4.1.2.2

Manual mechanism 2

Operation of manual mechanism 2 (figure 4.1.2.2.1) is purely
manual, with the exception of the motorized stored energy spring
mechanism for the circuit-breaker. The three position disconnec-
tor is mechanically interlocked against the closed circuit-breaker.
Operation of the earthing switch is only possible when the discon-
nector is open, and vice versa.
Fig. 4.1.2.2.1: Manual mechanism 2: Displays and controls
1
OFF button for circuit-breaker
2
ON button for circuit-breaker
3
Switch position indicator for
circuit-breaker
4
Selector lever
5
Opening for disconnector operation
6
Switch position indicator for
disconnector
7
Opening for earthing switch
operation
8
Switch position indicator for
earthing switch
4.1.2.2.1 Operation of the
circuit-breaker
− Mechanical switch position indication is effected by a
graphical symbol (3) in the low voltage compartment door.
− In order to change the switching condition of the circuit-
breaker, press the mechanical OFF button (1) or the me-
chanical ON button (2).
6
8
4
5
7
2
1
3
Manual ZX0 HB 600 en - Revision 05 | 43