 Figure 6-26 Dimension drawing of dV/dt filter compact plus Voltage Peak Limiter, type 2 Table 6- 27 Assignment of the dV/dt filter compact plus Voltage Peak Limiter to the dimension drawings dV/dt filter compact plus Voltage Peak Limiter Dimension drawing type...
Control Units, Control Unit Adapters and operating components Introduction 7.1.1 Control Units Brief description The CU310-2 Controller Units are designed for operation connected to a Power Module, in the blocksize or chassis formats. CU310-2 DP CU310-2 PN AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 258
Control Units, Control Unit Adapters and operating components 7.1 Introduction Features Designation Features Order number - PROFIBUS as an external communications interface CU310-2 DP - LAN (Ethernet) 6SL3040-1LA00-0AA0 - TTL/HTL/SSI – encoder evaluation - analog setpoint input - 2x PROFINET as an external communications interface CU310-2 PN - LAN (Ethernet) 6SL3040-1LA01-0AA0...
Control Units, Control Unit Adapters and operating components 7.1 Introduction 7.1.2 Control Unit Adapter Brief description Using a Control Unit Adapter, a Power Module can be connected as an additional axis to an existing DC/AC group. A higher-level closed-loop control module is always required. Control Unit Adapter CUA31 Control Unit Adapter CUA32 Features...
Control Units, Control Unit Adapters and operating components 7.2 Safety instructions for Control Units and Control Unit Adapters Safety instructions for Control Units and Control Unit Adapters WARNING Danger to life if the fundamental safety instructions and residual risks are not observed The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death.
Page 261
Damage or malfunctions can occur on the devices or system when DRIVE-CLiQ cables are used that are either incorrect or have not been approved for this purpose. • Only use suitable DRIVE-CLiQ cables that have been approved by Siemens for the particular application.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) Control Unit CU310-2 PN (PROFINET) 7.3.1 Description The Control Unit CU310-2 PN (PROFINET) is a control module for single drives in which the open-loop and closed-loop control functions of the drive are implemented. It controls the Power Modules in the blocksize format via the PM-IF interface and is mounted directly on the Power Module.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2 Interface description 7.3.2.1 Overview Figure 7-2 CU310-2 PN overview of interfaces Note The PROFIBUS address switch on the CU310-2 PN has no function. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) The interface to the Power Module is located at the rear of the CU310-2 PN. Figure 7-3 CU310-2 PN interface to the Power Module (PM-IF) 7.3.2.2 X22 serial interface (RS232) Table 7- 2 X22 serial interface (RS232)
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.3 X23 HTL/TTL/SSI encoder interface Table 7- 3 X23 HTL/TTL/SSI encoder interface Signal name Technical data +Temp KTY or PTC input SSI_CLK SSI clock, positive SSI_XCLK SSI clock, negative P encoder 5 V / 24 V Encoder power supply...
Page 266
AN_SSI_XDAT, BN, RN not connected to X23 See SINAMICS S120/S150 List Manual for setting the mode Other signal levels according to the RS422 specification. The absolute level of the individual signals varies between 0 V and Vcc of the measuring system.
Page 267
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) Encoder cables Encoder type Maximum encoder cable length in m HTL unipolar HTL bipolar up to 100 (depending on the baud rate) 100 m with remote sense Because the transmission technology is more robust, the bipolar connection should always be used.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.4 X100 DRIVE-CLiQ interface Table 7- 5 X100 DRIVE-CLiQ interface Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use...
• Make sure that you connect the KTY temperature sensor with the correct polarity. Further information regarding the temperature sensor may be found in the SINAMICS S120 Commissioning Manual, "Temperature sensors for SINAMICS components" section. The maximum length of the temperature sensor cable is 300 m. The cables must be shielded.
Page 270
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) EP terminal The pulse inhibit function (EP) is only available when Integrated Basic Functions are enabled. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.6 X121 digital inputs/outputs Table 7- 7 X121 digital inputs and bidirectional digital inputs/outputs Terminal Designation Technical data DI 0 Voltage: -3 … 30 VDC Current consumption, typical: 6 mA at 24 V DI 1 Electrical isolation: via optocoupler DI 2...
Page 272
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) Note An open input is interpreted as "low". Terminal M2 must be connected so that the digital inputs (DI0 ... DI3) can be used. This is achieved through one of the following measures: •...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.7 X124 Electronics power supply Table 7- 8 X124 Electronics power supply Terminal Designation Technical data Electronics power supply Voltage: 24 VDC (20.4 ... 28.8 VDC) Current consumption: Max.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.8 X127 LAN (Ethernet) Table 7- 9 X127 LAN (Ethernet) Signal name Technical data Ethernet transmit data + Ethernet transmit data - Ethernet receive data + Reserved, do not use Reserved, do not use Ethernet receive data -...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.9 X130 digital input (fail safe) digital output Table 7- 10 X130 digital input / fail-safe digital output Terminal Designation Technical data DI 22+ Voltage: -3 … 30 VDC Current consumption, typical: 6 mA at 24 V DI 22- Electrical isolation: via optocoupler...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.10 X131 digital inputs/outputs and analog input Table 7- 11 X131 bidirectional digital inputs/outputs and analog input Terminal Designation Technical data DI/DO 12 As input: Voltage: -3 … 30 VDC DI/DO 13 Current consumption, typical: 5 mA at 24 V Level (incl.
Page 277
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) Note Permissible voltage values at the analog input The common-mode range must not be violated in order to avoid incorrect results of the analog-digital conversion. This means that the analog differential voltage signals can have a maximum offset voltage of +/- 15 V with respect to the reference potential.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.11 X150 P1/P2 PROFINET Table 7- 12 X150 P1 and X150 P2 PROFINET Signal name Technical data Receive data + Receive data - Transmit data + Reserved, do not use Reserved, do not use Transmit data -...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.2.12 Measuring sockets Table 7- 14 Measuring sockets T0, T1, T2 Socket Function Technical data Measuring socket 0 Voltage: 0 … V Resolution: 8 bits Measuring socket 1 Load current: max.
CU310-2 PN Inserting the memory card The memory card in a faulty CU310-2 PN If you are returning a faulty CU310-2 PN to Siemens, remove the memory card and keep it in a safe place. This ensures that all your saved data (firmware, licenses, parameters) will be available to you immediately again to commission a replacement unit.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.3 Connection examples CU310-2 PN without safety function Figure 7-6 Connection example, CU310-2 PN without safety function AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 282
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) CU310-2 PN with safety function Figure 7-7 Connection example, CU310-2 PN with safety function AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.4 Meaning of the LEDs 7.3.4.1 Function of the LEDs There are four LEDs on the front panel of the CU310-2 PN's housing (see CU310-2 PN Interface Overview (Page 263).) Table 7- 16 LEDs...
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) 7.3.4.2 Behavior of the LEDs during booting Table 7- 17 Load software State Comment OUT>5V Orange Orange Orange Orange POWER ON All LEDs light up for approx. 1 s Hardware reset After pressing the RESET button the LEDs light up for approx.
Green/oran Flashing light Recognition of the component via LED is 2 Hz activated (see SINAMICS S120/S150 List Manual.) red/orange Note: Both options depend on the LED status when component recognition is activated. Cyclic communication has not (yet) taken place.
Control Units, Control Unit Adapters and operating components 7.3 Control Unit CU310-2 PN (PROFINET) Color State Description / cause Remedy OUT > 5 V Orange Continuous light The voltage of the electronics power supply for the measuring system is 24 V. Make sure that the encoder connected is designed for a 24 V supply.
