3.2
Wiring to the control panel
Follow the procedure below to wire one or two
D8125MUX modules to the 9000 Series, and G Series
control panels. For the B9512G, B9512G-E, B8512G,
B8512G-E control panels, see the Control Panels
Installation and System Reference Guide.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
Remove all power (AC and Battery) before
making any connections. Failure to do so
may result in personal injury and/or
equipment damage.
3.2.1
Disconnecting the Battery and Transformer
1.
Disconnect the battery by unhooking the positive
(red) battery lead from the battery.
2.
Unplug the transformer.
Reversed polarity damages the D8125MUX.
Make sure you wire the D8125MUX AUX
and GND terminals to the control panel.
Figure 3:
D8125MUX Wiring Diagram
1 -
D8125MUX on ZONEX 1
2 -
D8125MUX on ZONEX 2
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 3.0 Installation
3.2.2
For Points 9 up to Point 127:
1.
2.
3.
4.
For Points 129 up to Point 247:
1.
2.
3.
4.
Do not connect more than one D8125MUX to ZONEX 1
(IN and OUT terminals) or ZONEX 2 (IN and OUT
terminals).
1
RESET
+
-
+
-
12V
IN
OUT
GND
FIRE MANUAL
PROG
PORT
ZONEX BUS
POWER A
MUX BUS A
WALK TEST
4
3 -
4 -
Wiring Procedure
Connect the GND terminal of the D8125MUX to the
control panel ZONEX COMMON terminal.
Connect the OUT terminal of the D8125MUX
module to ZONEX IN 1.
Connect the IN terminal of the D8125MUX module
to ZONEX OUT 1.
Connect the AUX terminal of the D8125MUX to
ZONEX POWER + terminal.
Connect the GND terminal of the D8125MUX to the
control panel ZONEX COMMON terminal.
Connect the OUT terminal of the D8125MUX
module to ZONEX IN 2.
Connect the IN terminal of the D8125MUX module
to ZONEX OUT 2.
Connect the AUX terminal of the D8125MUX to
ZONEX POWER + terminal.
2
RESET
+
-
+
-
12V
IN
OUT
POWER B
MUX BUS B
ZONEX BUS
ZONEX Common Terminal
Supervised, Power Limited.
+
-
+
-
+
-
+
-
GND
FIRE MANUAL
PROG
PORT
POWER B
POWER A
MUX BUS A
MUX BUS B
WALK TEST
3
5