Table 15; Ds7460(I) Dual Input Multiplex Module; Ds7432 Eight Input Remote Module; Ds7460(I) Point Type Configuration - Bosch D8125MUX Installation And Operation Manual

Multiplex bus interface
Hide thumbs Also See for D8125MUX:
Table of Contents

Advertisement

D8125MUX | Installation and Operation Guide | 4.0
4.10 DS7460(i) Dual Input Multiplex
Module
The DS7460(i) reserves two points on the MUX bus.
Dual input multiplex points can be programmed as
Points 9 through 127 (ZONEX 1) and 129 through 247
(ZONEX 2) (59 per ZONEX, 118 modules) on G Series,
D9412, and D9112: Points 9 through 75 (33 modules)
on G Series, D7412, and D7212; Points 9 through 40
on G Series (16 modules). When programming dual
points, they occupy first an odd point number, then an
even point number. For example, DS7460(i) Modules
must be programmed to occupy Points 9 and 10, not
10 and 11.
When using the D5060 programmer, only
program the odd or first point on the
module. The even or second point is
automatically added.
The DS7460i cannot be used for Point 75
on G Series, D7412, and D7212 or for
Points 127 or 247 on G Series, D9412, and
D9112. Failure to observe these
programming requirements will result in
intermittent missing conditions.
In addition, both points on the DS7460i must have a
Point Index assigned to it when programming the
control panel. If one of the two points is not required
on the device, simply place the 47 kΩ end-of-line (EOL)
resistor on the point input terminals and program the
unused point with the same Point Index. When
programming the point type for the DS7460(i), using
the D5060 Programmer refer to Table 14 for
information on configuring the point type. Tamper
conditions on multiplex points are treated as Missing
conditions by the control panel.
Table 14:

DS7460(i) Point Type Configuration

Device Type
Point Type
DS7460i Dual
6
Input Multiplex
Module
22
Program Multiplex Bus Points
4.11 DS7432 Eight Input Remote
This device type reserves eight points on the multiplex
bus. Each D8125MUX supports fifteen DS7432s on
G Series, D9412, and D9112 Control Panels, up to
eight on G Series, D7412, and D7212 Control Panels,
and up to four on G Series Control Panels. The
DS7432s occupy groups of eight points; however,
when programming the DS7432 with the multiplex
point programmer, program them as four sets of dual
points. For example, if using a DS7432 on the system
for Points 9 through 16, program Points 9, 11, 13, and
15 as dual points with the even points being added
automatically. Program starting point locations for the
DS7432 on G Series, D9412, and D9112 Control Panels
as follows: 9, 17, 25, 33, 41, 49, 57, 65, 73, 81, 89, 97,
105, 113, 121. Refer to Table 15.

Table 15:

ZONEX 1/
ZONEX 2
9/129
17/137
25/145
33/153
41/161
49/169
57/177
65/185
73/193
81/201
89/209
97/217
105/225
113/233
Point Response
121/241
Configurable
(N/O or N/C)
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
Module

DIP Switch Settings

DIP Switch
1
2
3
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Closed
Open
Open
Closed
Open
Open
Closed
Open
Open
Closed
Open
Closed
Open
Open
Closed
Open
Open
Closed
Open
Open
Closed
Open
Open
Closed
Closed
Open
Closed
Closed
Open
Closed
Closed
Open
Closed
Closed
Points 127/128 and 247/248 cannot be
programmed when using DS7432s
(G Series, D9412, or D9112).
4
5
Open
Closed
Closed
Open
Closed
Closed
Open
Open
Open
Closed
Closed
Open
Closed
Closed
Open
Open
Open
Closed
Closed
Open
Closed
Closed
Open
Open
Open
Closed
Closed
Open
Closed
Closed