At the housing with M4/3 Nm screw Response time The response time of digital inputs/outputs depends on the evaluation. Weight 0,95 You will find information on this topic in the SINAMICS S120/S150 List Manual, Chapter "Function block diagrams." AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) Control Unit CU310-2 DP (PROFIBUS) 7.4.1 Description The CU310-2 DP Control Unit (PROFIBUS) is a control module for single-motor drives in which the open-loop and closed-loop control functions of the drive are implemented. It controls the Power Modules in the blocksize format via the PM-IF interface.
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2 Interface description 7.4.2.1 Overview Figure 7-9 CU310-2 DP interface overview The interface to the Power Module is located at the rear of the CU310-2 DP. Figure 7-10 CU310-2 DP interface to the Power Module (PM-IF) AC Drive...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.2 X21 PROFIBUS The PROFIBUS interface X21 can be operated isochronously. Table 7- 22 X21 PROFIBUS interface Signal name Meaning Range Not assigned M24_SERV Teleservice supply, ground RxD/TxD-P Receive/transmit data P (B) RS485...
The factory setting for the rotary coding switches is 0 The PROFIBUS address is set as follows: 1. via a parameter (see SINAMICS S120/S150 List Manual) – To set the bus address for a PROFIBUS node using STARTER, first set the rotary...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.4 X22 serial interface (RS232) Table 7- 24 X22 serial interface (RS232) Signal name Technical data Reserved, do not use XRXD_RS232 Receive data XTXD_RS232 Transmit data Reserved, do not use Ground Reserved, do not use...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.5 X23 HTL/TTL/SSI encoder interface Table 7- 25 X23 HTL/TTL/SSI encoder interface Signal name Technical data +Temp KTY or PTC input SSI_CLK SSI clock, positive SSI_XCLK SSI clock, negative P encoder 5 V / 24 V Encoder power supply...
Page 294
AN_SSI_XDAT, BN, RN not connected to X23 See SINAMICS S120/S150 List Manual for setting the mode Other signal levels according to the RS422 specification. The absolute level of the individual signals varies between 0 V and Vcc of the measuring system.
Page 295
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) Encoder cables Encoder type Maximum encoder cable length in m HTL unipolar HTL bipolar up to 100 (depending on the baud rate) 100 m with remote sense Because the transmission technology is more robust, the bipolar connection should always be used.
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.6 X100 DRIVE-CLiQ interface Table 7- 27 X100 DRIVE-CLiQ interface Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use...
• Make sure that you connect the KTY temperature sensor with the correct polarity. Further information regarding the temperature sensor may be found in the SINAMICS S120 Commissioning Manual, "Temperature sensors for SINAMICS components" section. The maximum length of the temperature sensor cable is 300 m. The cables must be shielded.
Page 298
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) EP terminal The pulse inhibit function (EP) is only available when Integrated Basic Functions are enabled. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.8 X121 digital inputs/outputs Table 7- 29 X121 digital inputs and bidirectional digital inputs/outputs Terminal Designation Technical data DI 0 Voltage: -3 … 30 VDC Current consumption, typical: 6 mA at 24 V DI 1 Electrical isolation: via optocoupler DI 2...
Page 300
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) Note An open input is interpreted as "low". Terminal M2 must be connected so that the digital inputs (DI0 ... DI3) can be used. This is achieved through one of the following measures: •...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.9 X124 Electronics power supply Table 7- 30 X124 Electronics power supply Terminal Designation Technical data Electronics power supply Voltage: 24 VDC (20.4 ... 28.8 VDC) Current consumption: Max.
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.10 X127 LAN (Ethernet) Table 7- 31 X127 LAN (Ethernet) Signal name Technical data Ethernet transmit data + Ethernet transmit data - Ethernet receive data + Reserved, do not use Reserved, do not use Ethernet receive data -...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.11 X130 digital input (fail safe) digital output Table 7- 32 X130 digital input / fail-safe digital output Terminal Designation Technical data DI 22+ Voltage: -3 … 30 VDC Current consumption, typical: 6 mA at 24 V DI 22- Electrical isolation: via optocoupler...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.12 X131 digital inputs/outputs and analog input Table 7- 33 X131 bidirectional digital inputs/outputs and analog input Terminal Designation Technical data DI/DO 12 As input: Voltage: -3 … 30 VDC DI/DO 13 Current consumption, typical: 5 mA at 24 V Level (incl.
Page 305
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) Note Permissible voltage values at the analog input The common-mode range must not be violated in order to avoid incorrect results of the analog-digital conversion. This means that the analog differential voltage signals can have a maximum offset voltage of +/- 15 V with respect to the reference potential.
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.2.13 Measuring sockets Table 7- 34 Measuring sockets T0, T1, T2 Socket Function Technical data Measuring socket 0 Voltage: 0 … V Resolution: 8 bits Measuring socket 1 Load current: max.
CU310-2 DP Inserting the memory card The memory card in a faulty CU310-2 DP If you are returning a faulty CU310-2 DP to Siemens, remove the memory card and keep it in a safe place. This ensures that all your saved data (firmware, licenses, parameters) will be available to you immediately again to commission a replacement unit.
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.3 Connection examples CU310-2 DP without safety function Figure 7-13 Connection example, CU310-2 DP without safety function AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 309
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) CU310-2 DP with safety function Figure 7-14 Connection example, CU310-2 DP with safety function AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.4 Meaning of the LEDs 7.4.4.1 Function of the LEDs There are four LEDs on the front panel of the CU310-2 DP housing (see CU310-2 DP Interface Overview (Page 289).) Table 7- 36 LEDs...
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.4.2 Behavior of the LEDs during booting Table 7- 37 Load software State Comment OUT > 5V Orange Orange Orange Orange POWER ON All LEDs light up for approx. 1 s Hardware After pressing the RESET button the reset...
Green/oran Flashing light Recognition of the component via LED is activated 2 Hz (see SINAMICS S120/S150 List Manual). Note: red/orange Both possibilities depend on the status of the LED when activating. Cyclic communication is not (yet) running.
Page 313
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) Color State Description / cause Remedy OUT > 5 V Orange Continuous light The voltage of the electronics power supply for the measuring system is 24 V. Make sure that the encoder connected is designed for a 24 V supply.
Control Units, Control Unit Adapters and operating components 7.4 Control Unit CU310-2 DP (PROFIBUS) 7.4.5 Dimension drawing Figure 7-15 Dimension drawing, Control Unit CU310-2 DP, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
At the housing with M4/3 Nm screw Response time The response time of digital inputs/outputs depends on the evaluation. Weight 0,95 You will find information on this topic in the SINAMICS S120/S150 List Manual, Chapter "Function block diagrams". AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.5 Control Unit Adapter CUA31 Control Unit Adapter CUA31 7.5.1 Description The CUA31 Control Unit Adapter is used to connect a Power Module blocksize to an existing DC/AC group with a higher-level control module, e.g. a CU320-2. Since the closed-loop control is realized externally, for operation, a SINAMICS, SIMOTION, or SINUMERIK closed- loop control is always required for several axes.
Control Units, Control Unit Adapters and operating components 7.5 Control Unit Adapter CUA31 7.5.2 Interface description 7.5.2.1 Overview Figure 7-16 Interface overview of the CUA31 AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.5 Control Unit Adapter CUA31 7.5.2.2 X200-X202 DRIVE-CLiQ interfaces Table 7- 42 X200-X202 DRIVE-CLiQ interfaces Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use...
