CHAPTER 5: SETPOINTS
5.5.4
Auxiliary Relays
3 AUXILIARY
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
PATH: SETPOINTS
S4 OUTPUT RELAYS
[]
MESSAGE
MESSAGE
MESSAGE
The Typical Wiring Diagram on page 3–10 shows relay contacts with no control power
applied. If the
RELAY 3(7) NON-OPERATED STATE
the relay contacts is as shown in the wiring diagram. If the non-operated state is
"Energized", then the state of the relay contacts is opposite to that shown in the wiring
diagram.
FIGURE 5–2: Output Relay 2 Close Logic
3(7) AUX RELAY
RELAY 3 NAME:
Auxiliary
RELAY 3 NON-OPERATED
STATE: De-energized
RELAY 3 OUTPUT TYPE:
Self-Resetting
PULSED OUTPUT DWELL
TIME:
0.1 s
setpoint is "De-energized", then the state of
S4 OUTPUT RELAYS
Range: 16 alphanumeric
characters
Range: Energized, De-
energized
Range: Self-Resetting,
Latched, Pulsed
Range: 0.1 to 6000.0 s in
steps of 0.1
5 - 41