H → L: 1000 μs Type: Screw-type terminal 1 (Page 437) Max. cross-section that can be connected 1.5 mm Further information regarding the temperature sensor may be found in the SINAMICS S120 Commissioning Manual, Section "Temperature sensors for SINAMICS components." Temperature sensor input The temperature sensor is required for motors where the temperature value is not transmitted via DRIVE-CLiQ.
Control Units, Control Unit Adapters and operating components 7.5 Control Unit Adapter CUA31 7.5.2.4 X224 electronics power supply Table 7- 44 X224 electronics power supply Terminal Function Technical data Electronics power supply Voltage: 24 VDC (20.4 ... 28.8 VDC) Current consumption: max. 0.8 A (without DRIVE-CLiQ) Electronics power supply Max.
The component is ready for operation and cyclic DRIVE-CLiQ communication is taking place. Cause and rectification of faults Information about the cause and rectification of faults can be found in the SINAMICS S120 Commissioning Manual. 7.5.5 Dimension drawing...
Control Units, Control Unit Adapters and operating components 7.5 Control Unit Adapter CUA31 7.5.6 Technical data Table 7- 46 Technical data CUA31 6SL3040-0PA00-0AA0 / 6SL3040-0PA00-0AA1 Unit Value Electronics power supply Voltage 24 DC (20.4 ... 28.8) Current (without DRIVE-CLiQ) Power loss Maximum DRIVE-CLiQ cable length CUA31 with order number 6SL3040-0PA00-0AA0 CUA31 from order number 6SL3040-0PA00-0AA1...
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 Control Unit Adapter CUA32 7.6.1 Description The Control Unit Adapter CUA32 is used to connect a Power Module blocksize to an existing DC/AC group with a higher-level control module, e.g. a CU320-2. Since the closed-loop control is realized externally, for operation, a SINAMICS, SIMOTION, or SINUMERIK closed- loop control is always required for several axes.
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 7.6.2 Interface description 7.6.2.1 Overview Figure 7-19 Interface overview CUA32 AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 7.6.2.2 X200-X202 DRIVE-CLiQ interfaces Table 7- 48 X200-X202 DRIVE-CLiQ interfaces Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use...
H → L: 1000 μs Type: Screw-type terminal 1 (Page 437) Max. cross-section that can be connected 1.5 mm Further information regarding the temperature sensor may be found in the SINAMICS S120 Commissioning Manual, Section "Temperature sensors for SINAMICS components." Temperature sensor input The temperature sensor is required for motors where the temperature value is not transmitted via DRIVE-CLiQ.
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 7.6.2.4 X220 HTL/TTL/SSI encoder interface Table 7- 50 X220 HTL/TTL/SSI encoder interface Signal name Technical data +Temp KTY or PTC input SSI_CLK SSI clock, positive SSI_XCLK SSI clock, negative P encoder 5 V / 24 V Encoder power supply P encoder 5 V / 24 V...
Page 328
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 Table 7- 51 Specification of measuring systems that can be connected Parameter Designation Threshold Min. Type Max. Unit High signal level Hdiff (TTL bipolar at X220) Low signal level Ldiff (TTL bipolar at X220) High signal level...
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 7.6.2.5 X224 electronics power supply Table 7- 52 X224 electronics power supply Terminal Function Technical data Electronics power supply Voltage: 24 VDC (20.4 ... 28.8 VDC) Current consumption: max. 0.8 A (without DRIVE-CLiQ Electronics power supply and encoder) Electronics ground...
If an encoder that is designed for a 5 V power supply is operated with a 24 V power supply, this can destroy the encoder electronics. Cause and rectification of faults Information about the cause and rectification of faults can be found in the SINAMICS S120 Commissioning Manual. AC Drive...
Control Units, Control Unit Adapters and operating components 7.6 Control Unit Adapter CUA32 7.6.5 Dimension drawing Figure 7-21 Dimension drawing of Control Unit Adapter CUA32, all data in mm and (inches) 7.6.6 Technical data Table 7- 54 Technical data CUA32 6SL3040-0PA01-0AA0 Unit Value...
Control Units, Control Unit Adapters and operating components 7.7 Mounting Control Units and Control Unit Adapters Mounting Control Units and Control Unit Adapters Power Modules Blocksize Control Unit (CU310-2 PN / DP) and Control Unit Adapter (CUA31 / CUA32) can be mounted onto Power Modules Blocksize of any size.
Page 333
Control Units, Control Unit Adapters and operating components 7.7 Mounting Control Units and Control Unit Adapters Removal 1. Press the blue locking latch downwards (see arrow). 2. Remove the Control Unit / Control Unit Adapter towards the front. Figure 7-22 Removing the CU310-2 PN from the PM340 Power Module Chassis 1.
Control Units, Control Unit Adapters and operating components 7.8 Basic Operator Panel BOP20 Basic Operator Panel BOP20 7.8.1 Description The Basic Operator Panel BOP20 is a basic operator panel with six keys and a backlit display unit. The BOP20 can be inserted on the CU310-2 DP and CU310-2 PN SINAMICS Control Units and operated.
Page 335
Control Units, Control Unit Adapters and operating components 7.8 Basic Operator Panel BOP20 Overview of displays and keys Figure 7-24 Overview of displays and keys Table 7- 55 Displays Display Meaning Top left The active drive object of the BOP is displayed here. 2 positions The displays and key operations always refer to this drive object.
Page 336
Control Units, Control Unit Adapters and operating components 7.8 Basic Operator Panel BOP20 BOP20 keyboard Table 7- 56 Assignment of the BOP20 keyboard Name Meaning Powering-up the drives for which the command "ON/OFF1", "OFF2" or "OFF3" should come from the BOP. Power-down the drives for which the "ON/OFF1,"...
Control Units, Control Unit Adapters and operating components 7.8 Basic Operator Panel BOP20 7.8.3 Mounting NOTICE Damage when using the BOP The interface for the BOP20 on the CU310-2 may be damaged when the BOP20 is used. • Make sure that you insert and withdraw the BOP20 straight into/out of the CU310-2 and that it is not tilted up or down.
Page 338
2. Keep the latching cams pressed together and pull the BOP20 straight out. 3. Insert the blanking cover. Display and operator controls of the BOP20 For information about display and operator controls of the BOP20, refer the SINAMICS S120 Commissioning Manual. AC Drive...
Page 339
Control Units, Control Unit Adapters and operating components 7.8 Basic Operator Panel BOP20 AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
When opening plug connections in operation, arcs can result in severe injury or death. • Disconnect or connect the encoder cables to Siemens motors, which are not expressly released for connecting and disconnecting during operation, in a deenergized condition only.
Page 342
Supplementary system components and encoder system integration 8.1 Sensor Modules Note Diminished level of interference immunity due to equalizing currents via the electronics ground Ensure that there is no electrical connection between the encoder system housing and the signal cables, or the encoder system electronics. If this is not carefully observed, the system may not be able to reach the required interference immunity level.
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.2 Sensor Module Cabinet-Mounted SMC10 8.1.2.1 Description The Sensor Module Cabinet-Mounted SMC10 evaluates encoder signals and transmits the speed, actual position value, rotor position and, if necessary, the motor temperature via DRIVE-CLiQ to the Control Unit.
Page 344
Supplementary system components and encoder system integration 8.1 Sensor Modules X500 DRIVE-CLiQ interface Table 8- 1 X500: DRIVE-CLiQ interface Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use Reserved, do not use...
Page 345
Supplementary system components and encoder system integration 8.1 Sensor Modules X520 encoder system interface Table 8- 2 X520: Encoder system interface Signal name Technical data Reserved, do not use Reserved, do not use Resolver signal A (sin+) Inverted resolver signal A (sin-) Ground Ground (for internal shield) Resolver signal B (cos+)
Page 346
Supplementary system components and encoder system integration 8.1 Sensor Modules WARNING Danger to life due to electric shock in the event of voltage flashovers at the temperature sensor Voltage flashovers in the signal electronics can occur in motors without safe electrical separation of the temperature sensors.
Red/oran See SINAMICS S120/S150 List Manual for the parameters to activate the recognition of components via LED Cause and rectification of faults The following documents contain information about the cause of faults and how they can be...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.2.4 Dimension drawing Figure 8-2 Dimension drawing of the Sensor Module Cabinet SMC10, all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.2.5 Mounting Installation 1. Tilt the component backwards slightly and attach it to the DIN rail using the hooks. 2. Swivel the component onto the DIN rail until you hear the mounting slide at the rear latch into position.
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.2.6 Technical data Table 8- 5 Technical data 6SL3055-0AA00-5AAx Unit Value Electronics power supply Voltage 24 (20,4 … 28,8) Current (without encoder system) ≤ 0,20 Current (with encoder system) ≤ 0,35 Power loss ≤...
Page 351
Supplementary system components and encoder system integration 8.1 Sensor Modules The ratio between the ohmic resistance R and the inductance L (the primary winding of the resolver) determines whether the resolver can be evaluated with the SMC10. See the following diagram: Figure 8-4 Connectable impedances with an excitation frequency f = 5000 Hz AC Drive...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.3 Sensor Module Cabinet-Mounted SMC20 8.1.3.1 Description The Sensor Module Cabinet-Mounted SMC20 evaluates encoder signals and transmits the speed, actual position value, rotor position and, if necessary, the motor temperature and reference point via DRIVE-CLiQ to the Control Unit.
Page 353
Supplementary system components and encoder system integration 8.1 Sensor Modules X500 DRIVE-CLiQ interface Table 8- 7 X500: DRIVE-CLiQ interface Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use Reserved, do not use...
Page 354
Supplementary system components and encoder system integration 8.1 Sensor Modules X520 encoder system interface Table 8- 8 X520: Encoder system interface Signal name Technical data P encoder Encoder power supply M encoder Ground for encoder power supply Incremental signal A Inverse incremental signal A Ground Ground (for internal shield)
Page 355
Supplementary system components and encoder system integration 8.1 Sensor Modules NOTICE Damage to motor in the event of incorrectly connected KTY temperature sensor A KTY temperature sensor connected with incorrect polarity cannot detect if the motor overheats. Overheating can cause damage to the motor. •...
Red / Orange See SINAMICS S120/S150 List Manual for the parameters to activate the recognition of components via LED Cause and rectification of faults The following documents contain information about the cause of faults and how they can be...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.3.4 Dimension drawing Figure 8-6 Dimension drawing of the Sensor Module Cabinet SMC20, all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.3.5 Mounting Installation 1. Tilt the component backwards slightly and attach it to the DIN rail using the hooks. 2. Swivel the component onto the DIN rail until you hear the mounting slide at the rear latch into position.
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.3.6 Technical data Table 8- 11 Technical data 6SL3055-0AA00-5BAx Unit Value Electronics power supply Voltage 24 (20,4 … 28,8) Current (without encoder system) ≤ 0,20 Current (with encoder system) ≤ 0,35 Power loss ≤...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.4 Sensor Module Cabinet-Mounted SMC30 8.1.4.1 Description The Sensor Module Cabinet-Mounted SMC30 evaluates encoder signals and transmits the speed, actual position value and, if necessary, the motor temperature and reference point via DRIVE-CLiQ to the Control Unit.
Page 361
Supplementary system components and encoder system integration 8.1 Sensor Modules X500 DRIVE-CLiQ interface Table 8- 12 X500: DRIVE-CLiQ interface Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data - Reserved, do not use Reserved, do not use...
Page 362
Overheating can cause damage to the motor. • Connect a KTY temperature sensor with the correct polarity. You can find information for parameterizing the KTY temperature sensor in the SINAMICS S120 Function Manual (FH1) in Chapter "Monitoring and protective functions/thermal motor monitoring". AC Drive...
Page 363
Supplementary system components and encoder system integration 8.1 Sensor Modules WARNING Danger to life due to electric shock in the event of voltage flashovers at the temperature sensor Voltage flashovers in the signal electronics can occur in motors without safe electrical separation of the temperature sensors.
Page 364
Supplementary system components and encoder system integration 8.1 Sensor Modules X521 / X531 alternative encoder system interface Table 8- 14 X521/X531: Alternative encoder system interface Designation Technical data X521 Incremental signal A Inverse incremental signal A Incremental signal B Inverse incremental signal B Reference signal R Inverse reference signal R CTRL...
Page 365
Overheating can cause damage to the motor. • Connect a KTY temperature sensor with the correct polarity. You can find information for parameterizing the KTY temperature sensor in the SINAMICS S120 Function Manual (FH1) in Chapter "Monitoring and protective functions/thermal motor monitoring". Note The maximum length of the temperature sensor cable is 100 m.
Page 366
Supplementary system components and encoder system integration 8.1 Sensor Modules Note The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply voltage is looped through. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.4.3 Connection examples Connection example 1: HTL encoder, bipolar, with reference signal Figure 8-10 Connection example 1: HTL encoder, bipolar, with reference signal Signal cables must be twisted in pairs to improve immunity to induced noise. Connection example 2: HTL encoder, unipolar, with reference signal Figure 8-11 Connection example 2: HTL encoder, unipolar, with reference signal...
Page 368
Supplementary system components and encoder system integration 8.1 Sensor Modules Figure 8-12 Photo of connection example 2: SMC30, 30 mm wide Note: Diagram of the wire jumpers to connect unipolar HTL encoders with reference signal AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
24 V supply, this can destroy the encoder electronics. See SINAMICS S120/S150 List Manual for the parameters to activate the recognition of components via LED Cause and rectification of faults The following documents contain information about the cause of faults and how they can be...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.4.5 Dimension drawing Figure 8-13 Dimension drawing of the Sensor Module Cabinet SMC30, all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.4.6 Mounting Installation 1. Tilt the component backwards slightly and attach it to the DIN rail using the hooks. 2. Swivel the component onto the DIN rail until you hear the mounting slide at the rear latch into position.
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.4.7 Protective conductor connection and shield support Shield contacts are only required if the system is connected to X521/X531. ① Protective conductor connection M4 / 1.8 Nm ② Shield connection terminal, Weidmüller company, type: KLBÜ CO1, order number: 1753311001 Figure 8-15 Shield support and protective conductor connection...
Supplementary system components and encoder system integration 8.1 Sensor Modules 8.1.4.8 Technical data Table 8- 17 Technical data 6SL3055-0AA00-5CA2 Unit Value Electronics power supply Voltage 24 (20,4 … 28,8) Current (without encoder system) ≤ 0,20 Current (with encoder system) ≤ 0,55 Power loss ≤...
Page 374
A and the next but one rising edge of ALo-BHi track B. Additional information on setting the "Zero pulse active time" can be found in the manual: SINAMICS S120, Function Manual, tolerant encoder monitoring for SMC30 AC Drive...
Page 375
Supplementary system components and encoder system integration 8.1 Sensor Modules Table 8- 19 Encoders that can be connected X520 X521 X531 Track Remote Sense (SUB-D) (terminal) (terminal) monitoring HTL bipolar 24 V HTL unipolar 24 V Yes (however, a bipolar connection is recommended) TTL bipolar 24 V TTL bipolar 5 V...
Page 376
Supplementary system components and encoder system integration 8.1 Sensor Modules SSI encoder Figure 8-16 Maximum cable lengths depending on the SSI baud rate for SSI encoders Encoders with 5 V supply connected to X521/X531 For encoders with a 5 V supply at X521/X531, the cable length depends on the encoder current (for 0.5 mm cable cross-sections): Figure 8-17...
Page 377
Supplementary system components and encoder system integration 8.1 Sensor Modules Encoders without remote sense For encoders without Remote Sense, the permissible cable length is restricted to 100 m. Reason: The voltage drop depends on the cable length and the encoder current. Figure 8-18 Signal characteristic of track A and track B between two edges: Time between two edges with pulse encoders...
The DC power supply should be set to 26 V. This ensures that the supply voltage for the brake remains within the permissible range when the following conditions are fulfilled: • Use of Siemens three-phase motors • Use of Siemens MOTION-CONNECT power cables • Motor cable lengths: max. 100 m AC Drive...
Supplementary system components and encoder system integration 8.2 Option module Safe Brake Relay 8.2.3 Interface description 8.2.3.1 Overview ① Connection for the solenoid of the motor brake ② Connection for the 24 VDC power supply ③ Connection for the pre-fabricated (CTRL) to the Power Module, Blocksize format Figure 8-20 Interface description: Safe Brake Relay 8.2.3.2...
Supplementary system components and encoder system integration 8.2 Option module Safe Brake Relay 8.2.5 Dimension drawing Figure 8-22 Dimension drawing of Safe Brake Relay, all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Supplementary system components and encoder system integration 8.2 Option module Safe Brake Relay 8.2.6 Mounting Installation with PM240-2 Power Modules The Safe Brake Relay is installed at the rear of the cabinet next to the Power Module. Installation with PM340 Power Modules The Safe Brake Relay is either installed beneath the Power Module on the screening kit or alternatively on the cabinet rear panel ①...
Supplementary system components and encoder system integration 8.3 Safe Brake Adapter optional module Safe Brake Adapter optional module 8.3.1 Description The Safe Brake Adapter (SBA) is required to implement Safe Brake Control (SBC) in conjunction with Power Modules in the chassis format. The Safe Brake Control (SBC) is a safety function, that is used in safety-related applications, e.g.
Supplementary system components and encoder system integration 8.3 Safe Brake Adapter optional module 8.3.2 Safety instructions for Safe Brake Adapters WARNING Danger to life due to release of motor brake when connection cable is damaged If the connection cable between the Safe Brake Adapter and the motor brake is broken or short circuited, this may result in the motor brake being supplied with power and released.
Supplementary system components and encoder system integration 8.3 Safe Brake Adapter optional module 8.3.3.2 X11 interface to the Control Interface Module Table 8- 25 X11 interface to the Control Interface Module Terminal Signal Description Technical data X11.1 Control channel 1 Connection to Control Interface Board, X46.1 X11.2 Control channel 2...
Supplementary system components and encoder system integration 8.3 Safe Brake Adapter optional module 8.3.3.4 X14 load connection Table 8- 27 X14 load connection Terminal Signal Technical data X14.1 BR L Supply voltage: AC 230 V Current consumption: 2 A X14.2 BR N Max.
Supplementary system components and encoder system integration 8.3 Safe Brake Adapter optional module 8.3.4 Connection example Figure 8-26 Connection example for a Safe Brake Adapter 8.3.5 Dimension drawing Figure 8-27 Dimension drawing of Safe Brake Adapter, all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Supplementary system components and encoder system integration 8.3 Safe Brake Adapter optional module 8.3.6 Mounting Safe Brake Adapter The Safe Brake Adapter is designed for mounting on a rail in accordance with EN 60715 Housing cover after replacing the fuse An adhesive label is provided on the housing cover indicating the position of the connector.
Damage or malfunctions can occur on the devices or system when DRIVE-CLiQ cables are used that are either incorrect or have not been approved for this purpose. • Only use suitable DRIVE-CLiQ cables that have been approved by Siemens for the particular application.
Accessories 9.1 DRIVE-CLiQ cabinet bushing 9.1.2 Interface description 9.1.2.1 Overview DRIVE-CLiQ cabinet bushing for DRIVE-CLiQ cables with DRIVE-CLiQ connectors ① Protective cap, Yamaichi, order number: Y-ConAS-24-S ② DRIVE-CLiQ interface on the outside (to connect DRIVE-CLiQ signal cables MOTION- CONNECT with IP67 degree of protection) ③...
Accessories 9.1 DRIVE-CLiQ cabinet bushing 9.1.3 Dimension drawings Figure 9-3 Dimension drawing of the DRIVE-CLiQ cabinet gland, all dimensions in mm and (inches) ① Cabinet panel ② Flange, SW18 Figure 9-4 Dimension drawing of the DRIVE-CLiQ cabinet bushing M12, all dimensions in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Accessories 9.1 DRIVE-CLiQ cabinet bushing 9.1.4 Installation 9.1.4.1 DRIVE-CLiQ cabinet bushing for cables with DRIVE-CLiQ connectors In order to install the DRIVE-CLiQ cabinet gland, you must make a cutout in the control cabinet panel as shown in the diagram below. Figure 9-5 Cutout in the control cabinet, all dimensions in mm and (inches) AC Drive...
Page 395
Accessories 9.1 DRIVE-CLiQ cabinet bushing Installation 1. Insert the DRIVE CLiQ cabinet bushing from the outside of the control cabinet through the cutout in the control cabinet. 2. Attach the DRIVE-CLiQ cabinet bushing to the outer control cabinet panel using 2 M3 screws and 2 nuts.
Accessories 9.1 DRIVE-CLiQ cabinet bushing 9.1.4.2 DRIVE-CLiQ cabinet bushing for cables with M12 plug/socket Prepare the cabinet panel for mounting the DRIVE-CLiQ cabinet bushing M12 as shown below. The removable O ring can be screwed from the inside or the outside. Mounting from the inside using an O ring that can be screwed ①...
Accessories 9.1 DRIVE-CLiQ cabinet bushing Installation 1. Insert the DRIVE-CLiQ cabinet bushing through the opening in the cabinet. 2. Fasten the DRIVE-CLiQ cabinet bushing using the associated O ring with a tightening torque of 3 to 4 Nm ① Flange, SW18 ②...
Damage or malfunctions can occur on the devices or system when DRIVE-CLiQ cables are used that are either incorrect or have not been approved for this purpose. • Only use suitable DRIVE-CLiQ cables that have been approved by Siemens for the particular application.
Accessories 9.2 DRIVE-CLiQ coupling 9.2.3 Dimension drawing Figure 9-11 Dimension drawing of the DRIVE-CLiQ coupling, all dimensions in mm and (inches) 9.2.4 Mounting ① Contact surface Figure 9-12 Hole drilling pattern for installation AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Accessories 9.2 DRIVE-CLiQ coupling Installation 1. Attach the DRIVE-CLiQ coupling to the mounting surface as shown in the drilling pattern. 2. Remove the protective caps of the DRIVE-CLiQ coupling. 3. Latch the DRIVE-CLiQ connectors at both sides of the DRIVE-CLiQ coupling. 9.2.5 Technical data Table 9- 2...
Accessories 9.3 Mounting frame Mounting frame 9.3.1 Description The 240-2 Push Through Power Modules should be installed using a mounting frame inside the cabinet. This mounting frame includes the necessary seals and frame to ensure compliance with degree of protection IP54. Order numbers ●...
Accessories 9.3 Mounting frame 9.3.2 Dimension drawings Dimension drawings of mounting frame, frame sizes FSA to FSC Figure 9-13 Dimension drawing of mounting frame, frame size FSA and FSB, all data in mm and (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Accessories 9.3 Mounting frame Figure 9-14 Dimension drawing of mounting frame, frame size FSC, all data in mm and (inches) 9.3.3 Mounting Installation steps 1. Make an installation cutout and drill holes for the Power Module and the mounting frame according to the drilling pattern.
Accessories 9.4 Shield connection kit Shield connection kit 9.4.1 Description A shield connection kit is offered as an optional shield support for PM340 Power Modules in frame sizes FSA to FSF. It is used to connect the shields of two power cables. The shield connection kit is screwed directly onto the panel of the control cabinet for frame sizes FSA to FSC.
Accessories 9.4 Shield connection kit 9.4.2 Dimension drawings 9.4.2.1 Shield connection kits Dimension drawings, screening kit, frame sizes FSA to FSC Figure 9-16 Dimension drawing of the shield connection kit for PM340 Power Modules, frame size FSA, all data in mm (inches) Figure 9-17 Dimension drawing of the shield connection kit for PM340 Power Modules, frame size FSB, all data in mm...
Page 406
Accessories 9.4 Shield connection kit Figure 9-18 Dimension drawing of the shield connection kit for PM340 Power Modules, frame size FSC, all data in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Accessories 9.4 Shield connection kit 9.4.2.2 Blocksize Power Modules with shield connection kit Dimension drawings of Power Modules with shield connection kit, frame sizes FSA to FSF Figure 9-19 Dimension drawing of PM340 Power Module with shield connection kit, frame size FSA, dimensions in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 408
Accessories 9.4 Shield connection kit Figure 9-20 Dimension drawing of PM340 Power Module with shield connection kit, frame size FSB, dimensions in mm (inches) Figure 9-21 Dimension drawing of PM340 Power Module with shield connection kit, frame size FSC, dimensions in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 409
Accessories 9.4 Shield connection kit Figure 9-22 Dimension drawing of PM340 Power Module with shield connection kit, frame size FSD with integrated line filter, dimensions in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 410
Accessories 9.4 Shield connection kit Figure 9-23 Dimension drawing of PM340 Power Module with shield connection kit, frame size FSE with integrated line filter, dimensions in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 411
Accessories 9.4 Shield connection kit Figure 9-24 Dimension drawing of PM340 Power Module with shield connection kit, frame size FSF with integrated line filter, dimensions in mm (inches) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Accessories 9.4 Shield connection kit 9.4.3 Mounting 9.4.3.1 PM340 Blocksize Power Modules The diagrams show the mounting of shield connection kits on PM340 Power Modules with various frame sizes. Frame size FSA Figure 9-25 Mounting: Shield connection kit on PM340 Power Module (FSA) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 413
Accessories 9.4 Shield connection kit Frame sizes FSB/FSC ① Rating plate ② Ferrite core Figure 9-26 Mounting: Shield connection kit and ferrite core on a PM340 Power Module (FSB / FSC) Mounting the ferrite core The ferrite core supplied should be attached to the line cable in order to dampen radio cable disturbances.
Page 414
Accessories 9.4 Shield connection kit Frame sizes FSD/FSE Figure 9-28 Mounting: Shield connection kit on PM340 Power Module PM340 (FSD/FSE) Frame size FSF Figure 9-29 Mounting: Shield connection kit on PM340 Power Module (FSF) AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Accessories 9.4 Shield connection kit 9.4.3.2 Power cable connection The diagram shows the connection of the power cables at the screening kit using the Power Module PM340, frame size FSD/FSE as an example. ① Signal cable ② Mounting clip ③ Protective braided shield ④...
Cabinet design and EMC for components, Blocksize format 10.1 General information The SINAMICS S components are designed in accordance with degree of protection IPXXB according to EN 60529 and as open-type devices according to UL 50. This ensures protection against electric shock. To also ensure protection against mechanical stress and climatic conditions, the components should only be operated in housing, cabinets or enclosed electrical operating areas that fulfill at least degree of protection IP54 and, as enclosure type 12, are designed according to UL...
Cabinet design and EMC for components, Blocksize format 10.2 Safety instructions for control panel manufacturing 10.2 Safety instructions for control panel manufacturing WARNING Danger to life if the fundamental safety instructions and residual risks are not observed The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death.
● SINAMICS line filter ● Observance of information about cable shielding and equipotential bonding ● Only the recommended Siemens power and signal cables are used ● Only cables from Siemens may be used for DRIVE-CLiQ connections For MOTION-CONNECT cables, refer to catalog PM21...
Cabinet design and EMC for components, Blocksize format 10.4 Cable shielding and routing 10.4 Cable shielding and routing In order to comply with the EMC requirements, certain cables must be routed apart from other cables and from certain components. To full EMC requirements, the following cables must be used with shields: ●...
Page 421
Cabinet design and EMC for components, Blocksize format 10.4 Cable shielding and routing Alternatively, the cable shields can be connected to them metal mounting plate using pipe clamps and serrated rails. The cable length between the shield contact point and the terminals for cable conductors must be kept as short as possible.
Cabinet design and EMC for components, Blocksize format 10.5 24 V DC Supply Voltage 10.5 24 V DC Supply Voltage 10.5.1 General The 24 VDC voltage is required for the power supply: 1. The load voltage of the Control Unit digital outputs The Control Units are supplied with power via the PM-IF.
● Cable routing method according to EN 60204-1 The overcurrent protection devices can be determined according to EN 60204-1, Section 14. Circuit-breakers from Siemens Catalogs LV 1 and LV 1T are recommended as overcurrent protection devices on the primary side.
Cabinet design and EMC for components, Blocksize format 10.5 24 V DC Supply Voltage Table 10- 1 MCBs by conductor cross-section and temperature Conductor cross-section Max. value up to 40° C Max. value up to 55° C 1.5 mm 10 A 2.5 mm 16 A 10 A...
Typical 24 V current consumption of the components A separate 24 V power supply must be used for the SINAMICS S120 drive line-up. The following table can be used to calculate the 24 VDC power supply. The values for typical current consumption are used as a basis for configuration.
Cabinet design and EMC for components, Blocksize format 10.5 24 V DC Supply Voltage 10.5.5 Selecting power supply units You are advised to use the devices in the following table. These devices meet the applicable requirements of EN 60204-1. Table 10- 4 Recommended SITOP Power Rated output Phases...
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6 Connection Methods 10.6.1 DRIVE-CLiQ signal cables 10.6.1.1 Overview To connect DRIVE-CLiQ components, various pre-assembled and non-assembled DRIVE- CLiQ signal cables are available. The following pre-assembled DRIVE-CLiQ signal cables will be discussed in more detail in the next sections: ●...
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.1.2 DRIVE-CLiQ signal cables without 24 V DC cores Pre-assembled DRIVE-CLiQ signal cables without 24 V DC cores are used to connect components with DRIVE-CLiQ connection, which have a separate or external 24 V DC power supply.
DRIVE-CLiQ connection and a direct measuring system equipped with DRIVE-CLiQ ASIC with 8-pin M12 connector. Measuring systems from third-party manufacturers can be directly connected to the SINAMICS S120. Basic cable The pre-assembled basic cable has eight cores, of which four are used for data transmission and two for the 24 V supply.
Page 430
The maximum permissible total cable length between the measuring system and the DRIVE- CLiQ socket of the SINAMICS S120 device is 30 m. For a longer total cable length, data transfer errors may occur. This is the reason that no additional extension can be connected to a 30 m long basic cable.
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.1.5 Comparison of DRIVE-CLiQ signal cables DRIVE-CLiQ signal cables are designed for various applications. The following table provides an overview of the most important properties. Table 10- 8 Properties of DRIVE-CLiQ signal cables DRIVE-CLiQ signal cable DRIVE-CLiQ DRIVE-CLiQ...
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.1.6 Combined use of MOTION-CONNECT 500 and MOTION-CONNECT 800PLUS In principle, MOTION-CONNECT 500 cables and MOTION-CONNECT 800PLUS cables be used together. Basic cables and extensions for MOTION-CONNECT cables with DRIVE-CLiQ connector and M12 socket can be combined without any restrictions.
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.2 Power cables for motors 10.6.2.1 Configuring the cable length Where a longer motor cable is required, a higher rating of Power Module must be selected or the permissible continuous output current I must be reduced in relation to the rated continuous output current I...
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.2.2 Comparison of MOTION-CONNECT power cables MOTION-CONNECT 500 power cables are mainly suitable for permanent routing. MOTION- CONNECT 800PLUS power cables fulfill all of the high mechanical requirements for use in tow chains.
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.3 Current-carrying capacity and derating factors for power cables and signal cables The current-carrying capacity of PVC/PUR-insulated copper cables is specified for routing types B1, B2 and C under continuous operating conditions in the table with reference to an ambient air temperature of 40 °C.
Page 436
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods Routing types B1 Cables in conduits or installation ducts B2 Multi-core cables in conduits or installation ducts C Cables along walls/panels, without conduits or installation ducts Table 10- 14 Derating factors for deviating ambient temperatures Ambient air temperature [°C] Derating factor according to EN 60204-1, Table D1 1,15...
Cabinet design and EMC for components, Blocksize format 10.6 Connection Methods 10.6.4 Spring-loaded terminals Table 10- 15 Spring-loaded terminals Spring-loaded terminal type Connectable cable cross- Rigid 0.2 … 1.5 mm sections Flexible 0.2 … 1.5 mm Flexible with end sleeve without plastic sleeve 0.25 …...
Cabinet design and EMC for components, Blocksize format 10.7 Protective connection and equipotential bonding 10.7 Protective connection and equipotential bonding Protective connections The SINAMICS S drive system is designed for use in cabinets with a protective conductor connection. The protective conductor connection of the SINAMICS components must be connected to the protective conductor connection of the control cabinet as follows: Table 10- 17 Conductor cross-section for copper protective connections Line supply cable in mm...
Page 439
Cabinet design and EMC for components, Blocksize format 10.7 Protective connection and equipotential bonding NOTICE Component destruction as a result of high leakage currents The Control Unit or other PROFIBUS and/or PROFINET nodes can be destroyed, if significant leakage currents flow via the PROFIBUS or PROFINET cable. •...
Cabinet design and EMC for components, Blocksize format 10.8 Arrangement of components and equipment 10.8 Arrangement of components and equipment 10.8.1 General The arrangement of the components and equipment takes account of: ● Space requirements ● Cable routing ● Bending radiuses of the connecting cables MOTION-CONNECT cables, refer to catalog PM21 ●...
Cabinet design and EMC for components, Blocksize format 10.8 Arrangement of components and equipment 10.8.2 Mounting The components should be mounted on a conductive mounting surface to ensure low impedance between the component and the mounting surface. Mounting plates with a galvanized surface are suitable.
Page 442
Cabinet design and EMC for components, Blocksize format 10.8 Arrangement of components and equipment Up to two base components can be mounted in front of one another. For configurations involving more than two base-type components (e.g. line reactor + motor reactor + braking resistor), the individual components must be mounted to the side of the Power Module.
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling 10.9 Information on control cabinet cooling 10.9.1 General Electrical cabinets can be cooled, using among other things with the following: ● filtered fans ● heat exchangers or ●...
Page 444
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling ① Mounting surface ② Discharged air ③ Air intake Figure 10-6 Ventilation clearances AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling 10.9.2 Ventilation The SINAMICS equipment is ventilated separately by means of integrated fans and is in some cases cooled by means of natural convection. The cooling air must flow through the components vertically from bottom (cooler region) to top (region heated by operation).
Page 446
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling ① Cooling units. ② Control cabinet Figure 10-7 Examples of cabinet ventilation If air conditioners are used, the relative air humidity of the expelled air increases as the air in the air conditioner cools and may exceed the dew point.
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling 10.9.3 Power loss of components in rated operation 10.9.3.1 General The tables below show the power loss for components during rated operation. The characteristic values apply for the following conditions: ●...
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling 10.9.3.3 Power loss for line reactors and line filters Table 10- 22 Overview of power loss during rated operation for line reactors and line filters Rated output current I Frame size Line voltage Unit...
Page 449
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling Rated output current I Frame size Line voltage Unit Power loss rated 50/60 Hz Line reactors for Chassis Power Modules 210 A 3-phase 380 ... 480 260 A 3-phase 380 ...
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling 10.9.3.4 Power loss for Power Modules Table 10- 23 Overview of power loss during rated operation for Power Modules Rated output current I /Unit rating Frame size Line voltage Unit Power loss...
Page 451
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling Rated output current I /Unit rating Frame size Line voltage Unit Power loss rated based on I rated Blocksize PM340 0.9 A / 0.12 kW 1-phase 200 ... 240 VAC 0,06 2.3 A / 0.37 kW 1-phase 200 ...
Page 452
Cabinet design and EMC for components, Blocksize format 10.9 Information on control cabinet cooling AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Service and maintenance 11.1 Safety instructions for service and maintenance WARNING Danger to life if the fundamental safety instructions and residual risks are not observed The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death. •...
Service and maintenance 11.2 Service and maintenance for components, Blocksize format 11.2 Service and maintenance for components, Blocksize format 11.2.1 Replacing hardware components Note Hardware components may only be replaced when in the no-voltage state! The following components can be replaced with replacement/exchange components with the same Order No.: ●...
Page 455
Service and maintenance 11.2 Service and maintenance for components, Blocksize format Replacing the fan The fan is available as a spare part and has the order number: 6SL3064-1AC00-0AA0. Disconnect the drive line-up from the power supply. Remove the CU310-2 from the drive line-up (see Chapter Mounting Control Units and Control Unit Adapters (Page 332).) Release the snap hooks on the left and right sides of 4.
Service and maintenance 11.2 Service and maintenance for components, Blocksize format 11.2.3 Replacing the fan on the PM240-2 Fans are available as spare parts for all PM240-2 installation sizes. Note Only trained personnel may replace the fan, observing ESD guidelines. Requirements 1.
Service and maintenance 11.2 Service and maintenance for components, Blocksize format 11.2.4 Replacing the fan on the PM340 Fans are available as spare parts for all frame sizes of PM340. Note Only trained personnel may replace the fan, observing ESD guidelines. Requirements 1.
Page 458
Service and maintenance 11.2 Service and maintenance for components, Blocksize format 1. Remove the fixing screws. 2. Remove the connector. 3. Remove the fan. 4. Insert the new fan. 5. Insert the connector. 6. Tighten the mounting screws (0.4 Nm tightening torque). Figure 11-3 PM340 fan replacement, frame size FSB/FSC (0.4 Nm tightening torque) AC Drive...
Page 459
Service and maintenance 11.2 Service and maintenance for components, Blocksize format Frame sizes FSD/FSE Figure 11-4 PM340 fan replacement, frame sizes FSD/FSE AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 460
Service and maintenance 11.2 Service and maintenance for components, Blocksize format 1. Remove the cover. 2. Remove both connectors and both fans. 3. Insert the new fans and reattach both connectors. 4. Close the cover. AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 461
Service and maintenance 11.2 Service and maintenance for components, Blocksize format Frame size FSF Figure 11-5 PM340 fan replacement, frame size FSF AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 462
Service and maintenance 11.2 Service and maintenance for components, Blocksize format 1. Unfasten the screws and remove the cover. 2. Remove both connectors and both fans. 3. Insert the new fans. Plug in both connectors. Close the cover and fasten the screws (3.0 Nm tightening torque).
The actual intervals at which maintenance procedures are to be performed depend on the installation conditions (cabinet environment) and the operating conditions. Siemens offers its customers support in the form of a service contract. For further details, contact your regional office or sales office.
Page 464
Service and maintenance 11.3 Service and maintenance for Chassis format components ● Screwdriver Torx T20 ● Screwdriver Torx T30 Tightening torques for current-carrying parts When securing connections for current-conducting parts (supply/motor connections, busbars), you must observe the following tightening torques. Table 11- 1 Tightening torques for connecting current-conducting parts Screw...
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.2 Installation equipment Description The installation equipment is used to install and remove the power blocks for Power Modules in the Chassis format. It is used as an installation aid, which is placed in front of and secured to the module. The telescopic guide support allows the withdrawable device to be adjusted according to the height at which the power blocks are installed.
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.3 Replacing components 11.3.3.1 Replacing the Powerblock, Power Module, frame size FX Replacing the powerblock Figure 11-7 Replacing the Powerblock, Power Module, frame size FX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 467
Service and maintenance 11.3 Service and maintenance for Chassis format components Preparatory steps ● Disconnect the drive line-up. ● Make sure the power block is accessible. ● Remove the front cover. Removal The steps for the removal procedure are numbered in accordance with the previous diagram. 1.
Page 468
Service and maintenance 11.3 Service and maintenance for Chassis format components Installation To reinstall, perform the above steps in reverse order. Note Connecting fiber-optic cables The fiber-optic cable plugs must be re-inserted at their original slot. Fiber-optic cables and sockets are accordingly labeled for correct assignment (U11, U21, U31). NOTICE Material damage caused by loose power connections Insufficient tightening torques can result in faulty electrical connections.
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.3.2 Replacing the Powerblock, Power Module, frame size GX Replacing the powerblock Figure 11-8 Replacing the Powerblock, Power Module, frame size GX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 470
Service and maintenance 11.3 Service and maintenance for Chassis format components Preparatory steps ● Disconnect the drive line-up. ● Make sure the power block is accessible. ● Remove the front cover. Removal The steps for the removal procedure are numbered in accordance with the previous diagram. 1.
Page 471
Service and maintenance 11.3 Service and maintenance for Chassis format components Installation To reinstall, perform the above steps in reverse order. Note Connecting fiber-optic cables The fiber-optic cable plugs must be re-inserted at their original slot. Fiber-optic cables and sockets are accordingly labeled for correct assignment (U11, U21, U31). NOTICE Material damage caused by loose power connections Insufficient tightening torques can result in faulty electrical connections.
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.3.3 Replacing the Control Interface Module, Power Module, frame size FX Replacing the Control Interface Module Figure 11-9 Replacing the Control Interface Module, Power Module, frame size FX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 473
Service and maintenance 11.3 Service and maintenance for Chassis format components Preparatory steps ● Disconnect the drive line-up. ● Make sure the power block is accessible. ● Remove the front cover. Removal The steps for the removal procedure are numbered in accordance with the previous diagram. 1.
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.3.4 Replacing the Control Interface Module, Power Module, frame size GX Replacing the Control Interface Module Figure 11-10 Replacing the Control Interface Module, Power Module, frame size GX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 475
Service and maintenance 11.3 Service and maintenance for Chassis format components Preparatory steps ● Disconnect the drive line-up. ● Make sure the power block is accessible. ● Remove the front cover. Removal The steps for the removal procedure are numbered in accordance with the previous diagram. 1.
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.3.5 Replacing the fan, Power Module, frame size FX Replacing the fan Figure 11-11 Replacing the fan, Power Module, frame size FX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 477
Service and maintenance 11.3 Service and maintenance for Chassis format components Description The average service life of the device fans is 50,000 hours. In practice, however, the service life depends on other variables, e.g. ambient temperature, degree of cabinet protection, etc. and, therefore, may deviate from this value in individual cases.
Service and maintenance 11.3 Service and maintenance for Chassis format components 11.3.3.6 Replacing the fan, Power Module, frame size GX Replacing the fan Figure 11-12 Replacing the fan, Power Module, frame size GX AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 479
Service and maintenance 11.3 Service and maintenance for Chassis format components Description The average service life of the device fans is 50,000 hours. In practice, however, the service life depends on other variables, e.g. ambient temperature, degree of cabinet protection, etc. and, therefore, may deviate from this value in individual cases.
Service and maintenance 11.4 Forming the DC link capacitors 11.4 Forming the DC link capacitors NOTICE Damage in the case of long storage periods After being in storage for more than two years, the components may suffer damage when switched on. •...
Page 481
Service and maintenance 11.4 Forming the DC link capacitors Forming circuit The forming circuit can be built using incandescent lamps or, alternatively, resistors. Components required for reforming outside the drive line-up ● 1 fuse switch, triple 400 V / 10 A or double 230 V / 10 A ●...
Page 482
Service and maintenance 11.4 Forming the DC link capacitors Figure 11-13 Forming circuit for 3-ph AC Power Modules with incandescent lamps Figure 11-14 Forming circuit for 3-ph AC Power Modules with resistors AC Drive Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4...
Page 483
Service and maintenance 11.4 Forming the DC link capacitors Figure 11-15 Forming circuit for 1-ph AC Power Modules with resistors Procedure ● Make sure that the device does not receive a power-on command (e.g. from the keyboard or terminal block). ●...
11.5 Spare parts 11.5 Spare parts Spare parts are available on the Internet at: http://support.automation.siemens.com/WW/view/de/16612315 11.6 Recycling and disposal Dispose of the product according to the applicable national regulations. The products described in this Equipment Manual are extensively recyclable on account of the low-toxic composition of the materials used.
Index Line filter, 44 Line reactors, 56 Motor reactors Chassis, 231 Motor reactors, Blocksize, 211 24 V power consumption, 425 Mounting frame, 401 24 V power supply, 422 PM240-2 Blocksize Power Modules, 88 24 VDC overvoltage protection, 423, 424 Power Modules Chassis, 159 Power Modules PM340 blocksize, 121 Safe Brake Adapter, 384 Safe Brake Relay, 378...
Page 496
Index Sensor Module Cabinet SMC30, 369 Dimension drawings Forming the DC-link capacitors, 480 Blocksize line filter, 51 Fuse, 41 Blocksize line reactors, 60 Braking resistors in Blocksize format, 182 Braking resistors, Chassis, 207 Chassis line filter, 52 Chassis line reactors, 63 Heat dissipation, 443 Control Unit Adapter CUA31, 321 Control Unit Adapter CUA32, 331...
Page 497
Index Line connection voltage, 35 Sensor Modules, 447 Line contactor, 43 Power Modules Chassis, 159 Line disconnector, 40 Power Modules PM340 blocksize, 121 Line filter, 44 Power Supply Units, 426 Line frequency, 35 Protection class, 36 Line reactors, 56 Protective connection, 438 Motor reactors Chassis, 231 RCD, 41 Motor reactors, Blocksize, 211...